6/28/2019 Page 1 <br /> City of Everett <br /> 10:44:12AM <br /> INSPECTION ACTIVITY REPORT <br /> Permit No. E1906-121 Site Address 5505 EVERGREEN WAY <br /> Applied 6/19/2019 Applicant Lot <br /> Approved 6/19/2019 Owner HENSRUDE SCOTT T&CHRISTY M Block <br /> Issued 6/19/2019 Contractor BRACK ELECTRIC LLC Tract <br /> Parent Permit No. Description UPGRADE A 200A SINGLE PHASE TO 200A THREE PHASE <br /> Notes <br /> Scheduled Completed Tune Inspector Result Remarks Inspector's Comments <br /> 6/24/2019 6/24/2019 ELEC 09-FINAL SKB CORRECTION eTRAKiT Inspection 6/22/2019 6:03 PM Riley Brack <br /> Request PUD needs to reconnect by 11:00 Monday <br /> Contact Name:Riley Brack <br /> Site Address:5505 EVERGREEN WAY <br /> Phone:3606721684 <br /> e-Mail:brackelectric@gmail.com <br /> (6/24/2019 9:27 AM SKB) <br /> Install a number for main bonding jumper. <br /> Install a number for copper to the building <br /> steel and drilling tap the steel and scrape <br /> the paint.Label the AIC on the service. <br /> 6/24/2019 6/24/2019 ELEC 05-SERVICE SKB PARTIAL APPR <br /> 6/25/2019 6/25/2019 ELEC 09-FINAL SKB APPROVAL Rylie 360-672-1684 <br /> 6/25/2019 6/25/2019 ADMIN USE KLC APPROVAL <br /> ONLY** <br /> INSP12 <br /> CRWS YST M <br />