Laserfiche WebLink
Dec. 2nd, 2014 <br /> ARCHITECTURAL DESIGN <br /> ASSOCIATES, PS <br /> 3.Wall section 3/A4.2 should be clarified to show that fire-retardant sheathing is also required <br /> for eave over-hanges and over-framing within 4' of the two hour wall. Section R302.2.2 <br /> a) Revised wall section 3/A4.2 to include a notation for required fire-retardant sheathing <br /> for eave over-hangs and also add notation to elevations sheets A1.1 & A1.1.1 for over- <br /> framing conditions <br /> 4.The two, one-hour walls separating the dwelling units requires mineral fiber per GA No. <br /> 3644. Wall section 3/a4.2 should be revised to show this requirement or a different fire- <br /> resistive wall assembly should be provided. Section R303.2 <br /> a) Have changed the (2) one-hour walls to one 2-hr party wall assembly. Wall section <br /> 3/A4.2 has been updated to reflect this as well as detail 3b/A4.2. <br /> 5.An additional 20-minute door (or approved alternate) should be added to create a hallway <br /> between the 'storage' rooms and garages on the lower floors. The doors into the storage <br /> rooms could then be reduced to a non-rated passage doorway and note stating 'rooms not <br /> to be used as sleeping rooms' should be removed from the plans. Section R302.5.1 <br /> -The CO alarms should be shown in the (new) hallway outside of the sleeping <br /> rooms on the first level. Section R315.1 <br /> -An additional smoke alarm should be shown in the (new) hallway outside of the <br /> sleeping rooms on the first level. Section R314.3 <br /> a) Floor plan A2.2 has been revised to reflect the change showing a "new" hallway off of <br /> the garage and a second 20 min. door into the conditioned space to the rear of the <br /> garage in the 16' wide units <br /> -CO alarm has been shown in the "new" hallway out side of the sleeping rooms <br /> -Additional smoke detector is shown in the "new" hallway out side of the <br /> sleeping rooms <br /> 6.The 2'6"x2'6" slider in the master bathroom of unit #1&6 should be shown as safety glazing. <br /> Section R308.4.5. <br /> a) Window has been called out as Safety glass on plan & window schedule. <br /> 7.Opening windows on the 3 floor front elevation should be shown to be a minimum of 24" <br /> from the finished floor to the actual opening of the window. Section R312.2 <br /> a) Elevation has been revised to reflect this change also the addition of notes on the floor <br /> plan & window schedule on sheet A2.3. <br /> 8.The attic access hatches in units 1 &l, should be shown in an unobstructed, readily <br /> accessible location and not over closet shelves. Section RS07.1 <br /> a) Attic accesses have been move to not be interfered by closet shelves and rod Re:A2.3 & <br /> A2.4 <br /> i, <br />