Laserfiche WebLink
Dec. 5th, 2014 <br /> ARCHITECTURAL DESIGN <br /> ASSOCIATES, PS <br /> 3.Wall section 3/A4.2 should be clarified to show that fire-retardant sheathing is also required <br /> for eave over-hanges and over-framing within 4' of the two hour wall. Section R302.2.2 <br /> a) Revised wall section 3/A4.2 to include a notation for required fire-retardant sheathing <br /> for eave over-hangs and also add notation to elevations sheets A1.1 for over-framing <br /> conditions <br /> 4.The site plan shows approximately 10 feet between buildings D, E and F. Based on that <br /> distance, the eves parallel to the assumed property line should be protected on the <br /> underside by one-hour, fire-resistive construction. Section R302.1 <br /> a) A notation has been added to the building elevation sheet (A1.1) and roof plan sheet <br /> (A2.4) for min. 1-Hr fire protection to underside of eves that are less than 5' from the <br /> assumed property line. <br /> 5.The two-hour walls should be shown to continue to the underside of the over-framed dormer <br /> sheathing between units 2&3. Section R302.2 <br /> a) Elevation sheets A1.1 show & notate the 2-hr wall to continue to the underside of the <br /> over-framed sheathing <br /> 6.An additional 20-minute door (or approved alternate) should be added to create a hallway <br /> between the 'storage' rooms and garages on the lower floors. The doors into the storage <br /> rooms could then be reduced to a non-rated passage doorway and note stating 'rooms not <br /> to be used as sleeping rooms' should be removed from the plans. Section R302.5.1 <br /> -The CO alarms should be shown in the (new) hallway outside of the sleeping <br /> rooms on the first level. Section R315.1 <br /> -An additional smoke alarm should be shown in the (new) hallway outside of the <br /> sleeping rooms on the first level. Section R314.3 <br /> a) Floor plan A2.2 has been revised to reflect the change showing a "new" hallway off of <br /> the garage and a second 20 min. door into the conditioned space to the rear of the <br /> garage in the 16' wide units <br /> -CO alarm has been shown in the "new" hallway out side of the sleeping rooms <br /> -Additional smoke detector is shown in the "new" hallway out side of the <br /> sleeping rooms <br /> 7.The 2'6"x2'6" slider in the master bathroom of unit #1 & 3 should be shown as safety <br /> glazing. Section R308.4.5. <br /> a) Window has been called out as Safety glass on plan & window schedule. <br /> 8.Opening windows on the 3rd floor front elevation should be shown to be a minimum of 24" <br /> from the finished floor to the actual opening of the window. Section R312.2 <br />