Laserfiche WebLink
Nov. 24 th, 2014 <br /> ARCHITECTURAL DESIGN <br /> ASSOCIATES, PS <br /> 9.The glazing at the stair landing in Unit s should be shown to be a minimum of 36" a.f.f or <br /> safety glazing. Section R30S.4.7 . <br /> a) The window in question is show on the elevations (Re:l/A1.1) to be minimum of 36" A.F.F. <br /> & for further clarification a notation has been added to the window on plan sheet A2.2 <br /> 10.Opening windows on the 3 floor front elevation should be shown to be a minimum of 24" <br /> from the finished floor to the actual opening of the window. Section R312.2 <br /> a) Elevation has been revised to reflect this change (Re:1/A1.1) also the addition of notes <br /> on the floor plan & window schedule on sheet A2.3. <br /> 11.The attic access hatches in units 1 && should be shown in an unobstructed, readily <br /> accessible location and not over closet shelves. Section RS07.1 <br /> a) Attic accesses have been move to not be interfered by closet shelves and rod Re:A2.3 & <br /> A2.4 <br /> 12.Deck lateral load connections should be detailed on the plans. Section R507.1 <br /> a) Deck lateral load connections have been indicated on the floor plans where needed, <br /> additionally Detail 1/A4.2 has been revised and detail la/A4.2 has been added for <br /> further clarification. <br /> Sincerely, <br /> Jam . homas, Architect / Owner Matt Sc. - eels, Project Manager <br /> Emai . jthomas@larch-design.net Email: matt@arch-design.net <br /> 2221 Everett Ave Ste#104, Everett, Wa 98201 — Phone: (425) 259-0661 <br /> 33 <br />