Laserfiche WebLink
Electrical Panel Schedule <br /> Location: 1-11,2ND FLOOR VAULT Building: 40-23 Panel Name: 3V22-5UI11 D <br /> Panel Type: G.E.'CCB' AIC Rating(amps): 25,000 Instatlation Date: 1/28/SO <br /> Main Bkr: 600A Revised Circuits: 6abc <br /> Rating: 600A,480Y/277V,3PH,4W Date Revised: 7/15/18 <br /> Br Bkrs: G.E.'TFJ' Engineer: TRAN,THUHA <br /> Feeders: (2)3-1/2"C.(4)350KCM EACH. Job number: 22334128 <br /> From: V22-5/A3(SUB 9-9) Ref Dwg: 140-022-2001-393 Rev: <br /> Rev Ckt Breaker- Wire Load Descdption Amps Location <br /> Date No Amps/Poles Size a b c <br /> 1 a / #4/0 ,�;�� <br /> 1b 225/3 #4/0 3V22-5UH10 '�r��� <br /> 1c / #4/0 <br /> 3a / #4 �� <br /> 3b 70/3 #4 2V22-5UH9 via 45 KVA XFMR 2nd.FLR COL:H/9 <br /> 3c / #4 ' t <br /> 5a / #8 <br /> 5b 50/3 #8 2V22-5UI10.5 via 30 KVA XFMR x, �\ �,: <br /> 5c / #8 <br /> 7a / — <br /> 7b 50/3 — SPARE <br /> 7c / — <br /> 9a / SPACE <br /> 9b / SPACE <br /> 9c / SPACE =;� <br /> 2a / #4/0 <br /> 2b 225/3 #3/0 3V22-5H10 , � <br /> 2c / #4/0 � s;-.< <br /> 4a / #12 <br /> 4b 20/3 #12 TRUCK DOOR,5HP `:���'�;',COL I-11 <br /> 4c / #12 �� <br /> 6a / �y r;; <br /> 07/18 6b 350/3 SPARE 'ka <br /> 6c / \ ,. <br /> 8a / ? <br /> 8b 70/3 ? 2V22-5UH9 VIA 45 KVA XFMR <br /> 8c / ? ;a <br /> 10a / — <br /> 10b 30/3 — SPARE ��%'' <br /> 10c / — y, <br /> � + r=�.. <br /> Total Amperage o.o o.o o.o <br /> Notes: <br />