AIR HAND � ING UNITS .
<br /> GENERAL �OTES ,
<br /> FAN DATA COIL/HEATER DATA FILTER DATA I , PROVIDE MIXING BOX �
<br /> M I N ESP , TSP , CO I L/ 0 P A I R ENTER I NG LEAV I NG GPM % I N I T I AL MAX , REMARKS A (SEE PLANS FOR ARRANGEMENT) .
<br /> MARK LOCATION SERVICE MFR , MODEL CFM FACE MBH KW MIN ,
<br /> CFM I N , I N , RPM HP ELECT , SERV I CE HEATER I N , A I R TEMP, A I R TEMP, MED I UM F I NS/ SERV I CE TYPE EFF , 0 P FACE
<br /> TOTAL O,A , W, G , W, G, (V-PH-HZ) CFM VEL , FPM W � o o OUTPUT LB/HR ROWS FT , ASHRAE IN ,W, G , ELOCIT 2 , HEATING COIL SECTION TO
<br /> F F BE FACE AND BYPASS TYPE ,
<br /> »
<br /> SILKSCREEN ODULAR PREFILTER 2 AT 30 0 , 27 550 VERTICAL ARRANGEMENT NOTE 2
<br /> CLIMATE 20 PSIG 681 THROWAWAY 3 , FAN(S) TO BE PROVIDED WITH
<br /> AHU-201 MEZZANINE WASHER TRANE CHANGER 10, 000 10, 000 0 , 50 1 , 50 620 7 , 5 480-3-60 HEATING 10, 000 588 0 , 16 21 80 640 STEAM LB/HR I 65 BA� � INLET VORTEX DAMPER FOR
<br /> AREA ZE 5 FINAL � � R 85 0 , 45 500 VARIABLE VOLUME APPLICATION ,
<br /> GAME CUSTOM NAT , 2" FLAT NOTE 3 4. PRVIDE INLET DAMPER SECTION, �
<br /> AHU-202 ROOF DINKING WELL BUILT 40,000 40, 000 1 , 85 3 , 0 685 30 480-3-60 HEATING 40, 000 -- 0 , 50 21 90 298� GAS 323g THROWAWAY 30 0 , 27 500 5, PROVIDE RETURN AIR SECTION �
<br /> WITH TOP RETURN AIR INLET , •.
<br /> 3 AXIS NOTE 3 6 , PROVIDE FILTF_R SECTION
<br /> FOAM ROUT GAME CUSTOM NAT . 2" FLAT
<br /> AHU-203 ROOF DETAIL WELL BUILT 65 ,000 65 ,000 2 , 10 3 , 25 595 50 480-3-60 HEATING 65, 000 -- 0 , 50 21 90 4844 GAS 5265 -- -- -- THROWAWAY 30 0 , 27 500 WITH FILTERS ,
<br /> FOAM ROUT
<br /> STOWB I N VBANK RETURN AIR FILTER SECTION ADDED 4-19-07 PUROLATOR
<br /> ASSEMBLY GAME CUSTOM NAT , 2" FLAT '
<br /> AHU-204 ROOF AND TOOL WELL BUILT 65,000 65 ,000 2 , 10 3 , 25 595 50 480-3-60 HEATING 65 ,000 -- 0 , 50 21 90 4844 GAS 5265 -- -- -- THROWAWAY 30 0 , 27 500 MODEL VBA-2 WITH 24 2' X 2' X 4" MARK 80 PLEATED DISPOSABLE FILTERS.
<br /> STORAGE :
<br /> PRESS GAME CUSTOM NAT . 2" FLAT NOTE 3 �
<br /> AHU-205 ROOF AREA WELL BUILT 70 ,000 70 ,000 2 , 10 3 , 25 610 60 480-3-60 HEATING 70, 000 -- 0 , 50 21 90 5216 GAS 5670 -- -- -- THROWAWAY 30 0 , 27 500 ,
<br /> CRUSH CORE
<br /> ROUT, GAME CUSTOM NAT , 2" FLAT
<br /> AHU-206 ROOF gLANKING WELL BUILT 65 ,000 65 ,000 2 , 10 3 . 25 595 50 480-3-60 HEATING 65 ,000 -- 0 , 50 21 90 4844 GAS 5265 -- -- -- THROWAWAY 30 0 , 27 5�0
<br /> STOWBIN
<br /> INSERTS,
<br /> FLAT & HAND GAME CUSTOM NAT . 2" FLAT
<br /> AHU-207 ROOF ROUT, SUB, WELL BUILT 65 ,000 65,000 1 , 85 3 , 0 580 50 480-3-60 HEATING 65,000 -- 0 , 50 21 90 4844 GAS 5265 -- -- -- THROWAWAY 30 0 , 27 500
<br /> SWEEP & SAND :
<br /> AHU-208 ROOF STOWBIN GAME CUSTOM 65 ,000 65 ,000 2 , 10 3 , 25 595 50 480-3-60 HEATING 65 ,000 -- 0 , 50 21 90 4844 NAT , 5265 -- -- -- 2�� FLAT 30 0 , 27 500 VBANK RETURN AIR FILTER SECTION ADDED 4-19-07, PUROLATOR : '
<br /> PCA WELL BU I LT GAS THROWAWAY MODEL VBA-2 WITH 24 2' X 2' X 4" MARK 80 PLEAlED DISPOSABLE FILTERS.
<br /> CRUSH CORE
<br /> ROUT, GAME CUSTOM 65 ,000 65,000 NAT , 2" FLAT
<br /> _ AHU-209 ROOF gLANKING WELL BUILT 2 , 10 3 , 25 595 50 480-3-60 HEATING 65, 000 -- 0 , 50 21 90 4844 GAS 5265 -- -- -- THROWAWAY 30 0 , 27 500
<br /> STOWBIN
<br /> VACUUM FORM PREFILTER 2 FLAT 30 0 , 27 500 NOTE 3
<br /> PAINT/EDGE GAME CUSTOM NAT , THROWAWAY
<br /> AHU-210 ROOF WRAP/COLD WELL BUILT 70,000 70,000 1 , 85 3 , 25 610 60 480-3-60 HEATING 70, 000 -- 0 , 50 21 90 5216 GAS 5670 -- -- BAG
<br /> BOND FINAL FILTER 85 0 , 45 5U0
<br /> PRESS NAT , 2" FLAT NOTE 1 , 3 ,4, 5 ,6 -
<br /> AHU-211 MEZZANINE AREA HASTINGS SBDR-227 45,000 45, 000 2 , 0 2 , 5 660 40 480-3-60 HEATING 45,000 -- 0 , 50 21 90 3353 GAS 3645 -- -- -- THROWAWAY 30 0 , 27 500 ,
<br /> PRESS NAT . FLAT NOTE 1 , 3 ,4, 5 ,6
<br /> AHU-212 MEZZANINE AREA HASTINGS SBDR-227 45, 000 45,000 2 , 0 2 , 5 660 40 480-3-60 HEATING 45,000 -- 0 , 50 ZI 90 3353 GAS 3645 -- -- -- THROWAWAY 30 0 , 27 500 n
<br /> /�
<br /> AHU-213 NOT USED
<br /> �:
<br /> SWEEP & SAND „ NOTE I , 3 ,4, 5 , 6 COIVSTRUCTIOI �J NOTES �X
<br /> 3 AX I S ROUT NAT , 2 FLAT
<br /> AHU-214 MEZZANINE HAND ROUT HASTINGS SBDR-233 54,000 54,000 2 , 0 2 , 5 560 50 480-3-60 HEATING 54,000 -- 0 , 50 21 90 4024 GAS 4374 -- -- FINAL THROWAWAY 30 0 , 27 500
<br /> FOAM BEND � RE-BALANCE AHU TO SCHEDULED VALUES. .
<br /> 3 AXIS ROUT » NOTE I , 3 ,4, 5,6
<br /> AHU-215 MEZZANINE HAND ROUT HASTINGS SBDR-233 54,000 54,000 2 , 0 2 , 5 560 50 480-3-60 HEATING 54, 000 -- 0 , 50 21 90 4024 GAS 4374 -- -- FINAL THROWAWAY 30 0 , 27 500
<br /> FOAM BEND
<br /> MR&D I NSERTS „ NOTE I , 3 ,4, 5 , 6
<br /> AHU-216 MEZZANINE TOOL STORAGEHASTINGS SBDR-233 54,000 54,000 2 , 0 2 , 5 560 50 480-3-60 HEATING 54,000 -- 0 , 50 21 90 4024 NAT , 4374 -- -- FINAL 2 FLAT 30 0 . 27 500
<br /> VAN LOAD SUB GAS THROWAWAY
<br /> ASSY DRILL �
<br /> MACHINE LHD�DIEICH 20 PSIG 494 PREFILTER THROWAWAY 30 0 , 22 500 NOTE 2 '
<br /> AHU-217 MEZZANINE SHOP McQUAY AIR HANDL , 4500 4500 1 , 25 1 , 75 886 2 , 12 480-3-60 HEATING 4500 450 0 , 16 21 8� 278 STEAM LB/HR � 72 r (SPACE IS AN EX-MINSTER PRESS ROOM CONVERTED TO MACHINE SHOP)
<br /> UNIT BHP FINAL BAG 85 0 , 45 5�0 .
<br /> MODULAR PREFILTER FLAT 30 0 , 22 500 NOTE 2
<br /> MINSTER CLIMATE 20 PSIG 494 THROWAWAY
<br /> AHU-218 MEZZANINE PRESSES TRANE CHANGER 7400 7400 1 , 25 2 . 25 849 7 , 5 480-3-60 HEATING 7400 740 0 , 26 21 80 464 STEAM LB/HR I 72
<br /> SIZE 14 FINAL BAG 85 0 , 45 500
<br /> EGRESS » NOTE 4, 6
<br /> AHU-219 MEZZANINE TUNNEL HASTINGS SBD-215 10 , 000 10,000 2 , 0 2 , 5 I100 10 480-3-60 HEATING 10, 000 -- 0 , 50 21 80 745 GAS 810 -- -- FINAL THROWAWAY 30 0 , 27 500
<br /> ENTILATIO
<br /> � EGRESS » NOTE 4, 6 �
<br /> AHU-220 MEZZANINE TUNNEL HASTINGS SBD-215 10, 000 10, 000 2 , 0 2 , 5 I100 10 480-3-60 HEATING 10,000 -- 0 , 50 21 80 745 GAS 81a -- -- FINAL THROWAWAY 30 0 , 27 500
<br /> ENTILATIO �
<br /> POTI-ING „ UNIT PROVIDED FOR SPACE FOR ADDITION OF FUTURE COOLING
<br /> AHU-22 MEZZANINE ROOM MCQUAY CAH006FVA 2400 2400 1 .35 2.68 1650 2 480-3-60 VENTILAT 2400 -- -- -- -- -- -- -- -- -- FINAL 2 FLAT 30 .25 500 COIL AS NEEDED.
<br /> THROWAWA
<br /> ESRC NAT . 2" FLAT NOTE 1 ,6 ( INDIRECT FIRED GAS UNIT)
<br /> AHU-22 ROOF MEZZANINE MCQUAY RAH047C 22 �000 22 ,000 , 75 1 , 8 832 15 480-3-60 HEATING 22,000 0 , 50 56 9� 822 GAS 978 THROWAWAY 30 � 27 500
<br /> ESRC 2800 0 0 , 5 1 , 5 480-3-60 HEATING 2,800 0 , 50 20 72 , 7 160 NAT , 200 2" FLAT �� �,�
<br /> AHU-22 ROOF MEZZANINE TRANE MUA arrC GAS THROWAWAY NOTE 6 ( INDIRECT FIRED GAS UNIT) �� �
<br /> m„� �� � �� � �
<br /> C� � OIJ �
<br /> 600 Stewart �t., �te 1400
<br /> Se�ttle, Washington 98101
<br /> IFC SU MITT��L l�el 206.267.170�
<br /> � o.o�. � � �� F�x 206.267.1701 ;
<br /> SAZAN #500-1782
<br /> SYM REVISION BY APPROVED DATE SYM REVISION BY APPROVED DATE E• LA CHECKED DATE SUBTITLE cuRRENT�337�736 SYMBOL � DATE .�0.06.�7
<br /> ACCEPTABILITY AIR HANDLING UNIT SCHEDULE
<br /> - INSTALLED FILTERED RETURN JM FB 04.19.07 �,ti oF was�Jlt's THIS DESIGN AND/OR
<br /> ��� , �c�,O SPECIFICATION IS APPROVED SHEET
<br /> _ � �. . � ,�,��, ENGINEER TITLE ��s0 �
<br /> A IRC - WBS 2.2.3.5.5 AUTOMATED SILKSCREEN WASHER W3378736 SAZAN 10.06.17 � ,� ' � � �� \,�„ a,PPRovE� BY DEPT. DATE IRC - WBS 2.2.3.5.5 AUTOMATED SILKSCREEN WASHER
<br /> BO���� �..� ���� ����.. ��._. , CHECKED
<br /> � � ��rsTER�1� V U �LD��V ,�,o�o�� JOB N0. COMP N0.
<br /> �'SioNAL�� APPROVED
<br /> 10/06/2017 APPROVED MECHANICAL MASTER EVERETT, Wq °wc No. 40-056-M2-01 :