My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
3503 WETMORE AVE 2019-09-17
>
Address Records
>
WETMORE AVE
>
3503
>
3503 WETMORE AVE 2019-09-17
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
9/17/2019 2:32:44 PM
Creation date
9/17/2019 2:28:07 PM
Metadata
Fields
Template:
Address Document
Street Name
WETMORE AVE
Street Number
3503
Imported From Microfiche
No
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
35
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
RP' <br /> Plan Check No.: 92/36814 <br /> Page Two of Three <br /> 3. Toilets shall be located in clear space a m.nimvm of 30 inches wide <br /> with a minimum clear space of 24 inches in front of the toilet. <br /> Section 511(a). <br /> 4. Attic access opening (minimum 22 inches ty 30 inches) shall be <br /> provided with minimum'clear headroom rf 30 inches. Section 3205(a). <br /> 5. Walls and floor separating swelling snits in the same building shall <br /> be of not less than 1-Hr fire-resistive construction. Section <br /> 1202(b). <br /> 6. A 1-Hr fire-resistive occupancy separation is required between <br /> storage or laundry rooms that are used in c mmon by tenants and the <br /> rest of the building. Section 1202(b). <br /> 7. Every sleeping room below the fourth story shall have at least one <br /> openable window or exterior door conforming to Section 1204 for <br /> emergency escape or rescue, which must open directly onto a public <br /> street or alley, yard or exit court. <br /> 8. Habitable rooms are required to be have a minimum ceiling height of <br /> 7'-6" except as otherwise permitted in Section 1207(a). <br /> 9. Every dwelling shall have at least one room with a minimum floor <br /> area of 120 square feet and other habitable rooms, except kitchens, <br /> shall have an area of not less than 70 square feet. Section 1207(b). <br /> eellS 10. Provide smoke detectors per Section 1210. <br /> 11. A 1-Hr fire-resistive occupancy separation is required between a <br /> boiler room, central heating plant, or hot eater supply boiler and <br /> Croup R, Division 1 Occupancies when serving more than one dwelling <br /> unit. Section 1212. <br /> *4+ <br /> i <br />
The URL can be used to link to this page
Your browser does not support the video tag.