Laserfiche WebLink
IFC 906.2 General requirements <br /> IFC 906.2 General requirements. Portable fire extinguishers shall be selected,installed and maintained in <br /> accordance with this section and NFPA 10. Exceptions: 1.The travel distance to reach an extinguisher <br /> shall not apply to the spectator seating portions of Group A-5 occupancies.2.Thirty-day inspections shall <br /> not be required and maintenance shall be allowed to be once every three years for dry-chemical or <br /> halogenated agent portable fire extinguishers that are supervised by a listed and approved electronic <br /> monitoring,,de ice ro ided that all of the following conditions are met:2.1. Electronic monitoring shall <br /> confirm ti t ; e refcaperly positioned, properly charged and unobstructed. <br /> EVERETT FIRE DEPARTMENT 2811 Oakes Ave. Everett WA 98201 • (425)257-8120• Fax(425)257-8139 -.B•a31?3 <br />