Laserfiche WebLink
Sent viaa-mail <br /> PUBLIC 0 <br /> P W It`�� <br /> WORKS <br /> March 15, 2016 (Updated March 16, 2016) <br /> Ms. Jessica Robinson <br /> Crown Fire Protection <br /> PO Box 12113 <br /> Mill Creek, WA 98082 <br /> Project: Sprinkler permit for Mattress Depot Tenant Improvement <br /> Job Address: 305 SE Everett Mall Way <br /> Plan Review No: K1603-001 <br /> RE: Corrections Letter <br /> Dear Ms. Robinson, <br /> In response to the recent application, the plans have been examined and revisions are required. Although the <br /> sprinkler contractor may not under contract to install the work, three copies of the revisions requested below <br /> are required to obtain a sprinkler permit. <br /> 1. A single check detector is shown in our records at this address-see attached map. A double-check <br /> detector assembly (DCDA) is required for the fire service supply line servicing Mattress Depot. <br /> a. Correspondence dated March 8, 2012 that new suppression work would trigger this requirement <br /> was sent to the owner at the time listed on Snohomish County parcel records. <br /> b. A letter will be required from the owner, if the owner is allowing the tenant to do the work. <br /> c. If a single check detector is currently servicing this area of the building, a Public Works permit <br /> will be required to replace this with a double check assembly Please contact Benyam <br /> Stephanos, Public Works Plan Reviewer, to discuss this requirement, or if you have questions <br /> about Public Works plan review for the fire service. Benyam Stephanos can be reached at 425- <br /> 257-7289. <br /> d. All replacements of a single check detector to a double check detector should be installed by a <br /> private contractor, since the city only installs new services upon request. <br /> e. If a single check assembly will be replaced with a double check assembly, the revised sprinkler <br /> submittal should include three copies of the following, so that the submittal can be reviewed: <br /> i. The fire service for the tenant space should be shown from the tenant space to the city <br /> main, including the cross connection. <br /> ii. A catalog cut indicating the DCDA manufacturer's model in the Backflow Prevention <br /> Assemblies Approved for Installation in Washington State', published by the Washington <br /> State Department of Health, current edition. <br /> iii. A plan and section of the intended location and installation of the DCDA. The DCDA can <br /> be located in an interior or an exterior location, to comply with City of Everett Standard <br /> Construction Drawings 515 or 523, attached. <br /> iv. The model number of the DCDA should be shown on the drawings. <br /> f. The riser room should be identified on the plans. <br /> g. A post indicator valve (PIV) is required if there is not direct access to the riser room from <br /> outside of the building. <br /> h. All plan sheets affected by these revisions. <br />