Laserfiche WebLink
. ,�, <br />NARVEST CHF,I57IAN CEN2ER �e;NNAN7 Drawing Date:12-12-08 � 12/17/08 14:26 <br />Job Name: <br />Location: <br />Drawing Date: <br />Contractor: <br />H3CDRAULIC DESIGN <br />EiARVEST CHRISTIAN CENTER TENNANT <br />830 SE EVERETT MALL �4AY <br />EVERETT, WASHINGTOt7 <br />12-12-OB <br />BURN3 FIRE SYSTEMS <br />PO BOX 1110 <br />GRANITE FALLS, WA 96252 <br />Designer: NICK <br />Calculated By:SprinkCAD <br />www.sprinkcad.com <br />951 N. Cannon Ave. <br />Lansdale, PA 19946 <br />Construction: <br />Reviewing Authorities: <br />SYSTEM DESIGN <br />SHEEi <br />ko��a-oi, <br />C.��Ivl� �cf- I o�e. o✓�.�yJ <br />Remote Area Number: 1 <br />Telephone:l-877-388-0129 <br />Occupancy: <br />SubJectTo Fleld inspectlon <br />�Y 7t�e Fire Marsh�l <br />Code:NFPA 13 Hazard:LIGHT Syst.em Type:WET <br />Area of Sprinkler Oper. 900 sq ft� Sprinkler or Nozzle <br />Density !gpm/sq ft) 0.100 I Make: TYCO <br />Area per Sprinkler 130.0 sq ftl Model: TY-FRB <br />Hose Allowance Inside 0 gpm I K-FacLor: 5.60 <br />Hose Allowance Outside 100 ypm I Temperature Rating: 155 <br />CALCULATION SUMMARY 11 Flowing Outlets <br />gpm Required: 302.8 psi Required: 83.9 @ City Supply <br />WATER SUPPLY <br />Water Flow Test � <br />Date of Test I <br />Static Pressure 89.0 psi � <br />Residual Pres 69.0 psi I <br />At a['low of 2300 gpm I <br />Elevation 10'0" I <br />Pump Data I <br />Rated Capacity 0 gpm I <br />Rated Pressure 0.0 psi I <br />Elevation 0 I <br />Make: I <br />Model: I <br />Location: GVERETT MALL WAY <br />Source of Information: PATRIOT SPRINKLGR PLANS <br />SYSTEM VOLUME 170 Gallons <br />es: <br />: �, ; /; � .,-� <br />