Laserfiche WebLink
2006 W � gton State Nonresidential Energy Code Com �ce Form <br /> . . <br /> 2006 Washington State Nonresidential Energy Code Compliance Forms Revised July 2007 <br /> ProectAddress Date 4/4/2013 <br /> � SE Everett Mall Way <br /> The following information is necessary to check a mechanical permit application for compliance with the mechanical requirements in the <br /> Washington State Nonresidential Energy Code. <br /> Applicability Code Location Building Department <br /> (yes, no, n.a.) Section Component Information Required on Plans Notes <br /> HVAC REQUIREMENTS (Sections 1401-1424) <br /> 1411 Equipment performance <br /> .a. 1411.4 Pkg.elec. htg.&clg. List heat pumps on schedule <br /> yes 1411.1 Minimum efficiency Equipment schedule with type,capacity,efficiency AC-1 <br /> yes 1411.1 Combustion htg. Indicate intermittent ignition,flue/draft damper&jacket loss <br /> 1412 HVAC controls <br /> yes 1412.1 Temperature zones Indicate locations on plans ac-3 <br /> yes 1412.2 Deadband control Indicate 5 degree deadband minimum Ac-i <br /> .a. 1412.3 Humidity control Indicate humidistat <br /> yes 1412.4 Automatic setback Indicate thermostat with night setback and 7 diff. day types r�C-1 <br /> yes 1412.4.1 Dampers Indicate damper location and auto. controls&max. leakage Ac-i <br /> yes 1412.4.2 Optimum Start Indicate optimum start controls <br /> .a. 1412.5 Heat pump control Indicate microprocessor on thermostat schedule <br /> yes 1412.6 Combustion htg. Indicate modulating or staged control AC-i <br /> yes 1412.7 Balancing Indicate balancing features on plans Ac-3 <br /> 1412.8 Ventilation Control Indicate demand control ventilation for high-occupancy areas <br /> yes 1422 Thermostat interlock Indicate thermostat interlock on plans Ac-1 <br /> yes 1423 Economizers Equipment schedule ac-1 <br /> 1413 Air economizers <br /> yes 1413.1 Air Econo Operation Indicate 100%capability on schedule Ac-1 <br /> .a. 1413.1 Wtr Econo Operation Indicate 100%capacity at 45 degF db&40 deg F wb <br /> .a. 1413.2 Water Econo Doc Indicate clg load&water econoe&clg tower performance <br /> yes 1413.3 Integrated operation Indicate capability for partial cooling ac-1 <br /> .a. 1413.4 Humidification Indicate direct evap or fog atomization w/air economizer <br /> 1414 Ducting systems <br /> yes 1414.1 Duct sealing Indicate sealing necessary Ac-1 <br /> yes 1414.2 Duct insulation Indicate R-value of insulation on duct AC-i <br /> .a. 1415.1 Piping insulation Indicate R-value of insulation on piping <br /> 1416 Completion Requirements <br /> yes 1416.2.1 Commissioning Provide commissioning plan Ac-1 <br /> yes 1416.2.2-3 Sys.Bal& Func.Test Indicate air and water system balancing&functional testing r,c-i <br /> yes 1416.2.4 Commissioning Indicate O&M manuals, record drawings, staff training ac-1 <br /> yes 1416.2.5 Comm. RepoR Indicate requirements for prelim. &final commissioning report Ac-i <br /> yes 1434 Separate air sys. Indicate separate systems on plans Ac-i <br /> yes Mechanical Completed and attached. Equipment schedule with types, ac-i <br /> Summary Form input/output,efficiency, cfm, hp,economizer <br /> ections - <br /> 1440 Service water htg. <br /> .a. 1441 Elec.water heater Indicate R-10 insulation under tank <br /> .a. 1442 Shut-off controls Indicate automatic shut-off <br /> 1443 Pipe Insulation Indicate R-value of insulation on piping R-3 <br /> .a. 1452 Heat Pump COP Indicate minimum COP of 4.0 <br /> .a. 1452 Heater Efficiency Indicate pool heater efficiency <br /> .a. 1453 Pool heater controls Indicate switch and 65 degree control <br /> .a. 1454 Pool covers Indicate vapor retardant cover <br /> .a. 1454 Pools 90+degrees Indicate R-12 pool cover <br /> "no' is circle or any question, provi e exp anation: <br />