EXISTING PROTECTION CRITERIA FIRE SPRINKLER SYMBOL LEGEND
<br /> OCCUPANCY HOSE MAXIMUM SPRiNKLER TOTAL NEW SPRINKLERS REQUIRED 7 CONTRACTOR-PROVIDED FIRE SPRINKLERS
<br /> CLASSIFICATION DENSITY ALLOWANCE SPACING DESIGN BASIS TOTAL
<br /> (GPM) (SQ FT) SYMBOL DESCRIPTION SYMBOL SIZE MFR MAKE S.I.N. FINISH STYLE TEMP K-FACTOR �ENTIRE BUILDING)
<br /> CORRIDORS/TENANT SPACES/GROCERY PREP/FOOD TENANT/OFFICES 0.20/1500 SQ FT 250 130 EXISTING DESIGN DENSITY ------ EXISTING BRANCH LINE � 1/2" TYCO TY-FRB TY3231 WHITE RECESSED 155 5.6 4
<br /> (MISCELLANEOUS STORAGE) STYLE 15
<br /> ENTRY VESTIBULES (ORDINARY HAZARD GROUP 2) MINIMUM 0.20/1500 SQ FT 250 130 EXISTING DESIGN DENSITY ------ EXISTING SPRINKLER MAIN � 1/2" TYCO TY-B TY3251 BRASS INTER. 200 5.6 1
<br /> OR ENTIRE AREA PENDENT
<br /> COOLERS/FREEZERS (MISCELLANEOUS STORAGE) MINIMUM 0.20/1500 SQ FT 250 130 EXISTING DESIGN DENSITY NEW SPRINKLER BRANCH LINE Q 1" TYCO DS-C TY3555 WHITE/ CONCEAL 200 5.6 1
<br /> OR ENTIRE AREA CHROME C Y N T E R G Y
<br /> RESTROOMS/BREAKROOMS (LIGHT HAZARD) 0.10/1500 SQ FT 100 225 EXISTING DESIGN DENSITY NEW SPRINKLER MAIN � 1/2" TYCO TY-FRB TY3231 BRASS PENDENT 200 5.6 � CYNTERGY ENGINEERING,P��c
<br /> 810 S CINCINNATI
<br /> HYDRAULIC REFERENCE POINT: REFER TO EXISTING FIRE SPRINKLERS TO REMAIN (UNLESS NOTED OTHERWISE) CONTRACTOR SHALL SECOND FLOOR
<br /> 51 "" DESIGN DRAWINGS FOR EXACT LOCATIONS FIELD VERIFY TULSA,OK 74119
<br /> 918.877.6000
<br /> m EXISTING SPRINKLER RISER SYMBOL SIZE MFR MAKE S.I.N. FINISH STYLE TEMP K-FACTOR --- ��cyntergy.com
<br /> C-- EXISTING CAP �? 1/2" --- --- --- WHITE RECESSED 155 5.6
<br /> STYLE 10 STIPULATION FOR REUSE
<br /> [- NEW CAP <,�j ��Z" --- --- --- BRASS HSW ZOO �J.F> THIS DRAWING WAS PREPARED FOR
<br /> USE ON A SPECIFIC SITE AT EVERETT
<br /> 13 NEW TEE �� WHITE/ irs� ISSUE DATE ONR04/09%8, A D IT
<br /> � � CHROME CONCEAL 200 S.F) --- IS NOT SUITABLE FOR USE ON a
<br /> DIFFERENT PROJECT SITE OR AT A
<br /> SHIELD� --- LATER 11ME. USE OF THIS DRAWING
<br /> � NEW ELL LJ 3/4" --- --- --- BRASS HEAD 155 8.O FOR REFERENCE OR EXAMPLE ON
<br /> GUARD ANOTHER PROJECT REQUIRES THE
<br /> SERVICES OF PROPERLY LICENSED
<br /> o �- NEW INSPECTOR'S TEST/AUXILIARY EXISTING FIRE SPRINKLERS TO BE DEMOLISHED, CONTRACTOR SHALL FIELD VERIFY REP ODUCTION OF THISEDRAWING FOR
<br /> DRAIN REUSE ON ANOTHER PROJECT IS NOT
<br /> AUTHORIZED AND MAY BE CONTRARY
<br /> __�___ NEW BRANCH LINE TO BE INSTALLED SYMBOL SIZE MFR MAKE S.I.N. FINISH STYLE TEMP K-FACTOR --- To �E �aw.
<br /> --n-- NEW OUTLET WITH ARM-OVER X
<br /> � NEW PIPE "UP" OR "DN" WHERE SPRINKLERS ARE CALLED OUT TO "MATCH EXISTING," THE CONTRACTOR SHALL
<br /> C PROVIDE SPRINKLERS MANUFACTURED BY TYCO, WHICH ARE EQUIVALENT TO THE EXISTING
<br /> �
<br /> LONGITUDINAL SEISMIC BRACING TO REMAIN SPRINKLERS. SUBSTITUTIONS WILL NOT BE PERMITTED.
<br /> � VERIFY (12) SALES FLOOR TYPE SPRINKLERS, (4) DRY PENDENT SPRINKLERS, AND (2) OF
<br /> LATERAL SEISMIC BRACING EACH OTHER TYPES OF SPRINKLERS ARE PRESENT IN SPRINKLER CABINETS IN SPRINKLER
<br /> ROOM. PROVIDE ADDITIONAL SPRINKLERS IN SPRINKLER CABINETS AS REQUIRED. ►-a
<br /> � 4-WAY SEISMIC BRACING W
<br /> ABBREVIATIONS O O �
<br /> ,' HANGER TYP TYPICAL ELL ELBOW O O � W
<br /> REF REFER CMU CONCRETE MASONRY UNITS � �p �
<br /> ' REDUCER EVAP EVAPORATOR GPM GALLONS PER MINUTE N ,�
<br /> AHU AIR HANDLING UNIT PSI POUNDS PER SQUARE INCH � �N �
<br /> CONTRACTOR SHALL VERIFY ALL SPRINKLER K-FACTORS, RTU ROOF TOP UNIT MIN MINIMUM �
<br /> MAKES, MODELS, AND FIN�SHES. ALL NEW SPRINKLERS RC REDUCING COUPLING MAX MAXIMUM � W
<br /> ADDED SHALL MATCH EXISTING SPRINKLERS OF THE BOR BASE OF RISER MECH MECHANICAL
<br /> SAME TYPE. FLG FLANGE OR FLANGED HP HORSE POWER � �� U
<br /> GRV GROOVED CONT'D CONTINUED �
<br /> z
<br /> w
<br /> O �
<br /> O �
<br /> � �
<br /> O � �
<br /> 0
<br /> 0
<br /> O �
<br /> a
<br /> � �
<br /> �
<br /> � �-0 1 CONTRACTOR SHALL DROP 1" PIPE TO 12" �
<br /> ,�
<br /> ;� �, �� �� j, ABOVE PICKUP TOWER TO 4'-0" FLEX PIPE.
<br /> ;; ;j; ' r ^ ��� ;; INSTALL PENDENT SPRINKLER INSIDE UNIT. pWq
<br /> " '�'' P� P �ti il EXISTING SPRINKLERS AND BRANCHLINES TO
<br /> �
<br /> iE �;' �
<br /> :I ��� ,�� �! REMAIN. REF 5-FP3. Z
<br /> ��- -- -:o ;
<br /> �' i F�o�� I
<br /> w
<br /> 'j PICKIJP ��; �
<br /> �C H ECK'-I N �-��!'
<br /> � �,
<br /> �; i ,�`�
<br /> �i
<br /> � `�-�I
<br /> � �-11 CONTRACTOR SHALL REMOVE EXISTING PENDENT ISSUE BLOCK
<br /> O CONTRACTOR SHALL ADD NEW PENDENT i j r��; SPRINKLER THAT HAS BEEN PAINTED AND
<br /> SPRINKLERS WHERE SHOWN. UTILIZE EXISTING ��': ' � 04/09/18 PERMIT
<br /> ;; �; I � _ i �) PROVIDE NEW PENDENT SPRINKLER TO MATCH
<br /> �� � i� PIPING WHERE POSSIBLE. COLOR, STYLE AND
<br /> i �;- ; ,
<br /> EXISTING SPRINKLER.
<br /> ;; � �� �� -�-- "���� -��--�-�-��-�- - � --�� K-FACTOR SHALL MATCH EXISTING. r�' �j � �i
<br /> ' ` i� COORDINATE FINAL LOCATIONS OF NEW ;i �-'I i �
<br /> �`�� � k � '��� SPRINKLERS WITH ALL LIGHTS AND OTHER ` !�-'� � TOILET �`
<br /> II � ;I �. '� � ; � � ( � � � Ii
<br /> � � � � ! ,: i � i CEILING EQUIPMENT. ADDITIONAL SPRINKLERS � ��� � �;
<br /> ;j � ��`�'�`' VE TIBULE `'� i ; MAY BE REQUIRED AT NO ADDITIONAL COST TO �� � �- !I 1�
<br /> ' OWNER. REF 6-FP3. (TYP OF 3) '
<br /> VESTI B U LE P I CK U P TOWER AU TO CEN TER T01 LET
<br /> FIRE PROTECTION PLAN FIRE PROTECTION PLAN FIRE PROTECTION PLAN
<br /> 7 3/32" = 1'-0" � 3/32" = 1'-0" � 3/32" = 1'-0"
<br /> 30 X 42 SHEET SET
<br /> CHECKED BY: JMR
<br /> DRAWN BY: JAW
<br /> PROTO: 134 WM
<br /> PROTO CYCLE: 02/23/18
<br /> DOCUMENT DATE: 04/09/18
<br /> CONTRACTOR FIELD VERIFY
<br /> AND SHALL ADD NEW
<br /> GUARD ON SPRINKLER. DOCUMENTS WITHOUT
<br /> SIGNATURE AND REQUIRED
<br /> 11 11.4 12 SEAL OF AOR/EOR ARE
<br /> � NOT FOR CONSTRUCTION
<br /> „ � ._., ;- , I
<br /> - ` � -- �----' I ' ci ; �
<br /> ��. ' � j r � r i 7�� r �
<br /> _��J I 1.� � L� I'J I�� ,�
<br /> ...... i I' I I � I I �+ I
<br /> � � �
<br /> 1 I
<br /> F� I � � ' �_ l�.`JI �
<br /> I � I
<br /> i !
<br /> I I � c J L J ,��� !
<br /> i I
<br /> �
<br /> LJ �
<br /> �I i i
<br /> � �J L J �I � CONTRACTOR SHALL ADD ESCUTCHEON
<br /> P ' i �; � ON SPRINKLER. COLOR, AND STYLE
<br /> o, LUBE AND TI E �` � 6 SHALL MATCH EXISTING. 7
<br /> � � �
<br /> � .,, MOUNTING AR�A LJ i j
<br /> rn ! �� TIRE �� ���� ,"�.-� --- -�-� _ ,..____� ---- _ �;----- - `.;,�
<br /> CONTRACTOR FIELD VERIFY �-�-�' ���-� , ,; , ,
<br /> ,n ' - ; RACKS ,
<br /> � ; AND SHALL ADD NEW ��; ��� ;i ' !' : �) �'
<br /> � I i' ��
<br /> � F-' �, � �� �) GUARDS ON SPRINKLERS. � �, � � �i �! �' > > �� I;
<br /> z TYP OF 5 � � k� �
<br /> � � � �� �� � � � � PRODUCE , 'i�� �J �J i l i� J �' �i CONTRACTOR SHALL ADD ESCUTCHEON
<br /> I�; � �I ;i GROCERY ON SPRINKLER. COLOR, AND STYLE
<br /> Q � LJ LJ�� �
<br /> _ _--- -- _-- - - - � � ;��� C00,ER - ` I - ; A Y - �,'I !I FREEZER i i i'�
<br /> � i � SHALL MATCH EXISTING.
<br /> O - - - ---�-- -- --— - - - --- ---- �` � F � i -' � i, ,, l
<br /> � CONTRACTOR SHALL ADD ESCUTCHEON
<br /> [��- �� � �'�. , � � �R I � � �,; �,-,---, ON SPRINKLER. COLOR, AND STYLE OY SP
<br /> ; � � i � i� COOLER � ii F� � �� �i �� �i S � q
<br /> � � � i I,�� \ ; A i�� � _ �? ,�� ,; ( ;i _�� i SHALL MATCH EXISTING. �C s O
<br /> U � r� r� , I ( \ '�� —q � I! � t �i,' I I � ----- �I�j �Q'� �� �G'
<br /> LyJ � � LJ LJ '�� � � j� � �_�__L-L� � I� 't�� � i�� � �_���� ' ��� i� I� r<<G ���
<br /> � � � z i i � �� � � ' — -- � O
<br /> � i � i �� � �k: _ �� `ti � I _ �� �
<br /> ; �
<br /> ��_m.... . .: _..— __---. .-- ' __..._._ . -- - -- ' � ;i
<br /> _ _ _._. __.— i�
<br /> � � � � H -�- �
<br /> _ ...._ _ ,
<br /> rJ --- — — -
<br /> � L J j i . '��: I I....... .. ��—� �. . j� .
<br /> w � -, -------- ' - ---. ' ' CONTRACTOR SHALL ADD NEW INTERMEDIATE LEVEL �I UPC/ I_; i j =
<br /> � � I � �� ���' CONTRACTOR SHALL ADD ESCUTCHEON CONTRACTOR SHALL ADD NEW DRY PENDENT 6 I INVOICING: i; 35876 �
<br /> i u-� LJ SPRINKLER ABOVE TRASH COMPACTOR CHUTE ' �,
<br /> � � I � � i , I ON SPRINKLER. COLOR, AND STYLE SPRINKLER BEHIND EVAPORATOR. UTILIZE �I' � �, @ �I ,c RF�ISTER�O �
<br /> ., ,. i ., ,. i OPENING. SUPPLY SPRINKLER FROM OVERHEAD i I � �c G��
<br /> � J � ''" ;�� � , � ��; i i i SHALL MATCH EXISTING. EXISTING PIPING WHERE POSSIBLE. COORDINATE �'� i- � � ss/ E�
<br /> , �, ' ( �� - BRANCH LINES. HANG ALL NEW SPRINKLER PIPING ' I ONAL
<br /> � , - -
<br /> � i J L � � FINAL LOCATION OF NEW SPRINKLER WITH ALL K � ; ; FROM STRUCTURE. REF 4-FP3. �(u i
<br /> r
<br /> Q LIGHTS AND OTHER CEILING EQUIPMENT. - - - H
<br /> � � 1 ; , ��RECEIVING
<br /> w ADDITIONAL SPRINKLERS MAY BE REQUIRED AT JAMES ROY SPRADLING
<br /> NO ADDITIONAL COST TO OWNER. REF 3-FP3 ENGINEER OF RECORD
<br /> N FOR ALL INSTALLATION AND SEALING METHODS.
<br /> �
<br /> �
<br /> � LUBE AND TIRE MOUNTING AREA COOLER /FREEZER RECEIVING UPC INVOICING
<br /> � � /
<br /> FIRE PROTECTION PLAN FIRE PROTECTION PLAN FIRE PROTECTION PLAN FIRE PROTECTION PLAN ENLARGED
<br /> L O
<br /> ��' FI R E
<br /> w � � 3/32" = 1'-0" � 3/32" = 1'-0" � 3/32" = 1'-0" � 3/32" = 1'-p„
<br /> � �� PROTECTION
<br /> � �
<br /> � � PLANS
<br /> a�
<br /> � Q EXISTING CONDITIONS WERE TAKEN FROM ORIGINAL EACH SUBCONTRACTOR IS RESPONSIBLE FOR HAVING
<br /> � o DRAWINGS AND MAY NOT REFLECT EXACT A THOROUGH KNOWLEDGE OF ALL DRAWINGS AND
<br /> i � "AS-BUILT" CONDITIONS. CONTRACTOR SHALL FIELD SPECIFICATIONS IN THEIR RELATED FIELD. THE
<br /> � � VERIFY ALL EXISTING CONDITIONS PRIOR TO FAILURE TO ACQUAINT THEMSELF WITH THIS
<br /> o � SUBMITTING FINAL BIDS. CONTRACTOR SHALL KNOWLEDGE DOES NOT RELIEVE THE RESPONSIBILITY
<br /> �' % CAREFULLY COORDINATE NEW WORK AND DEMOLITION OF PERFORMING THE WORK PROPERLY. NO
<br /> o � WITH ALL OTHER DISCIPLINES AND EXISTING ADDITIONAL COMPENSATION SHALL BE ALLOWED SHEET:
<br /> a� CONDITIONS. BECAUSE OF CONDITIONS THAT OCCUR DUE F P 2
<br /> Q j TO FAILURE TO FAMILIARIZE WORKERS WITH THIS
<br /> � KNOWLEDGE.