Stantec Panel
<br /> Name F1CL10 120/208V 3 PH 4W 225A Main CB Type: Panelboard Stantec Consulting Services Inc.
<br /> Location: ELEC RM B10S2 Surface Mounted 10,000 AIC 4100 194th Street SW,Suite 400
<br /> Serves: Double Lugs Lynnwood WA
<br /> # Description Load CB * A B C CB * Load Description # TeL 206.667.0555
<br /> 1# Spare 0.00 20/1 CB X 20/1 CB 0.45 Lighting MRI EAST 2## www.stantec.com
<br /> 3# Spare O.OQ 20/1 CB X 20/1 CB 0.60 Lighting MRl EAST 4#
<br /> Stantec Dist Pnl 5# Spare 0.00 20/1 CB X 20/1 CB 0.30 Lighting MRI EAST 6# COpyC'Ight R@S@CY2C�
<br /> 7# S a re a.00 20/1 CB X 20/1 CB 0.15 Li htin MRI EAST g## . The Contractor shall venfy and be responsible for all dimensions.DO
<br /> Name F1CH2 277/480V 3 PH 4W 400A Main (ugs only Type: Distribution Panel - P g g NOTscalethedrawing-anyerrorsoromissionsshallbereportedto
<br /> Location: ELEC RM B1052 Surface Mounted 65,OOOAIC 9# Spare 0.00 20/1 CB X 20/1 CB 0.00 Spare 10# stantecwithoutdelay.
<br /> The Copyrights to all designs and drawings are the property of
<br /> Serves: Feed Thru Lugs 11# Spa re 0.00 20/1 CB X 20/1 CB 0.00 Spare 12# Stantec.Reproduction or use for any purpose other than thot
<br /> Overcurrentdevice 13 Lighting N.M. SCAN [EBRL] 0.91 20/1 CB X 20/1 CB 0.00 Spare 14# authorizedbyStantecisforbidden.
<br /> # Description Load Size *fype Remarks 15# Lighting N.M. SCAN OJS 20/1 CB X 20/1 CB 0.00 Spare 16#
<br /> 1# Spare 0.00 20A/1P CB 17# Spare 0.00 20/1 CB X 20/1 CB 0.00 Spare 1$# Consultants
<br /> 2# Lighting PATIENT HOLD 1.55 2QA/1P CB 19# Lighting N.M. SCAN 0.90 20/1 CB X 20/1 CB 0.50 Equip MRI C1101 RF FILTER 20#
<br /> 3# Lighting SW LEVEL 1 1.95 20A/1P CB 21# Equip AUTO DOORS NUC. MED. SCAN RMS 1.50 20/1 CB X 20/1 CB 0.50 Equip MRI C1101 RF FILTER 22#
<br /> 4# Lighting SW LEVEL 1 1.65 20A/1P CB 23# Equip AUATO DOOR PAT. HOLD 0.50 20/1 CB X 20/1 CB 0.00 Spare 24#
<br /> 5# Mech FCU-24 MRI EQUIP. RM, 5HP 6.32 20A/3P CB 25# Lighting RAD OA2 20/1 CB X 20/1 CB 0.00 Spare 26#
<br /> 6# Mech FCU-103 SW IDF 3.99 20A/3P CB 27# Spare 0.00 20/1 CB X 20/1 CB 0.00 Spare 28#
<br /> 7# Mech FCU-104 SE IDF 3.99 20A/3P CB 29# Spare 0.00 20/1 CB X 20/1 CB 0.00 Spare 30#
<br /> 8# Mech CRAG1 19.28 35A/3P CB 31# Spare 0.00 20/1 CB X 20j1 CB 0.00 Spare 32# �egend
<br /> 9 X-Ray NUGMED#3 50.50 80A/3P CB [NBNL] 33# Lighting N.M. SCAN XRAY 0.02 20/1 CB X 20/1 CB 0.00 Spare 34#
<br /> 10 Space 0.00 20A/3P 35# Recept SW US RMS 0.36 20/1 CB X 20/1 CB 0.00 Spare 36#
<br /> 11 Space 0.00 20A/3P 37# Spare 0.00 20/1 CB X 20/1 CB 0.00 Spare 38#
<br /> 12# Dist Pnl F1CL8 88.22 175A/3P CB 39# Equip FLYWHEEL CONTROL 0.59 20/2 CB X 20/1 CB 0.00 Spare 40#
<br /> Rev: * Circuit Breaker Code 41# -------FLYWHEEL CONTROL 0.59 ------- --- X 20/1 CB 0.00 Spare 42#
<br /> Revised Ckts Marked * Existing Ckts Marked# CB =Circuit Breaker S= Switching Duty Rev: PH A PH B PH C * Circuit Breaker Code
<br /> Project# G =GFCI M = Motor Ckt Prot Revised Ckts Marked * Existing Ckts Marked # Connected KVA 2.93 3.96 1.75 G =GFCI H = HID Rated
<br /> H = HID Rated F= Fused Switch S=Shunt Trip C= HACR Rated
<br /> File: R:\client\PRMCE\PEMC COLBY CAMPUS\New Master Panel Schedules\Winpanel (on goi C= HACR Rated #=See Note File: R:\client\PRMCE\PEMC COLBY CAMPUS\New Master Panel Schedules\Winpanel (on going schedule) D =Switching Duty #=See Note
<br /> Notes: EXISTING PANEL; PNL BRANCH BREAKERS TO BE SQ-D TYPE PJ [NBNL] = NEW BREAKER, NEW LOAD A=AFCI
<br /> Dem. Dem. Notes: EXISTING PANEL; 200%a RATED NEUTRAL BUS.
<br /> Load Type Conn KVA NEC Demand Factor KVA Amps NEC Feed % NEC Feed Amps PNL MCB TO BE SQ-D TYPE LA-MC PNL BRANCH BREAKERS TO BE SQ-D TYPE QOB [EBRL] = EXISTING BREAKER, REVISED LOAD
<br /> Equip 53J4 x 100% 53.74 65 x 100% 65 Dem.
<br /> Lighting 17.63 x 100% 17.63 21 x 125% 27 Load Type Conn KVA NEC Demand Factor KVA Dem. Amps NEC Feed % NEC Feed Amps
<br /> Mech 41.56 x 100% 41.56 50 125% of Largest 56 Equip 4.19 x 100% 4.19 12 x 100% 12
<br /> Recept 17.64 10 KVA @ 100%, rest @ 50% 13.82 17 x 100% 17 Lighting 4,10 x 100% 4.10 11 x 125% 14 NOt2S
<br /> X-Ray 57.24 Largest @ 50%, next @ 25%, rest @ 10% 26.45 32 x 100% 32 Recept 0.36 10 I<VA @ 100%, rest @ 50% 0.36 1 x 10Q% 1
<br /> 187.81 226 Amps 153.20 184 195 8.64 24 Amps 8.64 24 27
<br /> Stantec Dist Pnl Stantec Panel
<br /> Name F1CL8 120/208V 3 PH 4W 400A Main CB Type: Distribution Panel Name F1CL13 120/208V 3 PH 4W 225A Main CB Type: Paneiboard
<br /> Location: ELEC RM B1052 Surface Mounted 1Q,000 AIC Location: ELEC RM F1223 Surface Mounted 10,000 AIC
<br /> Serves: Single Lugs Serves: Double Lugs
<br /> Overcurrent device # Description Load CB * A B C CB * Load Description #
<br /> # Description Load Size *Type Remarks 1# Recept INJ. 1& INJ. 2 0.72 20/1 CB X 20/1 CB 0.36 Recept US RMS E1137,1138 2#
<br /> 1 Space Q.00 20A/1P 3# Equip THYROID UPTAKE 1.18 20/1 CB X 20/1 CB OJO Equip PAT. HOLD- CRASH CART E. 4#
<br /> 2# Panel F1CL9 35.78 225A/3P CB (NOTE 2} 5 <Multi> N.M. TECH WORK [EBRL� 1.08 20/1 CB X 20/1 CB 0.70 Equip TECH WKRM CRASH CART 6#
<br /> 3# Panel F1CL12 52.44 225A/3P CB (NOTE 2) 7# Recept HOT LAB--WIREMOLD OJ2 20/1 CB X 20/1 CB 0.18 Recept ECG EQUIP ALCOVE $#
<br /> 4# Equip TVSS 0.00 30A/3P CB (NOTE 1) 9# Recept HOT LAB--WIREMOLD OJ2 20/1 CB X 20/1 CB 0.54 <Multi> RAD RM E1177 10#
<br /> 5 Space 0.00 20A/1P 11# <Multi> PAT. HOLD --8D STN, WKSTN, C. E1166 0.54 20/1 CB X 20/1 CB 0.90 Recept RAD RM E1177,TECH WKRM CORR. 12#
<br /> Rev: * Circuit Breaker Code 13# Equip PAT. HOLD --WKSTN 0.18 20/1 CB X 20/1 CB 0.00 Spare 14#
<br /> Revised Ckts Marked * Existing Ckts Marked # CB =Circuit Breaker S= Switching Duty 15# <Multi> PAT. HOLD --8D STN,WKSTN 0.54 20/1 CB X 2Q/1 CB 0.54 <Multi> RAD RM E1175 16#
<br /> Project# G =GFCI M = Motor Clct Prot 17# <Multi> PAT. HOLD --8D STN,WKSTN 0.54 20/1 CB X 20/1 CB 0.90 Recept RAD RM E1175 18#
<br /> H = HID Rated F= Fused Switch 19# <Multi> PAT. HOLD --8D STN,WKSTN 0.54 20/1 CB X 20/1 CB 0.00 Spare 20#
<br /> _ . _ _ _ .
<br /> File: R:\dient\PRMCE\PEMC COLBY CAMPUS\New Master Panel Schedules\Winpanel (on goi C= HACR Rated #=See Note 21# <Multi> DOC. RDNG 0.36 20/1 CB X 20/1 CB 0.36 Recept SW ELEC. RM 22#
<br /> Notes: 200% RATED NEUTRAL BUS. PNL MCB TO BE SQ-D TYPE PG 23# <Multi> DOC. RDNG OJ2 20/1 CB X 20/1 CB 1.45 Equip N.M. TECH WK- PYXIS, REF. 24#
<br /> 1. BREAKER TO BE SQ-D TYPE PG 25# Equip HOT LAB- MW 1.50 20/1 CB X 20/1 CB 0.54 Recept R/F RM E1198 CNTRL 26#
<br /> 2. BREAKER TO BE SQ-D TYPE LA-MC 27# Equip US E1137 1.20 20/1 CB X 20/1 CB 0.54 Recept R/F RM E1198 28#
<br /> Dem. Dem. 29# Equip US E1138 1.20 20/1 CB X 20/1 CB 0.30 Lighting RAD RM 30#
<br /> Load Type Conn KVA NEC Demand Factor KVA Amps NEC Feed % NEC Feed Amps 31# Lighting RAD RM 0.30 20/1 CB X 20/1 CB 0.75 Lighting RAD RM 32#
<br /> Equip 53.74 x 100% 53J4 149 x 100% 149 33# Lighting RAD RM OJ5 20/1 CB X 20/1 CB 0.15 Lighting RAD RM 34#
<br /> Lighting 10.10 x 100% 10.10 28 x 125% 35 35# Lighting RAD RM 0.15 20/1 CB X 20/1 CB 0.02 Lighting XRAY ON LT-RAD RM 36#
<br /> Recept 17.64 10 KVA @ 100%, rest @ 50% 13.82 38 x 100% 38 37# Lighting XRAY ON LT-RAD RM 0.02 20/1 CB X 20/1 CB 0.54 <Multi> DOC. RDNG 38#
<br /> X-Ray 6.74 Largest @ 50%, next @ 25%, rest @ 10% 2.57 7 x 100% � 39# Equip HOT LAB DOOR CONTROLLERS 0.20 20/1 CB X 20/1 CB 0.54 <Multi> DOC. RDNG 40#
<br /> 8$.22 245 Amps 80.23 223 23� 41# Lighting DOC. RDNG 1.60 20/1 CB X 20/1 CB 0.54 <Multi> DOC. RDNG 42#
<br /> Rev: PH A PH B PH C * Circuit Breaker Code
<br /> Revised Ckts Marl<ed * Existing Ckts Marked # Connected KVA 6.35 8.32 10.64 G =GFCI H = HID Rated
<br /> S=Shunt Trip C = HACR Rated
<br /> File: R:\client\PRMCE\PEMC COLBY CAMPUS\New Master Panel Schedules\Winpanel (on going schedule) D =Switching Duty - #=See Note
<br /> A=AFCI
<br /> Notes: EXISTING PANEL; 200% RATED NEUTRAL BUS.
<br /> PNL MCB TO BE SQ-D TYPE LA-MC PNL BRANCH BREAKERS TO BE SQ-D TYPE QOB [EBRL] = EXISTING BREAKER, REVISED LOAD
<br /> dem.
<br /> Load Type Conn KVA NEC Demand Factor KVA Dem. Amps NEC Feed % NEC Feed Amps
<br /> Stantec Panel Equip 11.91 x 100% 11.91 33 x 100% 33
<br /> Name F1CL9 120/208V 3 PH 4W 225A Main CB Type: Panelboard Lighting 4.04 x 100% 4.04 11 x 125% 14
<br /> Location: ELEC RM 61052 Surface Mounted 10,000 AIC Recept 9.36 10 KVA @ 100%, rest @ 50% 9.36 26 x 100% 26
<br /> Serves: Double Lugs 25.31 70 Amps 25.31 70 73
<br /> # Description Load CB * A B C CB * Load Description #
<br /> 1# Spare 0.00 20J1 CB X 20J1 CB OJ2 Recept IP PREP STNS 2#
<br /> 3# <Multi> N.M. SCAN C1147, N.M. TECH WORI< 1.24 20/1 CB X 20/1 CB 0.36 Equip MR CNTRL RM 4#
<br /> 5# Equip N.M. SCAN C1147 COMPUTER 0.50 20/1 CB X 20/1 CB 0.70 Equip MR CNTRL RM CRASH CART 6#
<br /> 7# Equip N.M. SCAN C1146 COMPUTER 0.50 20/1 CB X 20/1 CB 0.72 <Multi> MR CNTRL RM SE WALL 8# R@VISIOn BY Appd. YY.nnnn.o�
<br /> 9# Equip N.M. SCAN C1145 COMPUTER OSO ZO/1 CB X 20/1 CB 0.00 Spare 10#
<br /> 11# Recept N.M. SCAN C1145, C1146 0.90 20/1 CB X 20J1 CB 0.72 Equip PAT. HOLD --8D STN, WKSTN, CCTV 12#
<br /> 13# Recept SW CT PROCED. OJ2 20/1 CB X 20/1 CB 0.54 <Multi> PAT. HOLD --8D STN, CCTV 14#
<br /> 15# Equip SW CT PROCED. LIFT 1.20 20/1 CB X 20/1 CB 0.54 <Multi> PAT. HOLD--8D STN, CCTV 16#
<br /> 17# Spare 0.00 20/1 CB X 20/1 CB 0.54 <Multi> PAT. HOLD --8D STN, CCTV 18#
<br /> 19# Equip CT CNTRL RM --SW 0.36 20/1 CB X 20/1 CB 0.54 <Multi> PAT. HOLD --8D STN, CCTV 20# CONSTRUCTION DOCUMENTS NCA MDJ 1s.12.t3
<br /> 21# Equip CT CNTRL RM --SE 0.54 20/1 CB X 20/1 CB 0.54 <Multi> PAT. HOLD --8D STN, CCTV 22#
<br /> Issued Bv Appd. YY.MM.DD
<br /> 23# Recept MRI WKSTN STORAGE 0.18 20/1 CB X 20/1 CB 0.50 Equip SOIL, HOLD, E1142 CRASH CART 24#
<br /> 25# Equip PAT. HOLD - CRASH CART W. OJO 20/1 CB X 20/1 CB 1.20 Equip US E111b 26#
<br /> NCA MDJ NCA 18.12.13
<br /> 27# Recept SW ELEC RM 0.36 20/1 CB X 20/1 CB 0.50 Equip US TECH WKRM CRASH CART 28# Dwn. Chkd. Dsgn. YY.MM.DD
<br /> 29# Equip IP PREP STN LIFT 1.20 20/1 CB X 20/1 CB 1.20 Equip US E1115 30# Permit-Seal
<br /> Q 31# Spare 0.00 30/2 CB X 30/2 CB 1.60 X-Ray NM SCAN RM C1146 32# -
<br /> � 33# ------- 0.00 ------- --- X ------- --- 1.60 -------NM SCAN RM C1146 34# ��,oF D AS�`��'
<br /> Q 35# Recept MRI PROCEDURE C1101 0.72 20/1 CB X 20/1 CB 0.36 Recept DI DIR OFFICE 36# �'��cz, j,�,��
<br /> m 37# Equip AUTO DOORS CT PROGED. SW RM 1.00 20/1 :GB X 35/3 CB 1.18 X-Ray N.M. SCAN RM C1147 , 38# ��4' � � ;
<br /> 39 Equip X-RAY EPO PUSHBUTTON [NBNL] 0.10 15/1 CB X ------- --- 1.18 -------N.M. SCAN RM C1147 40#
<br /> �
<br /> � 41 Space Q.00 0/1 X ------- --- 1.18 ------N.M. SCAN RM C1147 42#
<br /> � Rev: PH A PH B PH C * Circuit Breaker Code 38180
<br /> � ��.� ��GI STER �
<br /> 0o Revised Ckts Marked * Existing Ckts Marked # Connected KVA 9J8 8.66 8.70 G =GFCI H = HID Rated �SSIONAL ��1�
<br /> N S=Shunt Trip C= HACR Rated CZr�3��
<br /> � File: R:\client\PRMCE\PEMC COLBY CAMPUS\New Master Panel Schedules\Winpanel (on going schedule) D =Switching Duty #=See Note
<br /> � A =AFCI
<br /> ient Pro�ec
<br /> o Notes: EXISTING PANEL; 200% RaTEo rvEurRa�Bus. PROVIDENCE REGIONAL MEDICAL
<br /> w PNL MCB TO BE SQ-D TYPE LH-MC PNL BRANCH BREAKERS TO BE SQ-D TYPE QOB [NBNL] = NEW BREAKER, NEw �oao CENTER EVERETT - COLBY CAMPUS
<br /> �
<br /> � Dem.
<br /> o Load Type Conn KVA NEC Demand Factor KVA Dem. Amps NEC Feed % NE� Feed Amps NUC MED #3 REPLACEMENT
<br /> � Equip 13.92 x 100% 13.92 39 x 100% 39
<br /> ,,; Recept 6.48 10 KVA @ 100%, rest @ 50% 6.48 18 x 100% 18
<br /> N X-Ray 6.74 Largest @ 50%, next @ 25%, rest @ 10% 2.57 7 x 100% 7 EVERETT, WA
<br /> � 27.14 75 Amps 22.97 64 64
<br /> i
<br /> �
<br /> Tit e
<br /> � PANEL SCHEDULES
<br /> Q
<br /> �
<br /> �
<br /> 0
<br /> N
<br /> /
<br /> �
<br /> �
<br /> O
<br /> Y Project No. Scale
<br /> 3 204820937 N O N E
<br /> �
<br /> � Drawing No.
<br /> �
<br /> 0
<br /> �
<br /> � E
<br /> �
<br /> � '
<br /> �
<br /> ORIGINAL SHE=T-ARCH E1