SPECIFICATIONS <br /> SECTION 260100 - GENERAL PROVISIONS C. EXISIING SYSTEM DRAWINGS C. PROVIDE PULLWIRE IN ALL EMPTY RACEWAYS. <br /> THE DRAWINGS SHOW PORTIONS OF THE EXISTING SYSTEMS WHICH ARE DERIVED FROM RECORD DRAWINGS. Stantec Consulting Services Inc. <br /> PROVIDE COMPLETE AND FULLY OPERATIONAL ALL ELECTRICAL SYSTEMS WITHIN THE PROJECT AREA, ALONG THE DRAWINGS ARE INCOMPLETE AND NO GUARANTEE IS MADE TO THEIR CORREC7NESS. THE CONTRACTOR D, INTERIOR RACEWAYS: ELECTRICAL METALLIC TUBING (EMT) WITH STEEL COMPRESSION OR SE� SCREW 4100194th Street SW,Suite 400 <br /> WITH POWER CONNECTIONS TO EQUIPMENT FURNISHED UNDER OTHER DIVISIONS OF THE SPECIFICATIONS. SHALL ASSUME THERE IS 20� MORE ELECIRICAL SYSTEMS THAN SHOWN ON THE DEMOLITION AND EXISIING FITTINGS. INDENTOR, DRIVE-ON AND PRESSURE CAST ON DIE CAST TYPE SET SCREW FITTINGS ARE NOT <br /> SYSTEM DRAWINGS. ACCEPTABLE. �ynnwood WA <br /> A. CODES: Tei. 206.667.0555 <br /> CONFORM TO THE NAl10NAL ELECTRICAL CODE AND ALL OTHER CODES AND REGULATIONS AS ADOPTED AND D. DEMOLITION WORK E. RACEWAY PENETRATIONS: PENETRAIIONS THROUGH FIRE RATED CONSTRUCTION SHALL BE SEALED USING WWWstantec.com <br /> AMENDED BY THE STATE OF WASHINGTON AND CITY 0�' EVERETT INCLUDING THE AMERICANS WITH DISABILIIIES CONTRACTOR SHALL REMOVE ALL ELECTRICAL EQUIPMENT IN THE AREA BEING REMODELED WHICH IS NO 3M FIRE BARRIER CAULK, NEL50N ELECTRIC FLAMESEAL OR T & B FLAMESAFE. <br /> ACT (ADA). LONGER IN SERVICE PRESENTLY OR AS A RESULT OF THIS CONTRACT. THE DEFINITION OF ELECTRICAL Copyright Reserved <br /> EQUIPMENT IS ANY EQUIPIuIENT MENTIONED IN THE NATIONAL ELECTRICAL CODE. r. PROVIDE AND SIZE OUTLET BOXES FOR DEVICES SUCH AS RECEPTACLES, SWITCHES AND LIGHT FIXTURES fy p nsible for all dimensions.DO <br /> The Contractor shall veri and be res o <br /> AND PULL BOXES AS REQUIRED IN THE CONDUIT SYSTEM PER THE NATIONAL ELECTRICAL CODE. NOT scale the drawing-any errors or omissions shall be reported to <br /> �. PERMITS AND FEES: stantec without de�ay. <br /> CONTRACTOR 70 OBTAIN AND PAY FOR ALL REQUIRED LICENSES, PERMITS AND INSPECTIONS. E. PREMIUM TIME CONTRACTOR SHALL COORDINATE IMTH 6ENERAL CONTRACTOR TO DETERMINE ANY SPECIALTY INSTALLATION The copyrights to a��designs and drawings are the property ot <br /> PREMIUM TIME SHALL BE INCLUDED IN THE BASE BID FOR ELEC7RICAL SYSTEM(S� OUTAGES AND FOR OTHER REQUIREMENTS DUE TO FIRE RATINGS, CORE WALLS, ETC. Stantec.Reproduction or use for any purpose other than that <br /> WORK AS REQUIRED BY THE SCHEDULE, AS SHOWN ON THE DRAWINGS AND AS NOTED IiV OTHER DIVISIONS authorized by Stantec is forbidden. <br /> C. COORDINATION: OF THE SPECIFICA710NS. G. INTERIOR WIRING: PRESSED STEEL, ZlNC GOATED WIThI PLASTER RING WHERE APPLICABLE. MOUNT <br /> CONTRACTOR TO COORDINAiE ELEC�RICAL W�RK WITH OTNER TRADES. OUTLET BOXES FOR RECEPTACLES AND OTHER DEVICES AT 18", UNLESS OTHERWISE NOTED. Consultants <br /> D. WARRANTY: F. WORK OUTSIDE OF REMODEL AREAS <br /> PROVIDE WARRANTY FOR ONE FULL YEAR AFTER COMPI.ETION. CAUTION - THIS WORK IS NOT SHOWN ON THE CONTRACT DOCUMENTS. PROVIDE NEW WIRING SYSTEMS IN SECTION 262726 - WIRING DEVICES <br /> CONCEALED CEILING SPACES TO SWITCHBOARDS, PANELBOARDS, COMMUNICAIION AND SIGNALING AND SYSTEM <br /> CONTROL PANELS. PRO�DE NEW CONDUIT SYSTEMS IN CEILING SPACES OF FLOOR BELOW REMODEL FLOORS. A. RECEPTACLES: PROVIDE HOSPITAL GRADE RECEPTACLES IN ALL PATIENT CARE AREAS, OPERATING ROOMS, <br /> E. CONTRACT DRAWINGS: REMOVE AND RELOCATE ELECTRICAL EQUIPMENT IN THE WAY OF OTHER TRADES WORK INSTALLED UNDER THIS PATIENT CORRIDORS, WORK ROOMS, EQUIPMENT ROOMS, UTILITY ROOMS, PAl1ENT PREPARATION ROOMS, EXAM <br /> RACEWAYS AND OUTLE7 BOXES ARE SHOWN DIAGRAMMATICALLY ONLY AND THE LAYOUT DOES NOT CONTRACT. SPACES ABOVE EXISTING CEILINGS ARE HIGHLY CONGESTED. ROUTE WIRING AROUND ROOMS AND NURSES STATIONS. PROVIDE 15 AMP RECEPTACLES IN ALL LOCATIONS EXCEPT PROVIDE 20 AMP <br /> NECESSARILY SHOW THE 70TAL NUMBER OF RACEWAYS NOR THEIR EXACT LOCATION. THE CONTRACTOR SHALL OBSTRUCTIONS AND PROVIDE PULL BOXES RER CODE. RECEPTACLES ON DEDICATED 20 AMP CIRCUITS. <br /> PROVIDE ALL RACEWAYS, BOXES, CABLES, AND OTHER MATERiALS REQUIRED FOR THE COMPLETE ELECTRICAL Legend <br /> SYSTEMS SHOWiV OR INDICATED ON THE CONTRACT DRAWINGS. G. EXIST1iVG MATERIALS <br /> B. IDENTIFICATION: <br /> ALL MATERIALS WHICH ARE A PART OF THE BUILDING SHALL REMAIN THE PROPERTY OF THE OWNER. RECEPTACLE D€VICE PLATES SNALL BE LABELED �ELOW WITH PANELBOARDS AND CIRCUlT NUMBER (BLACK <br /> F. RECORD DRAWINGS: <br /> AT THE CONCLUSION OF CONTACT WORK, PROVIDE THE OWidER WITH A COMPLETE SET OF REPRODUCIBLE H. EXISTING MATERIALS TO BE REINSTALLED FILLED LETTERS). RECEPTACLE COVERPLATES FOR RECEPTACLES OTHER THAN 15 AND 20 AMP SHALL BE <br /> DRAWINGS WITH ALL CHANGES CLEARLY AND LEGIBLY MARKED TO REFLECT THE AS-BUILT CONDITIONS. THESE LABELED WITH AMPERE RAl1NG, VOLTA6E AND PHASE. U1ILIZE MACHINE PRINTED ADHESIVE FILM LABELS BY <br /> DRAWINGS SHALL BE LABELED "AS-BUILT" AND CERTIFIED BY THE CON7RACTOR FOR ACCURACY. EXISTING MATERIALS AND EQUiPMENT (EXCEPT INTERIOR, UNDAMAGED RACEWAYS) THAT ARE REMOVED AS A THERMAL TRANSFER OR EQUIVALENT PROCESS. <br /> PART OF THE WORK OR STORED IN SURPLUS SHALL NOT BE REINSTALLED AS A PART OF THE NEW SYSTEMS <br /> UNLESS SPECIFICALLY NOTED OR AUTHORIZED IN WRI7ING BY THE OWNER. FORWARD A COPY OF THE SECTION 266020 - IMAGING SYSTE�1 <br /> G. MAINTENANCE MANUALS: AUTHORIZATION TO THE EPIGIPIEER. THE REQUIREMENTS OF THE SPECIFICATIONS (I.E., CONDITION, <br /> COMPLETE FOR EVERY SYSTEM. HARDBOARD COVERS WITH 3 RING BINDERS. INSTALLATION, TESTING, ETC.) SHALL APPLY AS IF THE MATERIALS WERE NEW, FURNISHED BY THE <br /> CONTRACTOR. A. SYSTEM MANUFACTURER�S DRAWINGS AND SPECIFICATIONS: <br /> H. QUALITY ASSURANCE: <br /> I. EXISIING MATERIALS NOT TO BE REINSTALLED 1. THE SYSTEMS INSTALLATION DRAWINGS BY SIEMENS ARE NOT A PART OF THE CONTRACT DOCUMENTS BUT <br /> 1. MATERIALS AND SYSTEMS: PROVIDE UL LISTED AND LABELED MATERIALS WHERE LISTING SERVICE 15 ALL MATERIAL TO BE DEMOUSHED AND DEBRIS SHALL BE LEGALLY DISPOSED OF BY THE CONTRACTOR. WILL �E AVAILABLE DURING CONSTRUCTION. THESE DRAWINGS AND THE MANUFACTURER'S VERBAL <br /> NORMALLY PROVIDED FOR A GIVEN PRODUCT. PROVIDE NEW AND SHIP TO JOBSITE IN ORIGINAL INSTRUCTIONS SHALL BE ADHERED TO AS DIRECTED BY THE ARCHITECT (NOTIFY THE ARCHITECT PRIOR TO <br /> MANUFACTURER�S CONTAINERS OR BUNDLES. J. EXISTING RACEWAYS DOING ANY WORK) IF THE MANUFACTURER'S INSTRUCTIONS REQUIRE A CHANGE IN THE CONTRACT PRICE. <br /> 2. WORKMANSHIP: ARRANGE WORK TO OBTAIN COORDINA7ED INSTALLATION. 1. THE CONTRACTOR MAY REUSE THE EXISTING RACEYVAYS IF NO OTHER SYSTEMS OCCUPY 1}iE RACEWAY, 8• WIRE: <br /> RACEWAYS AND ENCLOSURES ARE ELECTRfCALLY AND MECHANICAL:LY CONTINUOUS AND NEW WIRING IS Notes <br /> 3. ROUTING: EXACT ROUTING OF WIRING AND LOCATIONS OF OUTLETS, PANELS, ETC. SHALL BE GOVERNED PROVIDED. NO WARRANTY IS MADE AND THE CONTRACTOR SHALL ASSUME THE RISK OF USING EXISTING 1. WIRE WHICH IS USED FOR INTERCONNECTING MRI EQUIPMENT SHALL BE STRANDED COPPER TYPE THHN <br /> BY STRUCTURAL CONDITIONS, OBSTRUCTIONS AND EXISTING CONDITIONS. ARCHITECT RESERVES THE RIGHT AT OUTLET BOXES AND RACEWAY SYSTEMS. INSULATION. <br /> NO INCREASE IN PRICE, TO MAKE REASONABLE CHANGES IN LOCATIONS OF ELECTRICAL ITEMS EXPOSED AT <br /> CEILING AND/Oft ON '�JAtLS. 2. TiiE CONTRACTOR ShALL RELOCATE EXfSTING RACEWAYS fN TNE AREA OF WORK AS REQUIRED �0 C. BOXES IN THE IMAGING EXAM R00!�: <br /> SUPPORT INSTALLATION OF MECHANICAL EQUIPMENT. IT IS THE RESPONSIBILITY OF THE ELECTRICAL <br /> I. COORDINATION: CONTRACTOR TO COORDINATE WITH MECHANICAL CONTRACTOR TO DETERMINE THE EXTEN7 OF EXISTING 1. SHALL �E FLUSH MOUNTED WITH 1/2" (MINIMUM) COVER OVERLAP ON ALL SIDES. ALL COVERS SHALL <br /> CONDUITS THAT NEED TO BE RELOCATED BE REMOVABLE. <br /> 1. WORK OUT ALL "T1GHT" CONDI110NS INVOLVING WORK UNDER THIS CONTRACT IN ADVANCE OF <br /> 1NSTALLATION. K. EXISTING CONDITIONS D. WIRES AND CA�LES <br /> EXAMINE THE STRUCTURE, BUILDING, AND CONDITIONS UNDER WHICH ELECTRICAL WORK IS TO BE INSTALLED <br /> 2. COORDINATE ALL ELECTRICAL POWER AND CONTROL WIRING REQUIREMENTS OF MECHANICAL EQUIPMENT. FOR CONDITIONS DE7RIMENTAL TO PROPER AND TIMELY COMPLETION OF ELECTRICAL WORK. DO N07 PROCEED 1. INT�RCONNECTING WIRES AND CABLES SHALL BE CONTINUOUS BETWEEN EACH WIRING TERMINATION POINT. <br /> WITN WORK UNTIL DEFICIENCIES OR DETRIMENTAL CONDITIONS HAVE BEEN CORRECTED. REPORT DEFICIENCIES LENGTH OF WIRE RUNS SHALL INCLUDE THE DISTANCE THE WIRES WILL RUN IN THE WIREWAY AND <br /> 3. CONFIRM ALL ELECTRICAL EQUIPMENT AND SYSTEM PROGRAMMING NOMENCLATURE REQUIREMENTS WITH �R DETRIMENTAL CONDITIONS OF EXISTING ELECTRICAL WORK WHICH MIGHT BE UNSUITABLE TO CONNECT WITH INTERCONNECTING RACEWAY P�US THE VERTICAL DISTANCE FROM THE WIREWAY TO THE WIRING 7ERMINATION <br /> OR RECEIVE OTHER WORK. FAILURE TO SO REPORT SHALL CONSTITUTE ACCEPTANCE OF OTHER WORK AS POINT. IN ADDI110N, PROVIDE 8 FEET OF SLACK WIRE AT EA�H �OX, CONDUIT STUB UP AND WIRING <br /> THE OWNER PRIOR TO SUBMITTALS AND ROUGH-IN. CONFORM TO ALL NAMING CONVENTIONS DEFINED BEING FIT AND PROPER FOR THE RECEPTION OF ELECTRICAL WOFtK. TERMINATION POINT. <br /> THROUGHOUT THE PROJECT. <br /> L. EXISTING SYSTEMS MAINTAINED 2. COLOR CODE POWER, NEUTRAL AND GROUND WIRES IN ACCORDANCE WITH NEC ARTICLE 310. <br /> GENERAL <br /> SECTION 260126 - TESTING REROUTE EXISTING CIRCUITS THAT ARE INTERRUPTED AS A RESULT OF THIS CONTRACT THAT SERVE DEVICES <br /> TO REMAIN IN SERVICE. 3. RING OUT AND IDENTIFY ALL WIRE RUNS AT 60TH ENDS AND L�AVE READY FOR TERMINATION BY SYSTEM <br /> A. FURNISH ALL LABOR AND TEST EQUIPMENT AS REQUIRED UNDER THIS SECTION. MANUFACTURER'S INSTALLATION CREW. IDENTIFICATION SHALL UTILIZE BRADY °PERMA CODE" WIRE MARKERS. <br /> INFORMATION SHALL INCLUDE ORIGINATING 60X NUMBER (SEE DRAWINGS) AND A SEPARATE LETI�ER FOR EACH <br /> 1. POWER CIRCUITS WIRE WHICH IS A PART OF THE RUN. <br /> B. FACILITIES ENGiNEERING REPRESENTATIVE NEEDS TO BE PRESENT FOR FINAL TESTING. <br /> TRACE OU7 AND IDENTIFY LOADS AND SYSTEMS BEING SERVED. E. RACEWAY ONLY: <br /> C. TEST ALL PANELS AND/OR BRANCH CIRCUITS FOR GROUNDS OR SHORTS. REPAIR DEFECTIVE WIRING AS PROVIDE TEMPORARY WIRING, 5CHEDULE OUTAGE AND RECONNECT LOADS TO TEMPORARY WiRiiJG. <br /> REQUIRED. TEST EACH INDIVIDUAL CIRCUIT AT PANEL FOR PROPER OPERATION. PROVIDE NEW WIRING IN NEW LUCATION. 1. WHEN RACEWAYS ONLY ARE SHOWN ON THE DRAWINGS PROVIDE A MEASURING PULL TAPE IN EACH <br /> SCHEDULE OUTAGE, DlSCONNECT TEMPORARY WIRING, AND CONNECT LOADS TO NEW WIRING. RACEWAY SHOWING THE TOTAL RACEWAY LENGTH. <br /> D. AT COMPLE�ION OF WORK, PROVIDE WRITTEN CERTIFICATION THAT ALL SYSTEMS ARE FUNC110NING <br /> PROPERLY WITHOUT DEFECTS. <br /> M. DEMOLITION <br /> ELECIRICAL EQUIPMENT FREE STANDING OR SURFACE MOUNTED, RACEWAY (EXPOSED) AND CONDUCTORS; <br /> WHICH ARE NO LONGER IN SERVICE PRESEN7LY OR AS A RESULT OF THIS CONTRACT SHALL BE REMOVED. <br /> SECTION 260504 - BASIC MATERIALS AND METHODS UNUSED FLUSH MOUNTED DEVICES, OUTLET AND O7HER BOXES IN FINISHED AREAS SHALL BE REMOVED FROM <br /> WALL AND THE REMAINING HOLE PATCHED TO MATCH ADJACENT WALL SURFACES. UNUSED RACEWAYS AND <br /> INCLUDES GENERAL REQUIREMENTS FOR MATERIALS AND INSTALLATION ME7HODS, CUTTING BUILDING SLEEVES EMBEDDED IN CONCRETE SHALL BE CUT FLUSH AT CEILING, FLOQR OR WALL AND FILLED WITH <br /> CONSTRUCTION, PAINTING, CLEAN-UP, AND WORKMANSHIP. GROUT. ALL UNUSED RACEWAYS ABOVE CEILINGS SHALL BE REMOVED. CONTRACTOR SHALL REMOVE ALL <br /> FLOOR, WALL OR CEILING MOUNTED ELECTRICAL EQUIPMENT IN THE "DEMOLITION AREA" INDICATED ON THE <br /> A. MATERIALS: DRAWINGS EVEN IF THE EQUIPMENT/OR DEVICE IS NOT SHOWN ON THE PROJECT DRAWINGS. IF CONTRACTOR <br /> ALL MATERIALS SHALL BE NEW F�EE FROM DEFECTS, AND SHALL HAVE BEEN TESTED AND LISTED BY QUES710NS WHETHER A PARTiCULAR DEVICE IS TO BE REMOVED NOTIFY THE ENGINEER NOTING TYPE AND <br /> UNDERWRITERS LABORATORIES OR OTHER APPROVED TESTING ORGANIZATION AND SHALL BE SO LABELED. LOCATION OF DEVICE. IF SO DIRECTED THE CONTRACTOR SHALL MAINTAIN THE EXISTING DEVICE IN SERVICE <br /> WITHOUT ANY CHANGE IN CONTRACT PRICE. <br /> S. SUBSTITUTIONS: <br /> SHALL BE REVIEWED BY TNE ENGINEER. N. POWER OU7AGES <br /> 1. SCHEDULED OUTAGES. THE EXISTING FACILITY WILL CONTINUE ITS NORMAL OPERATION DURING THE <br /> C, WORKMANSHIP: CONSTRUCTION WORK; THEREFORE IT IS REQUIRED THAT 1NE CONTRACTOR SCHEDULE ELECTRICAL SYSTEM(S) <br /> SHALL �E OF THE BEST QUALITY AND PERFORMED BY EXPERIENCED ELECTRICIANS UNDER SUPERVISION OF AN �UTAGES WITH THE OWNER. SUBMIT A WRITTEN REQUEST FOR A POWER OUTAGE AT LEAST ONE WEEK IN <br /> EXPERIENCED FQREMAN. ADVANCE IDENTIFYING THE AREAS, AND SYSTEMS THAT WILL BE AFFECTED, TIME AND DURATtON OF THE <br /> POWER OUTAGE. 1`HE CONTRACTOR SHAI1 RECEIVE WRITTEN AUTHORIZATION TO PROCEED Wll�i THE OUTAGE <br /> AND SHALL RE-NOTIFY THE OWNER VER�ALLY AT LEAST ON� HOUR PRIOR TO THE OUTAGE AND ALSO <br /> D. NOISE TRANSMISSION: NOTiFY THE OWNER WHEN THE OUTAGE IS COMPLETED: <br /> TO PREVENT NOISE TRANSMISSION (IN NEW CONSTRUCTION) BETWEEN ADJOINING ROOMS, ALL DEVICES ON <br /> OPPOSITE SIDES OF WALL TO BE SPACE A MINIMUM OF 6" APART (HORIZONTALLY PREFERRED). 2. UNSCHEDULED OUTAGES. IN THE EVENT THAT TNE CONTRACTOR'S WORK CAUSES OR CONTRIBUTES TO AN <br /> UNSCHEDULED SYSTEM(S) OUTAGE (OR OTHER SYSTEM FAULT), THE CONTRACTOR IS RESPONSIBLE FOR <br /> E. BRANCH CIRCUIIING: IMMEDIATELY CORRECTING THE PR08LEM. INCLUDED {AS EXAMPLES} SHALL BE ANY PREMIUM TIME REQUIRED <br /> NO MORE THAN SIX CURRENT CARRYING CONDUCTORS IN ANY ONE (1) HOMERUN. TO STAY ON THE J08 SITE UNTIL PROBLEM IS CORRECTED AND AIR FREIGHT FOR PARTS NOT LOCALLY <br /> AVAILABLE. <br /> �. GROUNDING: <br /> PROVIDE SEPARATE GREEN GROUNDlNG CONDUCTOR IN ALL EQUIPMENT AND RECEPTACLE BRANCH CIRCUITS. 0. ACCESS TO PERFORM WORK <br /> SIZE PER NEC. CAREFULLY REMOVE, S70RE OR TEMPORARILY HANG AND RE-INSTALL IN UNDAMAGED CONDITION ALL <br /> ELECTRICAL EQUIPMENT, LIGHTING FIXTURES AND CEILING TILES WHERE ACCESS 70 PERFORM WORK IS <br /> G. SUBMITTALS: <br /> REQUIRED. CLEA�1 PRIOR TO RE-1NSTALLATiON. <br /> AFTER AWARD OF CONTRACT, SUBMIT THREE COMMON BOUND BROCHURES TO ENGINEER (ONE COPY <br /> RETURNED TO CONTRACTOR) CONTAINING CATALOG CUTS AND/OR SHOP DRAWINGS FOR THE �OLLOWING SECTION 260519 - LOW VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES <br /> ��M$: Revision BY Appd. YY.MM.DD <br /> -EPO PUSN BUTTON <br /> A. PROVIDE ALL WIRE AND CABLE COMPLETE: � <br /> H. CUTIING AND PATCHING: COPPER, INSULA7ED FOR 600V. ALUMINUM OR COPPER CLAD ALUMINUM CONDUCTORS NOT PERMIT7ED. <br /> DO NOT CUT STRUCTURAL MEMBERS. ALL CONSTRUCTION MATERIALS DAMAGED OR CUT INTO DURING THE �'E THW, THWN/Tf�IHN OR XHHW. NUMBER 12 AWG MINIMUM FOR POWER AND LIGHIING CIRCUITS. <br /> INSTALLATION OF THIS WORK MUST BE �REPAIRED OR REPLACED WITH MATERIALS BY SKILLED LABOR <br /> EX��Rk�i���R-1N �� PAR�lCt1LA�B�k�DkNG TRA�E. - - B_ SPLI(iES:.. <br /> SOLDERLESS TYPE ONLY. PRE-INSULATED "T1MST-ON" TYPE (LIMITED TO SIZE #10 AND SMALLER). �OLT OR ' c�o�sraQcrro�r 66cvrnENrs - NCA nn�� �Sr2.�s - <br /> I. PAINTING: COMPRESSION SET TYPE WITH APPLICATION OF PREFORMED INSULATED COVER, HEAT SHRINKABLE TU�ING OR Issued av Appd. YY.MM.DD <br /> TOUCH-UP TO MATCH FACTORY PAINT ANY ELECTRICAL ITEMS SCRATCHED OR MARRED IN SHIPMENT OR PLASIIC INSULA7ED TAPE ACCEPTABLE FOR ALL SIZES. <br /> INSTALLATION. <br /> C. TERMINATIONS: NCA MDJ NCA 18.12.13 <br /> J. CLEAN UP: COMPRESSION SET, BOLTED OR SCREW TERMINAL. CONDUCTORS #12 AND SMALLER SHALL UTIUZE EYE OR Dwn. Chkd. Dsgn. YY.MM.DD <br /> CONTINUALLY REMOVE DEBRIS, CUTTINGS, GRATES, CARTONS, ETC. CAREFULLY CLEAN WIRING DE�CES, F�ORKED TONGUE TYPE COMPRESSION SET TERMINATOR WHEN TERMINATION IS TO A BOLTED SCREW SET IYPE Permit-Seal <br /> a COVER PLATES, UGHT FIXTURES, ETC., TO REMOVE PAINT AND PLASTER, ETC. TERMINAL �LOCK OR TERMINAL CABINET. <br /> �� D . �� <br /> Z D. COLOR CODE: �,�,� �F wAs�I���� <br /> z 480 MARKING BRN, _ <br /> SECTION 260510 - EXISTING SYSTEMS � �'� � �, ,� <br /> a <br /> ORG YELL, GRAY NEUTRAL �,�' ? o O <br /> m 208 MARKING 6LK, RED, BLU, WHITE NEUTRAL <br /> � A. EXISTING SYSTEMS AND SYSTEMS ADJACENT T0 THE WORK SHALL �E INVESTIGATED THOROUGHLY. ANY <br /> �- E. BRANCH CIRCUITS: COPPER. SOL1D FOR N0.10 AWG AND SMALLER; STRANDED FOR N0.8 AWG AND � 38180 <br /> �- DAMAGE RESULIING FROM PERFORMANCE OF WORK UNDER THIS CONTRACT SHALL BE REPAIRED TO ASSURE LARGER. �°.�' ��'G'IST� � <br /> � CONTINUING OPERATION AND INTEGRITY DURING AND AT COMPLETION OF THE PROJECT AT NO INCREASE IN �`�SIONAL ��1� <br /> o CONTRACT COST. ANY EXISTING WIRING SERVING DEVICES TO REMAIN IN SERVICE AND WHICH IS INTERRUPTED <br /> N BY WORK PERFORMED UNDER THIS CONIRACT SHALL BE REROUTED 70 MAIN7AIN CIRCUIT CONTINUITY. F. MULTiCONDUCTOR CABLE IS PERMITTED ONLY AS DETAILED IN THE DRAWINGS. COMPLY WITH NEMA WC 70 �2����� <br /> � CONTRACTOR SHALL ASSUME 1NE RISK OF MAINTAINING EXISTING SYSTEMS EXCEPT RELOCATION OF WIRING OF FOR ARMORED CABLE, 1 YPE AC METAL-CLAD CABLE, TYPE MC AND TYPE SO WITH GROUN� WIRE. Client/Project <br /> � �2 AWG AND ABOVE SHALL BE CONSIDERED AN ADDI110NAL COST IF NOT SHOWN TO BE RELOCATED. IF <br /> � SUCH WIRING IS FOUND THE CONTRACTOR SHA!L NOTIFY ENGINEER OF WIRING LOCAl10N, REASON IT MUST BE G. ALL 480/277V WIRING V�ILL BE SEPA.RATED FROM THE 203/12�JV �llRiNG AT ALL TIMES. EXCEPTIONS: PROVIDENCE R��I�NAL ME[�ICAL <br /> o REMOVED AND COST OF RELOCATION AND RECEIVE THE OWNER'S APPROVAL BEFORE PROCEEDING WITH THE MOTOR CONTROLS. <br /> � WORK. THE BUILDING WILL CONTINUE OPERA710N DURING 7HE WORK AND IT IS ESSENTIAL TNAT NO SYSTEMS CENTER EVERETT - COLBY CAMPUS <br /> m OPERATION BE INTERRUPTED UNLESS SCNEDULED WITH THE OWNER. CONTRACTOR SHALL ASSUME <br /> � RESPONSIBILITY FOR UNSCHEDULED INTERRUPTIONS AND EXPEDIENT REPAIR. NUC MED #3 REPLACEMENT <br /> a SECTION 260526 - GROUNDING <br /> i <br /> � <br /> � <br /> o B. EXISTING SYSTEMS CONCEALED PROVIDE A GROUNDING SYSTEM FOR EQUIPMENT AND DEVICE GROUND AS REQUiRED BY CODE. EVERETT, WA <br /> � 1. THE ELECTRICAL DRAWINGS SHOW PORTIONS OF THE EXISTING ELECTRICAL SYSTEMS 4VHICH ARE TO REMAIN, <br /> � 8E REMOVED OR BE MODIFIED AS A PART OF 1'hIE CON7RACTOR'S WORK. CONCEALED FEATURES OF THE Title <br /> � EXISTING SYSTEMS ARE DERIVED FROM RECORD DRAWINGS AND THE ENGINEER'S BEST JUDGMENT OF THE SECTION 260533 � RACEWAYS AND BOXES <br /> � CONFIGURATION, BUT NO GUARANTEE IS MADE AS TO THEIR CORRECTNESS. ELECTRICAL SPECIFICATIONS <br /> i A. PROVIDE RACEWAY SYSTEM COMPLETE AND IN CONFORMANCE WITH CODE. INSTALL RACEWAYS CONCEALED <br /> � 2. THE CONIRACTOR SHALL INSPECT THE EXISTING INSTALLATION PRIOR 70 BIDDING AND SHALL MAKE HIS IN CONSIRUC110N FOR ALL AREAS UNLESS EXPOSED RACEWAYS ARE SPECIFICALLY SHOWN. <br /> � OWN JUDGMENT AS TO THE WORK REQUIRED TO PROVIDE A COMPLETE INSTALLAl10N AND DEMOLI710N �iiTHIN <br /> o THE INTENT OF THE CONTRACT DOCUMENTS. B. PROVIDE 1" RACEWAY FOR HO�iERUNS AND MAJOR CEILING CONDUIT RUNS. RACEWAY DROPS DOWN WALLS <br /> � AND RACEWAY CARRYING 2 CURRENT CARRYING CONDUCTORS CAN BE 3/4". ��INIMUM RACEWAY SIZE IS 3/4". Project No. Scale <br /> Y <br /> 3 204820937 N O N E <br /> � <br /> � Drawing No. <br /> � <br /> � E0.0 � <br /> M <br /> � <br /> � <br /> / _ <br /> / <br /> ORIGINAL SHcET-ARCH El <br />