8/23/2019 Page 1 <br /> City of Everett <br /> 10:12:27AM <br /> INSPECTION ACTIVITY REPORT <br /> Permit No. EW 1802-003 Site Address 2106 CHESTNUT ST <br /> Applied 2/21/2018 Applicant Lot <br /> Approved 2/21/2018 Owner STONE ROBERT Block <br /> Issued 2/21/2018 Contractor OWNER Tract <br /> Parent Permit No. W1712-003 Description REPLACE(2)A/C SWITCHES,(2)A/C SOCKETS,CAP OFF TO <br /> Notes <br /> Scheduled Completed Tvne Inspector Result Remarks Inspector's Comments <br /> 9/11/2018 9/11/2018 ELEC 08-OTHER MCB CORRECTION Mast supports. <br /> Ground rods. <br /> GFCI bath&kitchen <br /> Hot water tank plug <br /> Wiring under sink <br /> Outside J boxes <br /> Conduit to garage <br /> Wiring in garage <br /> 11/9/2018 11/9/2018 ELEC 09-FINAL SKB CORRECTION All replaced receptavcles are to be tamper <br /> resistant. <br /> Close unused openings in panel <br /> 1 neutral conductor under a lug only in <br /> panel. <br /> Only 1 grounding electrode conductor <br /> under an acorn nut not 2. <br /> Remove abandoned wiring in attic. <br /> Garage wiring disconnected from house- <br /> remove NM cable from conduit <br /> underground. <br /> 11/15/2018 11/15/2018 MARK FINAL** MCB APPROVAL <br /> 11/15/2018 11/15/2018 ELEC 09-FINAL MCB APPROVAL <br /> INSP12 CRWS YS TEM S <br />