Laserfiche WebLink
Envelope Requirements Summary, pg 1 ENV-REQ <br /> 2015 WSEC Compliance Forms for Commercial Buildings including R2,R3,&R4 over 3 stories and all R1 Revised Jun 2016 <br /> Minimum Requirements This table summarizes prescriptive compliance requirements for opaque elements and fenestration.Refer <br /> for Prescriptive Compliance to Tables C402.1.3,C402.1.4 and C4024 in the 2015 WSEC for important footnotes that apply to <br /> these tables. Refer to Section C402 for all applicable requirements that apply for each envelope element <br /> type and applicable exceptions. Refer to Section C410 for all applicable information for refrigerated <br /> spaces. <br /> Table C402.1.3 Notes 1,7 Table C402.1.4 Notes 1,2 <br /> Prescriptive Path Insulation Minimum R-Value Assembly Maximum U-factor <br /> Occupancy Group All Other I Group R All Other I Group R <br /> Opaque Elements <br /> Roofs <br /> Insulation Entirely above Deck R-38 c.i. R-38 c.i. U-0.027 U-0.027 <br /> Metal Building(with thermal spacer block)Note 3 R-25+R-I 1 Ls R-25+R-11 Ls U-0.031 U-0.031 <br /> Attic and Other R-49 R-49 U-0.021 U-0.021 <br /> Joist or single rafter R-49 R-49 U-0.027 U-0.027 <br /> Walls,Above-grade <br /> Mass R-9.S c.i.Note 6 R-13.3 c.i. U-0.104 Note 6 U-0.078 <br /> Mass transfer deck slab edge No R-Value for prescriptive compliance U-0.200 U-0.200 <br /> Metal Building R-19 c.i. R-19 c.i. U-0.052 U-0.052 <br /> Steel Framed R-13+R-10c.i. R-19+R-8.5 c.i. U-0.055 U-0.055 <br /> Wood Framed and Other R-2I w/int.frame R-21 w/int.frame U-0.054 U-0.054 <br /> Below Grade Wall Note 4 Same as above grade Same as above grade <br /> Floors <br /> Mass R-30 c.i. R-30 c.i. U-0.031 U-0.031 <br /> Steel Joist R-38+R-10 c.i. R-38+R-10 c.i. U-0.029 U-0.029 <br /> Wood Framed and Other R-30 R-30 U-0.029 U-0.029 <br /> Slab-On-Grade Floors <br /> Unheated R-10 for 24 in.(from top of slab) _ F-0.54 F-0.54 <br /> Heated Notes R-10 perimeter&under entire slab F-0.55 F-0.55 <br /> Opaque Doors <br /> Swinging No R-Value for prescriptive compliance U-0.37 U-0.37 <br /> Nonswinging(Roll-up or sliding) R-4.75 I R-4.75 U-0.34 U-0.34 <br /> Table C402.4-0-30%of wall area,or <br /> 30%-40%per Section C402.3.1.1 DLZ Section C402.3.1.3 High Performance <br /> or Section C402.3.1.4 DOAS Fenestration Option-0-40%of wall area <br /> Fenestration Assembly Maximum U-factor Notes 1,2 <br /> Vertical Fenestration <br /> Nonmetal framing U-0.30 U-0.30 U-0.28 U-0.28 <br /> Metal framing(fixed) U-0.38 U-0.38 U-0.34 U-0.34 <br /> Metal framing(operable) U-0.40 U-0.40 U-0.36 U-0.36 <br /> Entrance doors U-0.60 1 U-0.60 U-0.60 U-0.60 <br /> Skylights <br /> Skylights U-0.50 I U-0.50 U-0.50 l U-0.50 <br /> Fenestration Assembly Maximum SHGC Factor <br /> Vertical Fenestration PF<0.2:north-SHGC�.53; PF<0.2:north-SHGC 3.46; <br /> all other SHGCO.4 all other SHGC�.35 <br /> 0.2 5 PF<0.5:north-SHGC-0.58; 0.2 5 PF<0.5:north-SHGC-0.51; <br /> all other-SHGC-0.48 all other-SHGC-0.42 <br /> PF '0.5:all orientations-SHGC-0.64 ' PF>_0.5:all orientations-SHGC-0.56 <br /> Skylights SHGC-0.35 SHGC-0.35 <br /> C410.2 Refrigerated Spaces Insulation Insulation Minimum R-Value Assembly Maximum U-factor <br /> Freezers-Walk-in and Warehouse <br /> Roof/Ceiling R-32 U-0.030 <br /> Wall R-32 U-0.030 <br /> Door R-32 U-0.030 <br /> Door-transparent reach-in triple-pane,heat-reflective treated or gas <br /> Floor R-28 U-0.035 <br /> Coolers-Walk-in and Warehouse <br /> Roof/Ceiling R-25 U-0.039 <br /> Wall R-25 U-0.039 <br /> Door R-25 U-0.039 <br /> Door-transparent reach-in double-pane,heat-reflective treated&gas <br /> fill,or comply with freezer door req. <br /> Floor No Requirement <br /> 1 <br /> 7 <br />