Laserfiche WebLink
9/24/2019 City of Everett Page <br /> 1:33:17PM <br /> INSPECTION ACTIVITY REPORT <br /> Permit No. El 806-134 Site Address 1321 E MARINE VIEW DR <br /> Applied 6/18/2018 Applicant Lot <br /> Approved 6/18/2018 Owner MULLEN KEVN A Block <br /> Issued 6/18/2018 Contractor OWNER Tract <br /> Parent Permit No. Description ADD NEW BREAKER PANEL&POWER DROP FROM POLE <br /> Notes <br /> Scheduled Completed Tvpe Inspector Result Remarks Inspector's Comments <br /> 9/25/2018 9/25/2018 ELEC 05-SERVICE SKB CORRECTION Install a second ground rod. <br /> Install a lock nut behind both the panel and <br /> meter and bond the metal nipple. <br /> Grounding electrode conductor has to land <br /> on the grounded bus. <br /> Wire light and outlets. <br /> 7/25/2019 7/25/2019 PERMIT TAH APPROVAL EXTENDED TO <br /> EXTENSION 01/21/2020 <br /> 8/6/2019 8/6/2019 ELEC 05-SERVICE SKB APPROVAL Phone:206-718-1009 <br /> (8/6/2019 1:19 PM SKB) <br /> skb changed Inspection Type from ELEC <br /> 09-FINAL to ELEC 05-SERVICE <br /> 8/30/2019 8/30/2019 ELEC 09-FINAL SKB APPRVD-PERN eTRAKiT Inspection 8/29/2019 1:39 PM Kevin Mullen <br /> Request <br /> Contact Name:Kevin Mullen <br /> Site Address: 1321 E MARINE VIEW DR <br /> Phone:2067181009 <br /> e-Mail:kmullen@gowfire.com <br /> 8/30/2019 8/30/2019 ADMIN USE AKH APPROVAL <br /> ONLY** <br /> INSP12 <br /> Cfl YS TE MS <br />