Laserfiche WebLink
8/2/2019 Page <br /> City of Everett <br /> 2:48:00PM <br /> INSPECTION ACTIVITY REPORT <br /> Permit No. E1805-228 Site Address 3001 OAKES AVE <br /> Applied 5/31/2018 Applicant Lot <br /> Approved 5/31/2018 Owner SNOHOMISH CO PROP MGMT Block <br /> Issued 6/1/2018 Contractor CLK CONSTRUCTION LLC Tract <br /> Parent Permit No. B1709-011 Description ELECTRICAL TI OF CARNEGIE BLDG <br /> Notes <br /> Scheduled Completed Tyne Inspector Result Remarks Inspector's Comments <br /> 7/26/2018 7/26/2018 ELEC 03-ROUGH SKB CORRECTION oK electrical rough in walls and hardlids. <br /> IN Provide GFCI protection for all construction <br /> receptacles. <br /> 10/17/2018 10/17/2018 ELEC 04-TGRID SKB CORRECTION Not ready <br /> 10/23/2018 10/23/2018 ELEC 04-TGRID SKB PARTIAL APPR 2nd floor elect grid OK <br /> Leave 6 tiles open for lighting relays. <br /> 10/25/2018 10/25/2018 ELEC 04-TGRID MCB CORRECTION Install boxes on exit sign circuits. <br /> Working clearance. <br /> 10/26/2018 10/26/2018 ELEC 03-ROUGH TRA APPROVAL <br /> IN <br /> 10/26/2018 10/26/2018 ELEC 04-TGRID TRA APPROVAL <br /> 11/27/2018 11/27/2018 ELEC 09-FINAL TRA CORRECTION Correct EM6 light circuit. <br /> Note:Fire,low voltage final inspection <br /> required. <br /> 11/28/2018 11/28/2018 MARK FINAL** TRA APPROVAL <br /> 11/28/2018 11/28/2018 ELEC 09-FINAL TRA APPROVAL As noted Subject to builiding inspection approval of <br /> stairwell emergency lighting. <br /> INSP12 CRWS YS TEM S <br />