t- <br /> P <br /> OPERATOR INTERACTION <br /> Primary Operator Functions.The 4020 operator Notification appliances can be silenced by pressing <br /> panel maximizes the performance of primary fire alarm the ALARM SILENCE switch. Pressing the SYSTEM <br /> functions by displaying only the indications and RESET switch restores the system to the normal <br /> interaction switches required for responding to operation mode.The system tone-alert can be <br /> emergency situations (see Figure 1). programmed to resound at user specified time intervals <br /> to serve as an "active status reminder"when a trouble <br /> condition remains in the system and the audible trouble <br /> SYSTEM IS NORMAL signal has been silenced. <br /> 9:27:40 FRI 26 MAY 00 <br /> FRE PRIORITY SYSTEM SYSTEM ALARM POWER Additional Operator Function Keys. For increased <br /> ALARM ALAARRM SUPERVISORY TROUBLE SILENCED ONOfunctionality, additional operator keys are available by <br /> /\ /\ �\/- /\/\ opening the access door(see Figure 2).The <br /> ALARM ALARM SUPV TBL 1 ALARM SYSTEM FUNCTION KEYS, DISPLAY/ACTION keypad, and the <br /> ACK ACK ACK ACK J SILENCE RESET ENTRY keypad are the operator interface sections that <br /> ACKNOWLEDGE J are not essential in a fire emergency situation. These <br /> functions are presented in a self-directing manner and <br /> include: circuit/device ENABLE or DISABLE, control <br /> Figure 1. Primary Operator Functions point turn ON or OFF, DISPLAY HISTORICAL LOGS, <br /> etc. <br /> Indications.Alarm, supervisory, and trouble conditions The operator's access is determined by four passcode <br /> are indicated at the operator's panel by dedicated LEDs protected security levels. Level 1 allows routine actions <br /> and a local tone-alert.An 80 character(2 lines x 40 while level 4 is reserved for more sensitive operations <br /> characters)alphanumeric super-twist liquid crystal requiring higher level operator knowledge. Levels 2, 3, <br /> display provides information concerning point status and 4 are passcode protected to ensure proper <br /> (alarm,trouble, supervisory, etc.), type of alarm(smoke authorization for that level's control access. Passcode <br /> detector, manual station, waterflow supervisory, etc.), log-ins are stored in the history log for access review. <br /> number of alarms in the system, and a custom location Display Action and Entry Keypads.The <br /> label. <br /> Display/Action and Entry keypads allow operators (with <br /> Switch Operation.Alarm,supervisory, and trouble proper access levels)to perform controlling functions to <br /> conditions have dedicated acknowledge push-button system zones, notification appliance circuits (NACs), <br /> switches. Operation of the appropriate acknowledge and auxiliary control relays,or to gain access for <br /> switch silences the tone-alert with the LED remaining system information. DISABLE allows a specific circuit <br /> illuminated until all conditions in that category are or a specific addressable device to be disconnected <br /> restored to normal. from the system to isolate a problem. A trouble <br /> The 4020 can be programmed to perform a"global condition will occur as a reminder of the action taken. <br /> acknowledge"where a single push of the appropriate ENABLE followed by ENTER restores the circuit or <br /> acknowledge switch will silence the tone-alert for all device to active status in approximately 60 seconds. <br /> points in that condition. It can also be programmed for The display will count down the remaining time and will <br /> individual acknowledgment of each point in an warn the operator if the circuit to be enabled will cause <br /> abnormal condition, as well as their restoration. Both an alarm. <br /> operations are in accordance with the requirements of <br /> NFPA 72, the National Fire Alarm Code. <br /> I CONTROL FUNCTION KEYS 1 <br /> "-DISPLAY/ACTION-% ��ENTRY <br /> r �r ( <br /> Q F 1 F 2 F 3 I F 4 FUNCTION MENU ZONES ® ' • <br /> AUX <br /> �,. 111 •111 1 3 <br /> Ol Q/r �/ \/ �� �/ PREVIOUS TEST r FB .\ i 60 -MAP, <br /> [Ii]lO) SYSTEM IS NORMAL . 4 , . A \ 6 , <br /> 9:27:40 FRI 26 MAY 00 NEXT •) H <br /> "n( l FIRE PRIOR2 SYSTEM SYSTEM ALARM POWER l ARM 1`ENABLE 8 • (l )I <br /> l Jl J. l IJ i i <br /> Q ALOARM ALARMOSUPERVISORY SILENCEDQONOADDR DEL <br /> �� �� �� �� �� �� ,DISARM, DISABLE • 0 J . , <br /> r � r <br /> r O ALARM ALARM SUPV ' TBL ALARM SYSTEM AUTO 1`DISPLAY' ENTER CLR <br /> t ACK ( ACK ACK ACK (SILENCE, RESET 1 TIME , •` • <br /> ACKNOWLEDGE <br /> Figure 2.Additional Operator Keys <br /> S4020-0003-6 6/0 page 20. <br />