Laserfiche WebLink
4020 Product Selection Chart <br /> Product Description Comments <br /> Control Panel Selection <br /> 4020-8001 System Control Panel <br /> Master Controller Assembly, 1 MAPNET II Channel (127 points),4 I/O points, and Required <br /> 4020-7003 power supply/charger <br /> Optional Modules <br /> 4020-0110 MAPNET II Module, 127 points Three maximum <br /> 4020-0113 Dual Port RS-232 Module One maximum <br /> 4020-0305 8 Point I/O Module Two maximum <br /> 4020-0129 25.5 VDC Limiter Module,4 A maximum, for use with 4020-6007 <br /> 4020-0139 Dial-In Service Modem (requires 4020-0113 or 4020-6014) One each <br /> maximum <br /> 4020-0136 Coded Input Decoder Module <br /> 4020-0155` Serial DACT for connecting to RJ31X Telco jacks, requires one DACT cable per line Two maximum <br /> 4020-0153` Contact Closure DACT, connects to RJ31X Telco jacks, requires one cable per line Select as required <br /> DACT Accessories <br /> 2080-9046 DACT Cable with RJ45 plug, 7 ft long (2.1 m) <br /> 2080-9047 DACT Cable with RJ45 plug, 14 ft long (4.2 m) Select as required <br /> Operating Options <br /> 4020-7553 i Interface to 2120 system, requires 4020-0113 <br /> 4020-6001 240 VAC, 50/60 Hz power input <br /> 4020-6003 French control panel kit Select as required, <br /> one each <br /> 4020-6007 Automatic extinguishing,deluge, and preaction sprinkler release control, requires maximum <br /> 4020-0129 (refer to Simplex data sheet S4100-0019 for details) <br /> 4020-1010 External batteries and charger(batteries and charger ordered separately) <br /> Cabinet Size and Cabinet Options Separate Mounting Box(select if required for pre-ship) <br /> (shipped in mounting box) Beige Red <br /> 4020-2001 Two unit 2975-9184 2975-9185 <br /> Select size as <br /> 4020-2002 Four unit 2975-9186 2975-9187 required for option <br /> 4020-2003 Six unit 2975-9188 2975-9189 choices <br /> 4020-2201 Red finish for door, retainer,and cabinet Select one if req'd. <br /> 4120 Network Interface Options(select as required) <br /> 4020-7558 Interface to 4120 Network, requires 4020-6014 One maximum <br /> 4020-6014 4120 Network Interface Modular Card (requires 4020-7558 and two media cards) <br /> Reference <br /> 4020-0142 Wired Media Card data sheet <br /> 4020-0143 Fiber Optic Media Card S4120-0003 for <br /> details <br /> 4020-0144 Modem Media Card <br /> 4020-6023 Physical Bridge Module (requires 4020-7558&-6014) Ref. S4120-0005 <br /> Battery Selection and External Battery Cabinets(select one battery size per system requirements, quantities as indicated) <br /> 2081-9272 6.2 Ah Battery, 12 VDC <br /> 2081-9274 10 Ah Battery, 12 VDC <br /> 2081-9275 18 Ah Battery, 12 VDC 2 required for <br /> 24 VDC system <br /> 2081-9271 33 Ah Battery, 12 VDC NOTE: Use in cabinet will not allow bottom entry conduit <br /> 2081-9211 50 Ah Battery, 12 VDC NOTE: Requires external battery cabinet <br /> 2081-9281 External battery cabinet, beige Battery cabinet dimensions: <br /> 2081-9282 External battery cabinet, red 25 3/4"W x 20 3/4" H x 6 3/4" D (654 mm x 527 mm x 171 mm) <br /> *The 4020-0155 and 4020-0153 DACTs are programmed using a terminal or a laptop computer in terminal emulation mode.Connection and <br /> programming details are provided with the installation instructions. <br /> S4020-0003-6 6/00(page 7/�/ <br />