<br /> OPTIONAL FEATURES- • Single-stage,propane gas valve(field adjustable for operation to 9,000 ft.elevation B) '
<br /> FACTORY INSTALLED a Two-stage natural gas or propane gas valve-Sizes 60-400
<br /> • 409 or 316 Stainless steel heat exchangers
<br /> • Totally enclosed fan motor(Sizes 30-250,115V only)
<br /> ACCESSORIES -FIELD a Horizontal or Vertical Combustion AirNent Kit including concentric adapter.,
<br /> INSTALLED • Thermostat
<br /> • Thermostat guard with locking cover
<br /> • Vertical louvers
<br /> • Downturn nozzle kits
<br /> • Gas conversion kits(natural and propane)
<br /> • Primary/secondary controls for zoning up to six units
<br /> • Ceiling suspension kit-Sizes 30-125
<br /> • Hanger kits for 1"pipe
<br /> • Stepdown transformer(for 208/115,230/115 or 460/115 supply voltage)
<br /> • Manual shutoff valves
<br /> e Pressure switch change required for Installations above 6,000 ft.
<br /> °Selection of either a horizontal or vertical combustion air/vent kit is required.
<br /> TECHNICAL DATA
<br /> Model UDAS 1
<br /> Size 30 46 60 76 100 126 150 175 200 226 250 300 360 400
<br /> Input Heating Capacity BTUH 30,000 45,000 60,000 75,000 105,000 120,000 150,000 175,000 200,000 225,000 250,000 300,000 350,000 400,000
<br /> (kw/h) (8.8) (13.2) (17.6) (22,0) (30.8) (35.2) (44.0) (51.3) (58.6) (65.9) (73.3) (87.9) (102.6) (117,2)
<br /> Thermal Efficiency(%) 82 83 83 83 83 83 83 83 83 83 83 83 83 83
<br /> Output Heating BTUH 24,600 37,350 49,800 62,250 87,150 99,600 124,500 145,250 166,000 186,750 207,500 249,000 290,500 332,000
<br /> Capacity° (kw/h) (7.2) (10.9) (14.6) (18.2) (25.5) (29.2) (36.5) (42.6) (48.7) (54.7) (60.8) (73.0) (85.1) (97.3)
<br /> Gas Connection Natural 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 3/4 3/4 3/4 3/4 3/4
<br /> (inches)E Propane 1/2 1/2 1/2 1/2 1/2 1/2 1/2 _ 1/2 1/2 3/4 3/4 3/4 3/4 3/4
<br /> Vent Connection F(inches 4 4 4 4 4 4 5 5 5 5 5 6 6 6
<br /> diameter)
<br /> Combustion Air Inlet F(inches 4 4 4 4 4 4 6 6 6 6 6 6
<br /> diameter) 6 6
<br /> Control Amps(24 volt) 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1,0 1.0 1.0 1.0
<br /> Full Load Amps(115 volt) 1.9 2.4 2.4 3.3 3.9 5.1 3.8 3.8 4.6 7.5 7.5 11,0 11.0 11.0
<br /> Maximum Over Current Protection 15 15 15 15 15 15 15 15 15 15 15 20
<br /> (115V)° 20 20
<br /> Normal Power Consumption(watts) 109 155 155 217 276 354 392 392 491 747 747 1086 1086 1086
<br /> Discharge Air Temperature Rise 50 55 60 60 60 60 60 60 60 60 60 60 60 60
<br /> (°F)
<br /> Air Volume CFM 456 629 769 961 1345 1537 1921 2242 2562 2882 3202 3843 4483 5123
<br /> (Ms/min) (12.9) (17.8) (21.8) (27.2) (38.1) (43.5) (54.4) (63.5) (72.5) (81.6) (90.7) (108.8) (126.9) (145.1)
<br /> Discharge Air Opening ft2 0.96 0,96 1.25 1.25 2.01 2.01 2.56 2.56 2.56 3.51 3.51 4.79 4.79 4.79
<br /> Area (M2) (0,09) (0,09) (0.12) (0,12) (0.19) (0.19) (0.24) (0.24) (0.24) (0.33) (0.33) (0.45) (0.45) (0.45)
<br /> Output Velocity FPM 475 656 616 770 668 763 752 877 1003 820 911 802 936 1069
<br /> (M/min) (145) (200) (188) (235) (204) (233) (229) (267) (306) (250) (278) (244) (285) (328)
<br /> Fan Motor HP n Open 0.02 0.03 0.03 0.06 1/30 1/20 1/6 1/6 1/6 1/4 1/4 1/2 1/2 1/2
<br /> Enclosed 0.06 0.06 0.06 0.06 1/20 1/20 1/4 1/4 1/4 1/4 1/4 1/2 1/2 1/2
<br /> Fan Motor RPM 1550 1550 1550 1550 1050 1050 1050 1050 1050 1050 1050 1050 1050 1050
<br /> Fan Diameter inches 10 10 12 12 16 16 18 18 18 20 20 24 24 24
<br /> Sound Level dbafi 40 40 40 49 54 55 51 52 53 56 56 59 61 62
<br /> Approximate Net lbs 55 60 68 73 97 102 173 188 188 204 216 270 295 307
<br /> Weight (kg) (25) (27) (31) (33) (44) (46) (78) (85) (85) (93) (98) (122) (134) (139)
<br /> Approximate Ship lbs 63 68 76 81 120 125 206 221 221 247 259 323 348 360
<br /> Weight (kg) (29) (31) (34) (37) (54) (57) (93) (100) (100) (112) (117) (147) (158) (163)
<br /> "CSA rating for altitudes to 2000 ft.
<br /> e Size shown is for gas connection to a single stage gas valve,not supply line size.
<br /> °Smaller and/or larger vent and combustion air pipe diameters may be allowed;refer to the Venting Installation Manual for Separated Combustion
<br /> Units,Form I-V-SC.If vent diameter is different from vent connection,reducer/enlargers will be field-required.
<br /> °MOP=2.25 x largest motor FLA+remaining load.Answer is rounded down to the next size of commercially available circuit breaker or fuse.
<br /> "Ail other information in this table is based on a heater equipped with a standard 115 volt open fan motor.
<br /> For installations where dirt,dust,and other air borne contamination is present in the Indoor environment,it is
<br /> recommended to use separated combustion units(Model UDAS).These models use air from outside the space
<br /> forcombustion.This will help reduce the build up of contaminates on the burnerwhich would affect the combus-
<br /> tion process.Refer to the Installation manuals for recommended frequency of maintenance and cleaning.
<br /> Form RZ-C-UH(Version H)Page 6