Laserfiche WebLink
10/31/2019 Page <br /> City of Everett <br /> 8:52:39AM <br /> INSPECTION ACTIVITY REPORT <br /> Permit No. El 910-062 Site Address 1318 HOYT AVE <br /> Applied 10/8/2019 Applicant Lot <br /> Approved 10/8/2019 Owner POH PATRICK D&TONI L Block <br /> Issued 10/8/2019 Contractor 3 DIMENSIONAL ELECTRIC LLC Tract <br /> Parent Permit No. Description REWIRE HOUSE/NEW SERVICE <br /> Notes <br /> Scheduled Completed Tvne Inspector Result Remarks Inspector's Comments <br /> 10/24/2019 10/24/2019 ELEC 09-FINAL SKB CORRECTION (10/24/2019 12:32 PM SKB) <br /> Not really not all switches installed.Provide <br /> a three-way to illuminate the stairs at the <br /> top and bottom.Provide access to the <br /> meter.Provide access to the garage.Neutral <br /> conductors cannot land on the equipment <br /> bus and rely on the can to get to the <br /> grounded bus move them to the grounded <br /> buss or install a jumper. <br /> 10/24/2019 10/24/2019 ELEC 05-SERVICE SKB CORRECTION See elec final notes <br /> 10/30/2019 10/30/2019 ADMIN USE KLC APPROVAL <br /> ONLY** <br /> 10/30/2019 10/30/2019 ELEC 09-FINAL SKB APPRVD-PERIv as noted John:425-923-8437 <br /> (10/30/2019 10:02 AM SKB) <br /> Contractor is installing a 3 way to bsmt and <br /> GFCI breaker for detached garage. <br /> 10/30/2019 10/30/2019 ELEC 05-SERVICE SKB APPROVAL John:425-923-8437 <br /> INSP12 CRWS Y ` mMS <br />