Laserfiche WebLink
Meg Haley <br />From: Meg Haley <br />Sent: Tuesday, December 26, 2006 11:24 AM <br />To: 'rick lapinski'; 'Travis Falk' <br />Subject: 60612-008 2931 W. Marine View Drive - TI for Stat Medical �C� (,�. � <br />Rick and Travis, <br />For ext.rior walls that will have drywall facing installed as part of this permit, we will <br />accept the R-11 insulatioii originally submitted based on the R-value of the composite <br />consrzuction of tlie wall, in lieu of our markups to R-19 insulation based on the <br />pzescripti�ae requirementa of the WSEC 2004 edition, Table 13-1. <br />Additionall;, Ric: Lapinski has marked up tlie mechat.ical drawings (currently in review) to <br />include tlie large storage area as a heated space, �o :7-19 insulation will not be required <br />on the new east-�.uest wall north of column line 2 marked on Wall Type C1, enclosing lhe <br />st.orage room. The original wall type reference to B1 on thic wall (at the managers office <br />only) would cl'ill apply, subject to Wilco�c Construcl-ion's original design for the control <br />of sound L'ran�mission of tlie manager's office. Per my phone conversation today with Rick <br />and S�an, the new storage wall will be constructed to the underside of ceiling at 10'-7�� <br />in heiy7hC. <br />I will revise our record set to reflect tliece changes, and I will ❑otify our Inspectors of <br />this revision. <br />-Meg <br />Meg Haley <br />City of Everett <br />3200 Cedar Street <br />Everett, l9A 9820t <br />Ph: 425-257-8813 <br />Fax: A25-257-BflSG <br />mha ley���ci . evere[ C. wa . uc <br />WWIJ.G'VC1'LCCIJd.OL�]�(jC'fdLll:.tl�pr.?iD=376 <br />