2009 Washington Stave Energy Code Compliance Form for Nonresidential and Multifamily Residential
<br />Prescriptive Spaces Occupancy: Q Warehouse or Parking Garage Other I
<br />�2ualificationChecklist
<br />Lighting
<br />F-1Check d95%or more olfixtures comply with t,2or3and rest areballasted.
<br />got,. If occupancy type is 'Other- and fixture
<br />Fixtures
<br />1 Fluorescent fixtures with a) 1 or 2 two lamps, b) reflector or louvers,
<br />answer is checked, the number of fixtures In
<br />(Section
<br />c) 5-60 watt T-1, T-2, T-4, T.S. T-8, or CFL lamps, and d) hard -wired electronic
<br />the space is net limited try Cafe. Clearly
<br />indicate these spaces on plans. If not
<br />1521)
<br />dimming ballasts. Screw -in CFL fixtures and tracking lighting do not ;ualify.
<br />qualified, do LPA Calculations.
<br />2. Metal Halide with a) reflector b) ceramic MH lamps <=150w c) electronic ballasts
<br />3. LED lights I
<br />II LPA
<br />TABLE 15.1 Unit Lighting Power A owance
<br />LPA WI
<br />Use
<br />LPA Wlf
<br />Use
<br />0.91
<br />0.85
<br />Office buildings, offi e_1admimstrab a areas m facilities
<br />Automotive facility
<br />of other use types (including but not limited to schools,
<br />hospitals, institutions museums. banks churches
<br />Convention center
<br />1 .10
<br />Forum or esJ==O:.�20Courthous110
<br />0
<br />Pemlentia antl other Grou I.3 Occu ancies
<br />Cafeledas, fait food establishments',
<br />1.20
<br />Police and fire stations
<br />0.90
<br />restaurantslbarss
<br />1,00
<br />Dormito
<br />1 05
<br />Post office
<br />Retail ', retail banking, mall concourses, wholesale
<br />1.33
<br />Dwelling Units
<br />.00
<br />stores allet rack shelvin
<br />0.95
<br />School buildings (Group E Occupancy only(, school
<br />1.00
<br />Exercise center
<br />classrooms. day care centers
<br />G nasia, assembl s aces
<br />0,95
<br />Theater. motion Dicture
<br />0.97
<br />125
<br />Health care clinic
<br />1,00
<br />Theater, performing ads
<br />0.80
<br />Hospital, nursing homes, and other Group lot and
<br />1.20
<br />Transportation
<br />1-2 Occupancies
<br />Hotellmotel
<br />too
<br />Warehouses
<br />O50
<br />Laboratory spaces (all spaces not classified
<br />1.62
<br />Workshops
<br />1.20
<br />'laboratory' shall meet office and other appropriate
<br />categories)
<br />Laundries
<br />120
<br />1.20
<br />Plans Submitted for Common Areas Only
<br />Libraries
<br />Manufacturingfactit
<br />1.20
<br />Main floor buildinglobbies (except mall concourses
<br />1.10
<br />Too
<br />Common areas, corridors. toilet facilities and
<br />0.80
<br />Museum
<br />washrooms, elevator lobbies
<br />Footnotes for Table 15.1
<br />1) In cases in which a general use and a specific use are listed, the specific use shall apply. In cases in which a use is not mentioned
<br />specifically, the Unit Power Allowance shall be determined by the building official. This determination shall be based upon the most
<br />comparable use specified in the table. See Section 1512 for exempt areas.
<br />2) The watts per square foot may be increased, by 2% per fool of ceiling height above 20 feet, unless specifically directed otherwise by
<br />subsequent footnotes.
<br />3) Watts per square fool of room may be increased by 2% per foot of ceiling height above 12 reel.
<br />4) For all other spaces, such as sealing and common areas, use the Unit Light Power Allowance for assembly.
<br />5) Watts per square fool of room may be increased by 2% per fool of ceiling height above 9 feet.
<br />6) Reserved.
<br />7) For conference rooms and offices less than 1501t' with full height partitions, a Unit Lighting Power Allowance of 1.1 wlftr may be used.
<br />8) Reserved.
<br />9) For indoor sport toumemenl courts with adjacent spectator seating over 5.000. the Unit Lighting Power Allowance for the court area is
<br />2.60 Wlft'.
<br />10) Display window illumination Installed within 2 feel of the window, provided that the display window is separated from the retail space by
<br />walls or at least three -quarter -height partitions (transparent or opaque) and pghting for free-standing display where the lighting moves
<br />with the display are exempt.
<br />An additional lighting power allowance is allowed for merchandise display luminaires installed in retail sales areas that are specifically
<br />designed and directed to highlight merchandise. The following additional wattages apply:
<br />L 0.6 walls per square foot of sales floor area not listed In items ii and iii below;
<br />it. 1.4 watts per square fool of furniture, clothing, cosmetics or artwork floor area; or
<br />iii. 2.5 watts per square fool of jewelry, crystal or china floor area.
<br />The specified floor area for items I, ti, or iii above, and the adjoining circulation paths shall be identified and specified on building plans.
<br />Calculate the additional power allowance by multiplying the above LPDs by the sales floor area for each department excluding major
<br />circulation paths. The total additional lighting power allowance is the sum of allowances for sales categories I, 1, or in plus an additional
<br />1,000 watts for each separate tenant larger than 250 square feet in area.
<br />The additional wattage is allowed only if the merchandise display luminaires comply with all of the following:
<br />(a) Located on ceiling -mounted track or directly on or recessed into the ceiling itself (not on the wall).
<br />(b) Adjustable in both the horizontal and vertical axes (vertical axis only is acceptable for fluorescent and other fixtures with two
<br />points of track attachment).
<br />This additional lighting power is allowed only if the lighting is actually installed and automatically controlled. separately from the general
<br />lighting, to be turned off during nonbusiness nouns. This additional power shall be used only for the specified luminaires and shall not be
<br />used for any other purpose.
<br />This additional lighting power is allowed only if the lighting is actually installed.
<br />11) Provided that a floor plan, indicating rack location and height, is submitted, the square footage for a warehouse may be defined, for
<br />computing the interior Unit Lighting Power Allowance, as the floor area not covered by racks plus the vertical face area (access side only)
<br />of the racks. The height allowance defined in footnote 2 applies only to the floor area not covered by racks.