1 <br /> Exhibit A <br /> Clearview Pump Station / City of Everett Data Sharing <br /> This is to describe methods and data to be shared between CVPS and COE. <br /> Method <br /> Establish communications between COE RTU and CVPS System..This can be accomplished <br /> at CVPS between RTU's at that site via an agreed upon method that is reliable and secure for <br /> both parties. <br /> • Method 1: Via Hardwire signaling between devices, example PLC output to PLC input. <br /> • Method 2: Via Data block transmission through a secured serial port server (Lantronix) <br /> (MODBUS Register blocks exchange on comm.server and no direct access to network <br /> or PLC registers). <br /> Method 1 is preferred. <br /> Data update frequency shall be determined by normal SCADA system transmission methods <br /> and is dependent on 3rd party communications lines. Scan time will be as fast as media can <br /> provide for reliable transmission. <br /> Data from Clearview Pump Station to COE <br /> Discrete Signals (Method 1) <br /> 1. Check valve ZAC-702,85 or position switch bypass valve closed (not) ZAC-703,87 <br /> 2. Pump 1 run YI-100 <br /> 3. Pump 2 run YI-200 <br /> 4. Pump 3 run YI-300 <br /> 5. Pump 4 run YI-400 <br /> 6. Pump 5 run YI-500 <br /> 7. CVPS FQ707 inlet meter pulse <br /> 8. CVPS Station power status: online or offline <br /> Analog Data Signals (Method 1) <br /> 1. CVPS Station flow rate FIT707 (Inlet meter) <br /> 2. CV Reservoir#1 L1-101 • <br /> 3. CV Reservoir#2 L1-102 <br /> Digital Signals (Method 2) <br /> 1. CVPS RTU clock seconds for determining communications Watchdog <br /> 2. (signals that are provided Discrete and via Analog) <br /> 12 <br />