PLUMBING FIXTURE SCHEDU �E
<br /> SERVICE PIPE SIZE BASIS OF DESIGN '
<br /> MARK ITEM IXTURE/FITTIN FLOW RATE REMARKS NOTES
<br /> CALL—OUT WASTE VENT C.W. H,W. MANUFACTURER MODEL
<br /> �
<br /> P-1 LAVATORY—UNDER COUNTER L-1 — 2 1-1/2 — — AMERICAN STANDARD OVALYN 0496.221 19x16 OVAL, UNDER COUNTER MOUNTING, VITREOUS CHINA, W/ GRID DRAIN. A, aa
<br /> FAUCET LF-1 0.5 GPM — — 1/2 1/2 SLOAN OPTIMA ETF-80 DECK MOUNTED, IR FAUCET, 4" O.C., RIGID SPOUT, PROVIDE W/ 24 VAC TRANSFORMER.
<br /> SEE ELECTRICAL FOR PART NUMBER AND QUANTITY. .
<br /> MIXING VALVE MV-1 0.5 GPM — — 1/2 1/2 CHICAGO 242.165.00.1 CONCEALED MECHANICAL MIXING VALVE W/ 1/2" TEMPERED WATER LINE FROM OUTLET •
<br /> TO FAUCEf. -
<br /> P-2 URINAL—WA�L HUNG U-1 1.0 GPF 2 1-1/2 — — KOHLER DEXTER K-5016—ET VITREOUS CHINA, LOW CONSUMPTION, SIPHON JET, BACK OUTLET, 1-1/4" INLE� SPUD. 1
<br /> FLUSH VALVE FV-2 1.0 GPF — — 3/4 — SLOAN ROYAL OPTIMA 180-1.0 ES—S 1.0 GPF, W/ 120 VAC/24 VAC TRANSFORMER. SEE ELECTRICAL FOR PART NUMBER AND .
<br /> QUANTITY.
<br /> P-3 WATER CLOSET—WALL HUNG WC-1 1.6 GPF 4 2 — — AMERICAN STANDARD RAPIDWAY 3445J.101 VITREOUS CHINA, ELONGATED BOWL, BLOWOUT, BACK OUTLET, 1-1/2" TOP SPUD. 1
<br /> F�USH VALVE FV-1 1,6 GPF — — 1 — SLOAN ROYAL OPTIMA 111-1.6 ES—S TMO �•6 GPF, W/ COURTESY FLUSH & 120 VAC/24 VAC TRANSFORMER. SEE ELECTRICAL <�
<br /> FOR PART NUMBER AND QUANTITY. '
<br /> -�
<br /> SEAT TS-1 — — — — — BEMIS 1655SSCT OPEN FRONT, LESS COVER, ELONGATED, PLASTIC, SELF—SUSTAINING CHECK HINGES. ' �
<br /> P-3.1 WATER CLOSET—WALL HUNG—ADA WC-1 1.6 GPF 4 2 — — AMERICAN STANDARD RAPIDWAY 3445J.101 VITREOUS CHINA, ELONGATED BOWL,BLOWOUT, BACK OUTLET, 1-1/2" TOP SPUD. 1
<br /> FLUSH VALVE FV-1 1.6 GPF — — 1 — SLOAN ROYAL OPTIMA 111-1.6 ES—S TMO �•6 GPF, W/ COURTESY FLUSH & 120 VAC/24 VAC TRANSFORMER. SEE ELECTRICAL '
<br /> FOR PART NUMBER AND QUANTITY.
<br /> SEAT TS-2 — — — — — BEMIS 1655SSCT OPEN FRONT, LESS COVER, ELONGATED, PLASTIC, SELF—SUSTAINING CHECK HINGES.
<br /> 1. COORDINATE MOUNTING HEIGHT W/ ARCN'L INTERIOR ELEVATIONS. A. LAVATORY GRID TYPE (ADA) "DEARBORN" 760W aa. 1-1/4"x1-1/2" 17GA., "MCGUIRE" C8872
<br /> -`�
<br /> <�
<br /> P �UMB NG SYSTEM MATER A�.S Af� D METHODS - �
<br /> PIPE SYSTEM SYSTEM PIPE SIZE MATERIAL JOINING ME�HODS VALVES & ACCESSORIES INSULATION REQUIREMENT
<br /> ABBREV. RANGE
<br /> 5 2" SOLDERED, PROPRESS BRONZE OR BRASS BODY, CW: 1-1/2" '
<br /> DOMESTIC COLD WATER, HOT WATER, DCW, DHW, STAINLESS STEEL TRIM
<br /> HOT WATER CIRCULATING DHWC TYPE L COPPER HW: IF
<br /> >-2-1/2" WELDED, FLANGED, GROOVED FITTINGS W/ HIGH BRONZE, BRASS, OR CAST IRON BODY, PIPE S 1.5", THEN 1-1/2"
<br /> TEMP GASKETS, VICTAULIC NSF 61 OR EQUAL CHROME PLATED TRIM IF PIPE >_2", THEN 2" . `�
<br /> S 2" SOLDERED, PROPRESS BRONZE OR BRASS BODY, �W� �-1�2 " ,; .
<br /> INDUSTRIAL COLD WATER, HOT WATER, ICW, IHW, STAINLESS STEEL TRIM
<br /> HOT WATER CIRCULATING IHWC TYPE L COPPER HW: IF :
<br /> ,2_��2�� WELDED, FLANGED, GROOVED FITTINGS W/ HIGH BRONZE, BRASS, OR CAST IRON BODY, PIPE 5 1.5", THEN 1-1/2"
<br /> TEMP GASKETS, VICTAULIC NSF 61 OR EQUAL CHROME PLATED TRIM IF PIPE >-2", THEN 2"
<br /> DOMESTIC COLD WATER BELOW FOUNDATION DCW - DUCTILE IRON MECHANICAL JOINTS - -
<br /> DOMESTIC COLD WATER BELOW GRADE DCW - TYPE K COPPER BRAZED - -
<br /> EMERGENCY SHOWER & EYEWASH WATER ESE - TYPE � COPPER SOLDERED, PROPRESS BRONZE OR BRASS BODY, 1-1/2" �
<br /> STAINLESS STEEL TRIM
<br /> PROCESS VENT BELOW GRADE) PV ALL SIZES 316 SSTL, BLUCHER PASSIVATED, SOCKET WELDED W/ GASKET REMOVED TRANSITION BETWEEN DISSIMILAR _
<br /> � MATERIALS W/ COUPLINGS
<br /> �:�
<br /> PROCESS VENT (ABOVE GRADE) PV ALL SIZES 316 SSTL, BLUCHER PASSIVATED, SOCKET WELDED W/ GASKEf REMOVED TRANSITION BETWEEN DISSIMILAR _ �
<br /> MATERIALS W/ COUPLINGS .
<br /> PROCESS WASTE (BELOW GRADE) PW ALL SIZES 316 SSTI., BLUCHER PASIVATED, SOCKET WELDED W/ GASKET REMOVED N/A - ,
<br /> PROCESS WASTE (ABOVE GRADE) PW ALL SIZES 316 SSTL, BLUCHER SOCKET/PUSH FIT N/A - .
<br /> SANITARY VENT (BELOW GRADE) V ALL SIZES SERVICE WEIGHT CAST IRON HUB & SPIGOT N/A - '
<br /> SANITARY VENT (ABOVE GRADE) V ALL SIZES SERVICE WEIGHT CAST IRON NO HUB N/A -
<br /> SANITARY WASTE (BELOW GRADE) W ALL SIZES SERVICE WEIGHT CAST IRON HUB & SPIGOT N/A -
<br /> SANITARY WASTE (ABOVE GRADE) W ALL SIZES SERVICE WEIGHT CAST IRON HUB & SPIGOT N/A -
<br /> TRAP PRIMER PIPING - GENERAL TP 1/2" PEX TUBING CRIMP RINGS N/A -
<br /> TRAP PRIMER PIPING - C.I.P. SKID DRAIN TP 1/2" 304 STAINLESS STEEL TUBING WELDED N/A -
<br /> �:�
<br /> PIPE INSULATION (INSIDE BUILDING) UNLESS OWENS CORNING FIBERGLASS WITH "EVOLUTION PVC COVERS FOR FITTINGS AND •
<br /> NOTED OTHERWISE ON PLAN OR SPECIFICATIONS PAPER-FREE ASJ" REMOVABLE COVERS FOR VALVES ' .
<br /> F�:
<br /> f.,
<br /> �.
<br /> CC�FFMAN ��
<br /> W5741115 N G I N E E R S
<br /> PHASE 3 RENOVATION PACKAGE
<br /> 1101 2nd,Suite 400�Seattle,WA 98101 •
<br /> I FC SUBMITTAL ph 206.623.0717�fax 206.624.3775
<br /> 10.08.18 coffman.com
<br /> LASTING creativiry�resWts�relationships
<br /> SYM REVISION BY APPROVED DATE SYM REVISION BY APPROVED DATE DRAWN DATE SUBTITLE C E ON SYMBOL DATE �'
<br /> � . Jo���� ACCEPTABILITY COFFMAN 05.25.18 MECHANICAL SCHEDULES AND DETAILS W5741115 0 R I G 10.08.18
<br /> ORIG WORKPLACE ENVIRONMENT INVESTMENT W5741115 CEI PJ 10.08.18 ��' oF W�S�r``V� THIS DESIGN AND/OR CHECKED ' �
<br /> w � P. JONES 05.25.18 SHEET
<br /> � ��� ��o SPECIFICATION IS APPROVED NGINEER TITLE WORKPLACE ENVIRONMENT INVESTMENT
<br /> BO�,�� v� APPROVED BY DEPT. DATE COFFMAN 05.25.18 M 2 1 M 4 �
<br /> CHECKED .
<br /> � B U I L D I N G 40—S 1 T E JOB N0. COMP No. -
<br /> �o� � z�4 � �9 �,� APPROVED W5741115
<br /> �� �'G'I ST�' �'
<br /> �.ssjo1�rAL �`�� APPRovEo MECHANICAL MASTER EVERETT, Wq °wc No. 40—SITE—M2-1
<br /> 1 fl/d11 R •
<br />
|