Laserfiche WebLink
1/7/2020 Page <br /> City of Everett <br /> 12:42:41PM <br /> INSPECTION ACTIVITY REPORT <br /> Permit No. E1912-092 Site Address 2730 CEDAR ST <br /> Applied 12/16/2019 Applicant Lot <br /> Approved 12/16/2019 Owner GERARD LISA Block <br /> Issued 12/16/2019 Contractor COMPLETE ELECTRIC SVCS LLC Tract <br /> Parent Permit No. Description REPLACE ELECTRICAL PANEL <br /> Notes <br /> Scheduled Completed Tvne Inspector Result Remarks Inspector's Comments <br /> 12/18/2019 12/18/2019 ELEC 05-SERVICE MCB NO ACCESS 206-422-1957 <br /> 12/24/2019 12/24/2019 ELEC 05-SERVICE SKB CORRECTION Lisa:206-313-9789 <br /> (12/24/2019 9:29 AM SKB) <br /> Label all circuits.Multi wire branch circuits <br /> must have handled ties to simultaneously <br /> trip all in grounded conductors.Install the <br /> locknut and bushing on the PVC and close <br /> that excess of opening in the panel.Number <br /> 14 gage wire must be properly protected at <br /> 15 A not 20.Property bond the gas and <br /> water,and connect to the metal water <br /> within 5 feet of where it enters the building. <br /> 1/2/2020 1/2/2020 ELEC 05-SERVICE SKB CORRECTION 206-313-9789 <br /> (1/2/2020 9:50 AM SKB) <br /> Gas must be bonded on the load side of the <br /> meter only not the line side. <br /> 1/6/2020 1/6/2020 ADMIN USE HPC APPROVAL <br /> ONLY** <br /> 1/6/2020 1/6/2020 ELEC 09-FINAL SKB APPRVD-PERN <br /> INSP12 <br />