Laserfiche WebLink
FW: Code question <br />Page 1 of 2 <br />Meg Haley <br />From: Adam Clark [adam@garyparkinson.coml <br />Sent: Wednesday, November 14, 2007 2:22 PM <br />To: Meg Haley, Tony Lee <br />Subject: RE: Code questic <br />Attachments: ElevVestibule.pdf <br />Meg, <br />The attached shows the 30" x 48" clear floor space required by ANSI 117.1 section 407.2.1.3. Please let me know your comments <br />or. the other tems so we can put this to bed. <br />Thanks, <br />Adam <br />From: Meg Haley [mailto:MHaley@ci.everett.wa.us] <br />Sent: Wednesday, November 14, 2007 11:23 AM <br />To: Tony Lee; Adam Clal c <br />Subject: FW: Code question <br />ICC got back to me and said that clear floor space is required in front of the elevator door, per chapter 4 of the 2003 ICC/ANSI <br />At 17.1. 1 have some other questions which I marked in yellow and red. Tony is tied up right now, so I have not had a chance to <br />run this by him yet. <br />-Meg <br />From: Meg Haley <br />Sent: Wednesday, November 14, 2007 10:29 AM <br />To: 'phahnraiccsafe.org' <br />Subject: Code question <br />Phil, <br />This is the question about the accessible clearanres required when exiting from an elevator in a five -story mixed use building <br />where the elevator needs to meet the 2003 IBC definition of an accessible means of egress. Please see attached diagram. <br /><<3020_001.pdf>> <br />Thanks, <br />Meg <br />Meg,fi(a]ey <br />Plans Examiner, City of Everett <br />3200 Cedar Street, Fveretl, WA 98201 <br />Ph: 425-257-8813; Fax: 425-257-8856 <br />www. eve rattwa.o rg rdef ault. as px? I D=37r, <br />NOD32 2658 (20071114) Infuriation <br />This message was checked by NOD32 antivirus system. <br />11 /14/2007 <br />