<br /> FIRE RESISTANCE REQUIREMENTS 0. DURING ITS SWING, ANY DOOR IN A MEANS OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED WIDTH OF AN AISLE, CORRIDOR,
<br /> ALTERATION JNFORMATION: PASSAGEWAY, OR LANDING UNOBSTRUCTED AND SHALL NOT PROJECT MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, CORRIDOR,
<br /> TYPE II-B CONSTRUCTION STRUCTURAL ELEMENT FIRE RESISTANCE REQUIREMENTS (IBC TABLE 601, MODIFIED PER IBC 504.1) PASSAGEWAY, OR LANDING, WHEN FULLY OPEN. (IBC 1008.1.5) .
<br /> STRUCTURAL ELEMENT FIRE RESISTANCE RATING (HR.) P. FORCE TO OPEN DOORS, APPLIED AT THE LATCH SIDE. (IBC 1008.1.2)
<br /> PROJECT LOCATION / GOVERNING AGENCY JURISDICTION: 1. LESS THAN OR EQUAL TO 15 LBF TO OPERATE THE LATCH.
<br /> 3003 West Casino Road, Everett, WA 98204 2. LESS THAN OR EQUAL TO 30 LBF TO SET THE DOOR IN MOTION.
<br /> STRUCTURAL FRAME (INCLUDING COLUMNS, GIRDERS, TRUSSES) � 3. LESS THAN OR EQUAL TO 15 LBF TO FULLY OPEN DOOR TO MINIMUM REQUIRED WIDTH. '
<br /> APPLICABLE CODES AND STANDARDS 4. LESS THAN OR EQUAL TO 5 LBF FOR INTERIOR SIDE-HINGED OR PIVOTED SWINGING DOORS WITHOUT CLOSERS
<br /> INTERNATIONAL BUILDING CODE, 2012 (IBC) INTERIOR BEARING WALLS �
<br /> INTERNATIONAL MECHANICAL CODE, 2012 (IMC) Q. DOORS SHALL BE ARRANGED TO BE OPENED REAOILY FROM THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. LOCKS, IF PROVIDED,
<br /> INTERNATIONAL FIRE CODE, 2012 (IFC) EXTERIOR BEARING WALLS AND PARTITIONS p SHALL NOT REQUIRE THE USE OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE EGRESS SIDE. (IBC 1008.1.8) {=�
<br /> UNIFORM PLUMBING CODE, 2012 (UPC) THE MAIN EXTERIOR DOOR S SHALL BE PERMITTED TO HAVE KEY-OPERATED LOCKS FROM THE EGRESS SIDE, PROVIDED THAT �
<br /> NFPA 70, NATIONAL ELECTRICAL CODE (NEC), 2011 � �
<br /> NFPA 10, STANDARD FOR PORTABLE FIRE EXTINGUISHERS, 2010 FLOOR CONSTRUCTION 0 THE FOLLOWING CRITERIA ARE MET: (IBC 1008.1.8.3) ' '
<br /> ICC/ANSI A117.1, ACCESSIBLE AND USEABLE BUILDINGS AND FACILITIES 1. ON OR ADJACENT TO THE DOOR ON THE EGRESS SIDE, THERE IS A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS THAN 1 INCH (25 MM)
<br /> ROOF CONSTRUCTION 0 HIGH ON A CONTRASTING BACKGROUND THAT READS AS FOLLOWS: .
<br /> ALL JURISDICTIONAL MODIFICATIONS AND AMENDMENTS TO CODES AND STANDARDS SHALL BE THIS DOOR TO REMAIN UNLOCKED -
<br /> INCORPORATED. WHERE MULTIPLE CODES CONFLICT, THE MOST STRINGENT SHALL GOVERN.
<br /> EXTERIOR NONBEARING WALLS AND PARTITIONS 0 WHEN THE BUILDING IS OCCUPIED
<br /> 2. THE LOCKING DEVICE IS OF A TYPE THAT IS READILY DISTINGUISHABLE AS LOCKED.
<br /> 3. THE USE OF THE KEY-OPERATED LOCKING DEVICE IS REVOCABLE BY THE BUILDING OFFICIAL FOR DUE CAUSE.
<br /> TYPE II-B CONSTRUCTION EXTERIOR WALL RATING (IBC TABLE 602) �
<br /> R. STAIRS (IBC 1009, LSC TABLE 40.2.5.2.1)
<br /> ALTERATION AREA: FIRE SEPARATION DISTANCE (FT.) FIRE RESISTANCE RATING (HR.) MINIMUM 44 IN. WIDTH WHEN SERVING MORE THAN 50 PERSONS
<br /> Passageway: 2,737 SF MINIMUM 36 IN. WIDTH WHEN SERVING 50 PERSONS OR LESS _
<br /> GREATER THAN 30 FT. p MAXIMUM RISER HEIGHT OF 7 INCHES �
<br /> USE AND OCCUPANCY CLASSIFICATION: MINIMUM RISER HEIGHT OF 4 INCHES ,
<br /> THE SCOPE OF WORK CONTAINED HEREIN SHALL NOT ALTER THE GENERAL OCCUPANCY CLASSIFICATION OF THE EXISTING BUILDING. MINIMUM TREAD DEPTH OF 11 INCHES �
<br /> MAXIMUM VERTICAL RISER BEfWEEN LANDINGS OF 12 FEET
<br /> ACCESSORY OCCUPANCIES:
<br /> S. HANDRAILS AND GUARDRAILS �
<br /> A FIRE BARRIER SHALL BE REQUIRED TO SEPARATE ACCESSORY USE AREAS AND INCIDENTAL USE AREAS IN 1. STAIRS, AND RAMPS WITH A RISE GREATER THAN 6 INCHES, SHALL HAVE HANDRAILS ON BOTH SIDES. (IBC 1009.15 �
<br /> OCCUPANT LOAD: ACCORDANCE WITH IBC SECTION 302. ANY OTHER ACCESSORY USE AREA SHALL NOT BE REQUIRED TO BE SEPARATED BY A FIRE BARRIER AND 1010.9)
<br /> THE SCOPE OF WORK CONTAINED HEREIN SHALL NOT CAUSE THE BUILDING TO EXCEED PREVIOUSLY CALCULATED OCCUPANT LOADS. PROVIDED THE ACCESSORY USE AREA OCCUPIES AN AREA NOT MORE THAN 10� OF THE AREA OF THE STORY IN WHICH IT IS LOCATED 2. HANDRAILS SHALL BE PROVIDED WITHIN 30 INCHES OF ALL PORTIONS OF THE STAIR WIDTH REQUIRED FOR EGRESS
<br /> AND DOES NOT EXCEED THE TABULAR VALUES IN IBC TABLE 503 FOR THE ALLOWABLE HEIGHT OF AREA FOR SUCH USE. (IBC 302.2) CAPACITY. (IBC 1012.9) ,
<br /> MEANS OF EGRESS: OCCUPANCY SEPARATION REQUIREMENTS: 3. THE HEIGHT OF HANDRAILS AND GUARDS SHALL BE MEASURED VERTICALLY TO THE TOP OF THE GUARD OR RAIL
<br /> THE SCOPE OF WORK CONTAINED HEREIN SHALL RELOCATE THE MEANS OF EGRESS OF THE EXISTING BUILDING. WHERE FROM THE WALKING SURFACE ADJACENT THERETO. (IBC 1012)
<br /> F-1 TO S-1: NO SEPARATION REQUIREMENT 4. HANDRAIL SHAPE: CIRCULAR CROSS SECTION WITH OUTSIDE DIAMEfER ? 1-1/4 IN. TO S 2 IN. OR NON-CIRCULAR
<br /> WORK MAY TEMPORARILY IMPEDE EGRESS, THE CONTRACTOR SHALL COORDINATE WORK WITH THE OWNER AND BOEING SECURITY & F-1 TO B: NO SEPARATION REQUIREMENT CROSS SECTION WITH PERIMEfER ? 4 IN. TO S 6-1/4 IN. AND LARGEST CROSS SECTION S 2-1/4 IN. WITH ROUNDED
<br /> FIRE PROTECTION IN ORDER TO MAINTAIN CLEAR, RECOGNIZABLE AND SAFE EGRESS FOR BUILDING OCCUPANTS DURING CONSTRUCTION S-1 TO B: NO SEPARATION REQUIREMENT EDGE RADIUS ? 1/8 IN.). (IBC 1012.3) . �
<br /> ACTIVITIES. 5. HANDRAIL HEIGHT ? 34 IN. TO S 38 IN. ABOVE THE SURFACE OF THE TREAD, MEASURED VERTICALLY FROM THE TOP OF '
<br /> EXIT ACCESS TRAVEL DISTANCE: MEANS OF EGRESS THE RAIL FROM THE LEADING EDGE OF THE TREAD. A CLEARANCE OF NOT LESS THAN 1-1/2 IN. SHALL BE PROVIDED BETWEEN -
<br /> A. THE WIDTH OF MEANS OF EGRESS SHALL BE MEASURED IN THE CLFAR AT THE NARROWEST POINT OF THE EXIT COMPONENT UNDER BETWEEN RAIL AND WALL. (IBC 1012.1, IBC 1012.6)
<br /> THE SCOPE OF WORK CONTAINED HEREIN SHALL NOT CAUSE EXIT ACCESS TRAVEL DISTANCES TO EXCEED CODE-ALLOWED DISTANCES. CONSIDERATION. PROJECTIONS WHICH DO NOT EXCEED 4-INCHES ON EACH SIDE ARE PERMITTED BEfWEEN THE HEIGHTS OF 27 AND 80 6. HANDRAIL-GRIPPING SURFACES SHALL BE CONTINUOUS, WITHOUT INTERRUPTION BY NEWEL POSTS OR OTHER
<br /> INCHES. HANDRAILS SERVING STAIRS AND RAMPS ARE PERMITTED TO PROTRUDE 4.5-INCHES FROM THE WALL. (IBC 1003.3.3) OBSTRUCTIONS. (IBC 1012.4) �
<br /> ACTIVE FIRE PROTECTION SYSTEMS: 7. HANDRAILS SHALL RETURN TO A WALL, GUARD OR THE WALKING SURFACE OR SHALL BE CONTINUOUS TO THE
<br /> THE EXISTING BUILDING DESIGN INCLUDES A COMPLEfE AUTOMATIC SPRINKLER PROTECTION AND FIRE ALARM SYSTEM. B. MEANS OF EGRESS SHALL BE DESIGNED AND MAINTAINED TO PROVIDE HEADROOM NOT LESS THAN 7 FT 6 INCHES WITH PROJECTIONS HANDRAIL OF AN ADJACENT STAIR FLIGHT OR RAMP RUN. AT STAIRWAYS WHERE HANDRAILS ARE NOT CONTINUOUS
<br /> THE SCOPE OF WORK CONTAINED HEREIN SHALL NOT ALTER THESE EXISTING SYSTEMS WITH THE EXCEPTION OF FROM THE CEILING NOT LESS THAN 6 Fi 8 IN. NOMINAL HEIGHT ABOVE THE FINISHED FLOOR. THE MINIMUM CEILING HEIGHT SHALL BE BEiWEEN FLIGHTS, THE HANDRAILS SHALL EXTEND HORIZONTALLY AT LEAST 12 INCHES BEYOND THE TOP RISER
<br /> POTENTIAL RECONFIGURATION OF BRANCH LINES AS REQUIRED BY NEW SPACE CONFIGURATIONS. ALL FIRE MAINTAINED FOR NOT LESS THAN ONE-HALF OF THE CEILING AREA OF ANY ROOM OR SPACE (IBC 1003.3.1). AND CONTINUE TO SLOPE FOR THE DEPTH OF ONE TREAD BEYOND THE BOTTOM RISER. (IBC 1012.5)
<br /> PROTECTION SYSTEM SHUTDOWNS AND TIE-INS SHALL BE COORDINATED WITH BOEING SECURITY & FIRE PROTECTION. 8. GUARDS ARE REQUIRED TO PREVENT FALLS OVER THE OPEN SIDE WHEN MEANS OF EGRESS IS MORE THAN 30 IN.
<br /> C. ONCE A GIVEN LEVEL OF EXIT PROTECTION IS ACHIEVED, SUCH LEVEL OF PROTECTION SHALL NOT BE REDUCED UNTIL ARRIVAL AT THE ABOVE FLOOR OF GRADE BELOW. (IBC 1013.1)
<br /> EXIT DISCHARGE. (IBC 1020.1 9. GUARDRAIL HEIGHT MINIMUM: 42 IN. (IBC 1013.2)
<br /> PORTABLE FIRE EXTINGUISHERS (TO BE APPROVED BY BOEING FIRE PROTECTION) � 10. OPEN GUARDS SHALL HAVE BALUSTERS OR ORNAMENTAL PATTERN TO PREVENT 4 IN. DIAMETER SPHERE FROM
<br /> D. AN EXIT ENCLOSURE SHALL NOT BE USED FOR ANY PURPOSE THAT INTERFERES WITH ITS FUNCTION AS A MEANS OF EGRESS. (IBC PASSING TNROUGH ANY OPENING UP TO A HEIGHT OF 34 INCHES. FROM 34 INCHES TO 42 INCHES ABOVE THE WALKING -
<br /> 1. PORTABLE FIRE EXTINGUISHERS SHALL BE PLACED SO AS TO COMPLY WITH THE TRAVEL DISTANCE REQUIREMENTS OF NFPA-10 FOR THE 1020.1) EXIT CONSTRUCTION SHALL MEET THE FOLLOWING: SURFACES, A SPHERE 8 INCHES IN DIAMETER SHALL NOT PASS. (IBC 1013.3) EXCEPTION: THE TRIANGULAR OPENINGS � ;
<br /> OCCUPANCY CLASSIFICATION OF THE SPACE AND SHALL BE INSTALLED PER IFC 906, NFPA 10, AND BOEING FIRE PROTECTION FORMED BY THE RISER, TREAD, AND BOTTOM ELEMENT OF A GUARDRAIL AT THE OPEN SIDE OF A STAIR SHALL BE OF �� ,
<br /> REQUIREMENTS. SUCH SIZE THAT A SPHERE 6 IN. IN DIAMEfER SHALL NOT PASS THROUGH THE TRIANGULAR OPENING.
<br /> 2. PORTABLE FIRE EXTINGUISHERS SHALL 8E OF THE RECHARGEABLE TYPE AND SHALL BE U.L LISTED, AND F.M. APPROVED. E. PENEfRATIONS INTO AND OPENINGS THROUGH AN EXIT ENCLOSURE SHALL BE PROHIBITED EXCEPT FOR THE FOLLOWING: (IBC 1020.1.2)
<br /> 3. TYPE, SIZE, LOCATION, QUANTITY AND MOUNTING OF FIRE EXTINGUISHERS SHALL BE APPROVED BY THE AUTHORITIES HAVING JURISDICTION AND T. EXIT SIGNS
<br /> BY BOEING FIRE PROTECTION: 1. ELECTRICAL CONDUIT SERVING THE ENCLOSURE 1. EXITS AND EXIT ACCESS DOORS SHALL BE MARKED BY AN APPROVED SIGN READILY VISIBLE FROM ANY DIRECTION
<br /> 2. REQUIRED EXIT DOORS OF EXIT TRAVEL (IBC 1011.1)
<br /> PROVIDE DRY-CHEMICAL FIRE EXTINGUISHERS TO BE 3A:406:C AND BY AMEREX 3. DUCTWORK AND EQUIPMENT SERVING THE EXIT 2. ACCESS TO EXITS SHALL BE MARKED BY APPROVED, READILY VISIBLE SIGNS IN CASES WHERE THE EXIT OR THE PATH
<br /> MAXIMUM COVERAGE PER EXTINGUISHER - 11,250 SQ.FT. 4. SPRINKLER PIPING / STANDPIPES OF EGRESS TRAVEL IS NOT READILY APPARENT TO THE OCCUPANTS. EXIT SIGN PLACEMENT SHALL BE SUCH THAT NO
<br /> MAXIMUM TRAVEL DISTANCE TO EXTINGUISHER - 75' 5. ELECTRICAL RACEWAY SERVING THE EXIT ENCLOSURE AND TERMINATING AT A STEEL BOX NOT EXCEEDING 16 SQ. IN. POINT IN THE EXIT ACCESS CORRIDOR IS MORE THAN 100 Ff FROM THE NEAREST EXTERNALLY ILLUMINATED SIGN AND IS �
<br /> F. WHERE TWO EXITS OR TWO EXIT ACCESS DOORS ARE REQUIRED, THEY SHALL BE PLACED AT A DISTANCE APART EQUAL TO NOT LESS NOT IN EXCESS OF THE MARKED RATING FOR INTERNALLY ILLUMINATED SIGNS. (IBC 1011.1)
<br /> THAN ? THE MAXIMUM OVERALL DIAGONAL DIMENSION OF THE BUILDING (FULLY SPRINKLER PROTECTED). (IBC 1015.2.1) MINIMUM NUMBER 3. EXTERNALLY AND INTERNALLY ILLUMINATED SIGNS SHALL BE LEGIBLE IN BOTH THE NORMAL AND EMERGENCY
<br /> OF SEPARATE MEANS OF EGRESS: (IBC TABLE 1019.1 AND LSC TABLE 7.4.1.2) LIGHTING MODE. (IBC 1011.5)
<br /> G. 1- 500 OCCUPANTS: 2 EXITS 500- 1000 OCCUPANTS: 3 EXITS OVER 1000 OCCUPANTS: 4 EXITS INTERIOR FINISH RATINGS �
<br /> H. EXITS SHALL DISCHARGE DIRECTLY TO THE EXTERIOR OF THE BUILDING, UNLESS OTHERWISE PERMITTED BY IBC SECTION 1024.1. THE INTERIOR WALL AND CEILING FINISH MATERIALS FOR SPRINKLER-PROTECTED GROUP B OCCUPANCIES SHALL BE MINIMUM �
<br /> EXIT DISCHARGE SHALL BE AT GRADE OR SHALL PROVIDE DIRECT ACCESS TO GRADE. THE EXIT DISCHARGE SHALL NOT REENTER BUILDING. CLASS B IN EXIT ENCLOSURES AND PASSAGEWAYS AND CLASS C IN CORRIDORS AND ROOMS AND ENCLOSED SPACES AS
<br /> EXISTING BUILDING INFORMATION: (IBC 1024.1) DEFINED IN ACCORDANCE WITH ASTM E84, I.E. FLAME SPREAD 76-200, SMOKE DEVELOPED 0-450. (IBC TABLE 803.5)
<br /> I. EXIT PASSAGEWAY ENCLOSURES SHALL HAVE WALLS, FLOORS AND CEILINGS OF NOT LESS THAN A 1-HOUR FIRE RESISTANCE RATING (IBC 1023.3) MEZZANINES
<br /> APPLICABLE CODES AND STANDARDS
<br /> A) EACH OCCUPANT OF A MEZZANINE SHALL HAVE ACCESS TO AT LEAST TWO INDEPENDENT MEANS OF EGRESS WHERE THE
<br /> INTERNATIONAL BUILDING CODE, 2012 (IBC), WITH WASHINGTON AMENDMENTS COMMON PATH OF EGRESS TRAVEL EXCEEDS THE LIMITATIONS. WHERE A STAIRWAY PROVIDES A MEANS OF EXIT ACCESS FROM .
<br /> INTERNATIONAL MECHANICAL CODE, 2012 (IMC) A MEZZANINE, THE MAXIMUM TRAVEL INCLUDES THE DISTANCE TRAVELED ON THE STAIRWAY MEASURED IN THE PLANE OF THE
<br /> INTERNATIONAL FIRE CODE, 2012 (IFC)
<br /> OCCUPANCY LOAD FACTORS TREAD NOSING. (IBC 505.3)
<br /> UNIFORM PLUMBING CODE, 2012 (UPC) OCCUPANT LOAD FACTOR
<br /> NFPA 70, NATIONAL ELECTRICAL CODE (NEC), 2011 OCCUPANCY SMOKE CONTROL _
<br /> NFPA 101, LIFE SAFEIY CODE (LSC), 2012 SQ.Ff. PERSON) • ,
<br /> IN ACCORDANCE WITH SECTION 104.11 OF IBC, "ALTERNATIVE MATERIAL, DESIGN AND MEfHODS OF CONSTRUCTION" A PASSIVE
<br /> NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS, 2010 BUSINESS 100 GROSS SMOKE CONTROL SYSTEM IS PROVIDED. • -
<br /> NFPA 10, STANDARD FOR PORTABLE FIRE EXTINGUISHERS, 2010
<br /> NFPA 14, STANDARD FOR THE INSTALLATION OF STANDPIPE AND HOSE SYSTEMS, 2010
<br /> NFPA 20, STANDARD FOR THE INSTALLATION OF STATIONARY PUMPS FOR FIRE PROTECTION, 2010 STORAGE/MECHANICAL 300 GROSS FIRE EXTINGUISHERS (PER BOEING FIRE PROTECTION)
<br /> NFPA 24, STANDARD FOR THE INSTALLATION OF PRIVATE FIRE SERVICE MAINS AND THEIR APPURTENANCES, 2010 1. FIRE EXTINGUISHERS SHALL BE PLACED SO AS TO COMPLY WITH THE TRAVEL DISTANCE REQUIREMENTS OF NFPA-10 FOR �
<br /> SPECIAL INDUSTRIAL AREAS 300 GROSS SQ.FT. THE OCCUPANCY CLASSIFICATION OF THE BUILDING. FIRE EXTINGUISHERS SHALL BE OF THE RECHARGEABLE 1YPE AND
<br /> BUILDING SPECIFICS AND CONSTRUCTION REQUIREMENTS
<br /> SHALL BE U.L LISTED, AND F.M. APPROVED.
<br /> OCCUPANCY: MIXED NON-SEPARATED OCCUPANCY NON-CONCENTRATED ASSEMBLY 15 NET 2. FIRE EXTINGUISHERS IN THE OFFICE AND SUPPORT AREAS ARE TO BE SIX POUND (6 LBS.) UNITS (UNLESS OTHERWISE '
<br /> INDUSTRIAL: F-1 SPECIFIED) AND EQUIPPED WITH MOUNTING BRACKETS AND APPROPRIATE DECALS. THEY SHALL BE MOUNTED AT 42 IN. AFF.
<br /> STORAGE OCCUPANCY, MODERATE HAZARD (S-1) IBC 311.3 LOCKER ROOMS 50 GROSS
<br /> BUSINESS OCCUPANCY (B) IBC 304 3. FACTORY AREAS SHALL BE CONSIDERED MODERATE HAZARD. PROVIDE CLEAN AGENT TYPE (HALON 1211 OR HALOTRON 1)
<br /> AND A MINIMUM 2A:lOB:C RATING. _
<br /> MINIMUM CONSTRUCTION: TYPE II-B. FULLY FIRE SPRINKLER-PROTECTED •
<br /> 4. DRY-CHEMICAL FIRE EXTINGUISHERS TO BE 3A:408:C AND BY AMEREX
<br /> ACTUAL BUILDING AREA. HEIGHT. AND STORIES: AS PERMITTED BY IBC 1004.1.1 (EXCEPTION) THE CITY OF EVERETT BUILDING OFFICIAL HAS APPROVED THE USE "
<br /> BUILDING ARFA (GROSS) FIRST FLOOR: 224,742 SF OF ACTUAL OCCUPANT LOADS PROVIDED BY BOEING IN LIEU OF USING OCCUPANT LOAD FACTORS IN TABLE 1004.1.1 FOR EXIT STAIRS
<br /> HEIGHT: 59 Ff BUSINESS OCCUPANCIES 1. PENETRATIONS INTO AND OPENINGS THROUGH INTERIOR EXIT STAIRWAYS AND RAMPS ARE PROHIBITED EXCEPT FOR REQUIRED EXIT DOORS, .
<br /> J. EGRESS CAPACITY FOR APPROVED COMPONENTS OF MEANS OF EGRESS SHALL BE BASED ON THE FOLLOWING FOR A EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT VENTILATION, OR PRESSURIZATION, SPRINKLER PIPING, STANDPIPES, -
<br /> ALLOWABLE BUILDING AREA AND HEIGHT: ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION SYSTEMS AND ELECTRICAL RACEWAY SERVING THE INTERIOR EXIT
<br /> FULLY SPRINKLER-PROTECTED FACILITY: (IBC 1005.3.1, 1005.3.2 AND LSC TABLE 7.3.3.1) STAIRWAY AND RAMP AND TERMINATION AT A STEEL BOX NOT EXCEED 16 SQUARE INCHES. SUCH PENETRATIONS SHALL BE PROTECTED IN
<br /> THE AREA OF A GROUP B, F, M OR S BUILDING NO MORE THAN ONE STORY ABOVE GRADE PIANE OF ANY CONSTRUCTION TYPE, OR THE ACCORDANCE WITH SECTION 714. THERE SHALL BE NO PENETRATIONS OR COMMUNICATING OPENINGS, WHETHER PROTECTED OR NOT,
<br /> • AREA OF A GROUP A-4 BUILDING NO MORE THAN ONE STORY ABOVE GRADE PLANE OF OTHER THAN TYPE V CONSTRUCTION, SHALL NOT BE LEVEL COMPONENTS: 0.20 IN. / PERSON
<br /> LIMITED WHERE THE BUILDING IS PROVIDED WITH AN AUTOMATIC SPRINKLER SYSTEM THROUGHOUT IN ACCORDANCE WITH SECTION STAIR COMPONENTS: 0.30 IN. / PERSON BETWEEN ADJACENT INTERIOR EXIT STAIRWAYS AND RAMPS. MEMBRANE PENETRATIONS SHALL BE PERMITTED ON THE OUTSIDE OF THE �
<br /> 903.3.1.1 AND IS SURROUNDED AND ADJOINED BY PUBLIC WAYS OR YARDS NOT LESS THAN 60 FEEf IN WIDTH. (IBC 507.3) INTERIOR EXIT STAIRWAY AND RAMP. SUCH PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH SECTION 714.3.2. (IBC 1022.5)
<br /> ALLOWABLE BUILDING AREA: UNLIMITED K. EXIT TRAVEL DISTANCES 2. EQUIPMENT AND DUCTWORK FOR INTERIOR EXIT STAIRWAY AND RAMP VENTILATION AS PERMIITED BY SECTION 1022.5 SHALL COMPLY WITH
<br /> ALLOWABLE BUILDING HEIGHT: UNLIMITED ONE OF THE FOLLOWING ITEMS (IBC 1022.6):
<br /> 1. IN GROUP B, F, AND S OCCUPANCIES PROTECTED THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER . -
<br /> ACTIVE FIRE PROTECTION SYSTEMS SYSTEM, COMMON PATHS OF TRAVEL SHALL NOT EXCEED 100 Ff (IBC 1014.3, LSC TABLE 40.2.5) A. SUCH EQUIPMENT AND DUCTWORK SHALL BE LOCATED EXTERIOR TO THE BUILDING AND SHALL BE DIRECTLY CONNECTED TO THE
<br /> COMPLETE AUTOMATIC SPRINKLER PROTECTION SHALL BE PROVIDED. (IBC 903.2.3) 2. IN GROUP F-1 BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM, INTERIOR EXIT STAIRWAY AND RAMP BE DUCTWORK ENCLOSED IN CONSTRUCTION AS REQUIRED FOR SHAFTS. �
<br /> A FIRE ALARM SYSTEM IS REQUIRED (IBC 907.2.2, LSC 40.3.4.1) THE TRAVEL DISTANCE SHALL NOT EXCEED 250 FEET. (18C 1016.2) B. WHERE SUCH EQUIPMENT AND DUCTWORK IS LOCATED WITHIN THE INTERIOR EXIT STAIRWAY AND RAMP, THE INTAKE AIR SHALL 8E TAKEN
<br /> PORTABLE FIRE EXTINGUISHERS SHALL BE INSTALLED PER IFC, NFPA 10, AND BOEING FIRE PROTECTION. (IFC 906) DIRECTLY FROM THE OUTDOORS AND THE EXHAUST AIR SHALL BE DISCHARGED DIRECTLY TO THE OUTDOORS, OR SUCH AIR SHALL BE
<br /> 3. WHERE MORE THAN ONE EXIT OR EXIT ACCESS DOORWAY IS REQUIRED, THE EXIT ACCESS SHALL BE ARRANGED SUCN CONVEYED THROUGH DUCTS ENCLOSED IN CONSTRUCTION AS REQUIRED FOR SHAFTS y
<br /> ASSEMBLY AND ADMINISTRATIVE AREAS: ORDINARY HAZARD THAT THERE ARE NO DEAD ENDS IN CORRIDORS MORE THAN 20 FEEi IN LENGTH. (IBC 1018.4) C. WHERE LOCATED WITHIN THE BUILDING, SUCH EQUIPMENT AND DUCTWORK SHALL BE SEPARATED FROM THE REMAINDER OF THE
<br /> MINIMUM 2-A RATED SINGLE EXTINGUISHER;
<br /> BUILDING, INCLUDING OTHER MECHANICAL EQUIPMENT, WITH CONSTRUCTION AS REQUIRED FOR SHAFTS.
<br /> MAXIMUM 11,250 SQ.FT. COVERAGE PER EXTINGUISHER; 4. IN BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM, DEAD-END IN EACH CASE, OPENINGS INTO THE FIRE-RESISTANCE-RATED CONSTRUCTION SHALL BE LIMITED TO THOSE NEEDED FOR MAINTENANCE AND
<br /> 75' MAXIMUM TRAVEL DISTANCE TO EXTINGUISHER CORRIDORS IN 5. GROUP F, S AND B OCCUPANCIES SHALL NOT EXCEED 50 FT. (IBC 1018.4, EXCEPTION 2) OPERATION AND SHALL BE PROTECTED BY OPENING PROTECTIVES IN ACCORDANCE WITH SECTION 716 FOR SHAFT ENCLOSURES. THE
<br /> PASSIVE FIRE PROTECTION SYSTEMS L. MINIMUM CLEAR WIDTH OF MEANS OF EGRESS DOORS SHALL BE 32 INCHES. (IBC 1008.1.1) INTERIOR EXIT STAIRWAY AND RAMP VENTILATION SYSTEMS SHALL BE INDEPENDENT OF OTHER BUILDING VENTILATION SYSTEMS
<br /> EXTERIOR WALLS SHALL HAVE A FIRE RESISTANCE AND OPENING PROTECTION RATING AS SEf FORTH IN TABLES 601 AND 602 OF THE IBC AND IN M. DOOR ASSEMBLIES IN FIRE BARRIERS SHALL BE OF AN APPROVED TYPE WITH APPROPRIATE FIRE PROTECTION RATING ���G� ��' �i���� ��� {='
<br /> ACCORDANCE WITH SUCH ADDITIONAL PROVISIONS AS SET FORTH IN CHAPTER 6. DISTANCES SHALL BE MEASURED AT RIGHT ANGLES FROM THE FOR THE LOCATION IN WHICH INSTALLED AND SHALL COMPLY WITH THE FOLLOWING: ���J,��'�� ��r� �.�����`�' �
<br /> PROPERTY LINE. THE ABOVE PROVISIONS SHALL NOT APPLY TO WALLS AT RIGHT ANGLES TO THE PROPERTY LINE. BUILDINGS LOCATED ON THE . ,
<br /> SAME PROPERTY SHALL BE ASSUMED TO HAVE A PROPERTY LINE BEiWEEN THEM. 1. FIRE DOORS SHALL BE INSTALLED IN ACCORDANCE WITH IBC 715 AND NFPA 80, STANDARD FOR FIRE DOORS AND
<br /> CONSTRUCTION TYPE II-B WINDOWS. (IBC 715.4) 1.
<br /> 2. FIRE DOORS SHALL BE OF A DESIGN THAT HAS BEEN TESTED TO MEEf THE CONDITIONS OF ACCEPTANCE OF NFPA .
<br /> TYPE II CONSTRUCTION IS THAT TYPE OF CONSTRUCTION IN WHICH THE BUILDING ELEMENTS LISTED IN TABLE 601 ARE OF NONCOMBUSTIBLE 252, STANDARD METHODS OF FIRE TESTS OF DOOR ASSEMBLIES. (IBC 715) .
<br /> MATERIALS, EXCEPT AS PERMITTED IN IBC SECTION 603 AND ELSEWHERE IN THE IBC. (IBC 602.2) 3. UNLESS OTHERWISE SPECIFIED, FIRE DOORS SHALL BE SELF-CLOSING OR AUTOMATIC-CLOSING. (IBC 715.4.7)
<br /> �
<br /> N. DOORS SHALL SWING IN THE DIRECTION OF EGRESS WHEN SERVING 50 OR MORE OCCUPANTS OR A GROUP H N
<br /> N
<br /> OCCUPANCY OR, IN AN EXIT ENCLOSURE. (IBC 1008.1.2) � •
<br /> �
<br /> oi
<br /> SYM REVISION BY APPROVED DATE SYM REVISION BY APPRQVED DATE DRAWN DATE SUBTITLE CURRENT REVISION SYMBOL DATE
<br /> H SC ESGN B D/R CHECKED ,o ,5 ,5 COD E ANALYS I S / / N _
<br /> 16123 A 10 10 16 0
<br /> 1 AIRLOCK EXPANSION - RECORD WBS 16123 ALH KML 10/10/16 KML 10 15 15 •
<br /> SPECIFICATION IS APPROVED SHEEf �
<br /> � ENGINEER TITLE FACTORY TRANSFORMATION 40-30 AIRLOCK EXPANSION � ,
<br /> BOE,�� APPROVED BY DEPT. DATE KML 10 15 15 .
<br /> CHECKED A �
<br /> APPROVED B U I LD I N G 40�0� 1 �oe No. WO 15/2899-201 coMP rvo. �
<br /> APPROVED ARCHITECTIJRAL MASTER EVERETf, Wq °wc No. q.0-021 -A3