Laserfiche WebLink
�, <br /> �� <br /> L. <br /> �i �z MECHANICAL I�,OTES: <br /> O 1. DUCT MATERIAL IS 26 GA. GALV. AND FLEX DUCT. DUCTWORK SHALL BE SUPPORTED PER 2015 IMC <br /> WAC CHAPTER 6. SECTION 603 <br /> 2. MATERIAL IN DUCTS SHALL HAVE A FLAME SPREAD INDEX OF LESS THAN 25, SMOKE DEVELOPMENT <br /> OF 50 PER 2015 IMC WAC CHAPTER 6. SECTION 602 • <br /> 3. LOW PRESSURE DUCT SYSTEMS SHALL HAVE LONGITUDINAL AND TRANSVERSE JOINTS, SEAMS AND <br /> CONNECTIONS OF SUPPLY AND RETURN DUCTS AND PLENUMS SECURELY FASTENED AND SEALED WITH <br /> WELDS, GASKETS, MASTICS (ADHESIVES), MASTIC-PLUS EMBEDDED-FABRIC SYSTEMS -0R APPROVED TAPES � <br /> INSTALLED IN ACCORDANCE WITN 2015 IMC WAC CHAPTER 6 SECTION 603.9. , <br /> CD-1 CD-1 <br /> 10" 10" 4. WNEN ISOLATION SLEEVES ARE USED AT LINE CONNECTIONS TO PLENUMS, THEN THEY SHALL COMPLY Y <br /> WITH IMC CHAPTER 6 <br /> WALL MOUNT <br /> 1 RETURN 5. 10" DIFFUSERS WITH NO MANUAL DAMPERS. USE FLOW CONTROLS AT WYES, TYPICAL AS NOTED ON PLAN � <br /> 2� �0, �� <br /> 1 0 1 2 6. MINIMUM OUTSIDE AIR VENTILATION PER 2015 IMC WAC CHAPTER 4, TABLE 403.3.1.1. <br /> ,� Q ,� 2 7. OUTSIDE AIR DAMPERS SHALL COMPLY WITH 2O15 WSEC, SECTION C403.2.4.3: . <br /> HP-1 <br /> �1� 8. SINGLE PACKAGE UNITARY FAN COOLING UNITS HAVING A TOTAL COOLING CAPACITY OF GREATER THAN <br /> 2'�O o T TCURBF 20,000 Btu/h REQUIRE ECONOMIZERS PER WSEC 403.3. EXCEPT AS PERMITTED BY C403.3 EXCEPTION 1 <br /> co _ _ _ _ _ _ _ _ � _ _ _ _ <br /> �. <br /> SUPPLY PLENUM <br /> L <br /> #Pws�3� MECHANICAL NOTES: (cont.) � - <br /> OCCUPIED SET POINT MECHANICAL EQUIPMENT INSTALLATION IN OR ON THIS BUILDING SHALL BE IN ACCORDANCE WITH <br /> TO BE CONTROLLED BY THE REQUIREMENTS OF THE 2015 IMC WAC CHAPTER 6. <br /> nLIGHT OCCUPANCY " <br /> SENSORS ROUND FLEX DUCT SHALL BE U.L. LISTED CLASS 1, STANDARD 181 - FACTORY MADE AIR DUCTS AND AIR <br /> CONNECTORS: MEASURED IN ACCORDANCE TO ASTM C 518 OR ASTM C 177 AT 75DEG F MEAN <br /> TEMPERATURE. INSTALLATION SHALL BE IN ACCORDANCE WITH MANUFACTURES INSTALLATION INSTRUCTIONS <br /> CD-1 CD-1 <br /> 10" 10" MECHANICAL DRAWINGS SHOW DUCTWORK SIZES TO BE CLEAR INSIDE DIMENSION. <br /> DUCT INSULATION SHALL COMPLY WITH 2O15 IMC WAC CHAPTER 6, SEC. 604. <br /> �, <br /> ELECTRICIAN MUST VERIFY ALL ELECTRICAL REQUIREMENTS AND LOCATIONS. <br /> THERMOSTAT SCHEDULING TO BE PERFORMED ON SITE BY OTHERS. <br /> ALL HVAC EQUIPMENT LEAVES FACTORY WIRED FOR 240 VOLT OPERATION ' <br /> THE ACCEPTABLE OPERATING RANGE FOR THE 240V & 208V TAPS ARE: � <br /> OTAP RANGE <br /> 240 253-216 � <br /> M EC HAN I �AL P LAN 20� 220_�8� <br /> 1/4" = 1'-0" SITE MECHANICAL CONTRACTOR IS RESPONSIBLE FOR MAKING SURE THE RIGHT TAP IS CONNECTED FOR <br /> THE APPUED SITE VO�TAGE. `� <br /> MINIMUM VENTILATION RATES PER IMC SECTION 403 AIR FILTERS IN HVAC UNITS OR SYSTEMS ARE TO BE CHANGED EVERY 30 DAYS BY OTHERS ON SITE. � ' <br /> Rp <br /> room# name Az(sf) sf/1000 Occ. Dens Pz(calc) Pz (used} (cfmjperson) Ra(cfm/sf) Vbz(cfm) REGISTER AIR FLOW TEST AND BALANCE OF HVAC SYSTEM TO BE PROVID�D AND PERFORMED BY OTHERS ON SITE. . <br /> 1 Classroom 817 0.817 35 29 29 10 0.12 388 - <br /> 388cfm HVAC SITE CONTRACTOR IS RESPONSIBLE FOR BALANCING THE SYSTEM. (2015 IMC WAC 403.3.3.1.5) <br /> Az=room area(sf) <br /> Occ. Dens=occupant density(from Table 403.3) ' <br /> Pz(calc) =zone population or occupant quantity(calculated) <br /> Pz(used) =zone population or occupant quantity(user can override the calculatian-increase only) <br /> Rp=people outdoor airFlow rate in breathing zone (cfm/person) �� <br /> Ra=area outdoor airflow rate in breathing zone (cfm/sf) <br /> Vbz=Breathin zone outdoor airflow rate per eq.4-1( Rp*Pz+Ra*Az) ' ' <br /> PACKAGE *SPVU* HIGH EFFICIENCY WALL MOUNT HEAT PUMP - SCHEDULE <br /> DOAS/ERV/ELECTRICAL 1� DOAS/ERV/ELECTRICAL � COOLING CAPACITY 3� MEATING CAPACITY �4 DOAS UNIT HEAT STRIPS <br /> ENERGY RECOVERY ELECT. WFORM. CT. INF RM. . <br /> DOAS LOW VENTILATION MODE FULL VENTILATION MODE <br /> COMP TOTAL ECON. COOL SENS. COOL SENS. HTG HTG OUTQOOR ELEC. ELEC. OPER. <br /> BARD TYPE CFM BLR. 100% ERV ECM ECM OUTSIDE ENT ENT CAP. CAP. CAP. CAP. OUTSIDE CAP. CAP. SUMMER �B/WB HRS HRL WINTER INDOOR WHR HEAT HEAT WGT. ADDITIONAL <br /> TAG QTY MODEL # TONS SCROLL NOM. TYPE. FREEFLOW OSA V-PH ERV BLOWER V-PH ERV BLOWER DB DB WB EER IPLV BTUH BTUH BTUH BTUH DB COP BTUH BTUH EFFICIENT DEG'S BTUH BTUH EFFICIENT DB MOP V-PH MCA MOP CKT V-PH MCA BTUH CKT KW BTUH LBS. REMARKS <br /> � PART/FUL VENTIL .MOTOR � MOTOR PART LOAD PART LOA� FULL LOAD FULL LOAD PART/LOAD FUIL/LOAD . . � <br /> 750 388 AMPS-1.3 AMPS-.87 AMPS-2.2 AMPS-1.74 �- <br /> HP-1 1 C36HA-AtOZP4XXR 3 2-STAGE �100 ECM NO 45� 230/1 WATTS-296 WATTS-95 230/1 WATTS-497 WATTS-192 95 80 67 11.Q 14.5 23.4K 18.5K 35K 26:3K 47 3.3 22.7K 31K 65% 95/70 6,318 1,711 80% 1,711 23,328 230/1 27 40 A 240/1 52 60 B 10 34,130 678 1, 2, 3, 4, 5, 6, 7, 8 <br /> ADDITIONAI. REMARKS; c3sH� The sequence of operation for the Integrated QOAS system. � • . <br /> 1 - PLAN # --------- <br /> 2 - INC�UDE BARD WALL CURB #TCURBF3642A-4. ERV Wotts - Low 296 Watts Blower Full Load 192 Watts 1. Upon a call from the occupancy sensor the(DOAS) ERV and the indoor(ECM} motor will <br /> 3 - THERMOSTAT, BARD # 84Q3-O60, 7-DAY PROGRAMMABLE. ERV Am s - Low 1.3 Am s Blower Full Load 1 J4 Am s start in low vent mode and ventilate the space continuously as occupied. <br /> 4 - WAI.L CO2 SENSOR. #8403-067 ERV CFM - Low 300 CFM Blower Part Load 95 Watts Note: 1 on the HVAC Schedule. � <br /> 5 - OCCUPANCY SENSOR, (SUPPLIED BY BLAZER) ERV Watts - Med 415 Watts Blower Part Load 0.87 Am s 2. Upon a call from the CO2 sensor the(DOAS) ERV and the indoor(ECM) motor will <br /> 6 - GPS (FIELD INSTALLED CONTROL KIT). ERV Am s - Med 1.8 Am s <br /> 7 - 2" Fi�TER. ERV CFM - Med 375 CFM Com ressor Full 2588 Watts change to full vent mode and ventilate the space until the CO2 sensor is satisfied and then <br /> 8 - ERV (DOAS) ENERGY RECOVERY. ERV Watts - Hi 497 Watts Com ressor Full 11.46 Am s revert back to the low vent mode during the occupied time. <br /> 9 - UNIT COLOR IS *BUCKEYE GRAY* ERV Am s - Hi 2.2 Am s Com ressor Part 1734 Watts Note: 2 on the HVAC Schedule. <br /> 10 - PRE INSTALLED OUTDOOR THERMOSTAT, SET AT 40DEG'S. ERV CFM - Hi 450 CFM Com ressor Part 7.99 Am s 3. The Heating and Cooling section will only work if there is a Heating or Cooling call from � <br /> ** M.C. TO REFER TO INSTALLATION INSTRUCTIONS FOR START UP AND EQUIPMENT SET. Outdoor Fon 380 Watts the thermostat. This action works entirely independent of the DOAS ventilation portion. <br /> ** M.C. TO CHECK SITE VOLTAGE AND SET CORRECT TAP ON TRANSFORMER. Oufdoor Fpn 1.67 Am s Note: 3&4 on the HVAC Schedule. <br /> ** M.C. TO SET AND PROGRAM THERMOSTAT PER CUSTOMERS REQUIREMENTS. 4. ThiS aCflOfl Will k@ep f@p@8tlllg ItS21f 8S fG'qt11fG'd by the OCCUpatlCy S21150f, CO2 sensor <br /> and Room Thermostat. t� <br /> 8-18-17 REVISE HEAT PUMP SCHEDULE,ADD SEQUENCE OF OP. RMS COPYRIGHT 2017, BLAZER INDUSTRIES, INC. � MODULAR Approved for Const: Job No: 19D31 ,� <br /> 9-6-17 ADD SUPPLY PLENUM NUMBER(#PWS131) LDG THIS MATERIAL IS THE EXCLUSIVE PROPERTY Classroom for.� � <br /> OF BLAZER INDUSTRIES, INC.AND SHALL ■■ File Copy: <br /> NOT BE REPRODUCED, USED, OR DISCLOSED � 2$ X 32 �C DA - Eve rett S■D■ <br /> �� INDUSTRIES,INC. <br /> TO OTHERS EXCEPT AS AUTHORIZED BY THE Drawn By: LDG � � <br /> DATE REVISION BY WRITTEN PERMISSION OF BIAZER INDUSTRIES. � �•b�azerind.com Wq. GOLD Pacific Mobile 17 BLMP-04 A9 W/� ' <br /> �� P.O.BOX489 ■ Aumsville,OR97325-0489 Issue Date: 9-6-�7 <br /> �, <br /> �. <br />