—PLANS PREPARED FOR:
<br /> ELECTRICAL SPECIFICATION:
<br /> 1. COMPLY WITH THE LATEST EDITION OF THE INTERNATIONAL BUILDING CODE, THE REQUIREMENTS OF ALL APPLICABLE MUNICIPAL AND S ri n t
<br /> EXISTING 100A SERVICE `./ STATE CODES AND REGULATIONS, AND UTILITY GUIDELINES. 4.\
<br /> Ly YM 2. PERFORM ALL VERIFICATION, OBSERVATIONS, TESTING AND EXAMINATION OF WORK PRIOR TO THE ORDERING OF ELECTRICAL EQUIPMENT
<br /> EXISTING UTILITY TRANSFORMER, 100A SERVICE FOR AND THE ACTUAL CONSTRUCTION. ISSUE A WRITTEN NOTICE OF ALL FINDINGS TO NE CONSTRUCTION MANAGER LISTING ALL 15395 SE 30TH PL
<br /> SPRINT. MALFUNCTIONS, FAULTY EQUIPMENT AND DISCREPANCIES. BELLEVUE,WASHINGTON 98007
<br /> EXISTING SPRINT 100A, 240V, 3W UTILITY
<br /> METER 0
<br /> 3. UNDERGROUND CONDUIT SHALL BE RIGID POLYVINYL CHLORIDE CONDUIT: SCHEDULE 40 CONFORMING TO UL ARTICLE 651: WESTERN
<br /> OM PLASTICS OR CARBON MANUFACTURER. COUPLINGS SHALL BE SUP-ON SOLVENT SEALED T PIPE: SOLVENT, WESTERN TYPE COMPATIBLE -PLANS PREPARED BY:
<br /> EXISTING 100A SERVICE WITH PVC DUCT, ALL BENDS SHALL BE 30" MINIMUM RADIUS. I N F I N I GYM
<br /> 4. NEUTRAL SHALL BE COLOR CODED, INSULATION SHALL BE CROSS-LINKED POLYETHYLENE.
<br /> NEW 100A RATED 2-POLE, 240V NEMA-3R SERVICE FROM ZERO TO I N F I N I G Y
<br /> MAIN FUSED DISCONNECT SWITCH EQUIPPED WITH 5. CONTRACTOR TO CONTACT ALL UTIUTIES FOR LOCATION OF
<br /> • „77--NEW (3) #1/0 AWG CU. AND (1) #5 AWG
<br /> 100A 'RK1" FUSES. 6. UNDERGROUND SERVICES. SERVICE LOCATIONS TO BE CONFIRMED PRIOR TO CONSTRUCTION. the solutions are endless
<br /> CU. GROUND IN 2" RMC A.F.G. AND RNC • _L L S 7. THE CONTRACTOR IS RESPONSIBLE FOR ALL PERMITTING, FIUNG, AND FEES IN CONJUNCTION WITH THE PROJECT. 2500 W.HIGGINS RD.SUITE 510
<br /> B.F.G. HOFFMAN ESTATES,IL 60169
<br /> 8. THE CONTRACTOR SHALL SCHEDULE ALL NECESSARY INSPECTIONS WITH THE PROPER AUTHORITIES AND INFORM AT&T 24-HOURS IN JOB NUMBER 499-035
<br /> ® NEW #4 AWG CU. GROUND ELECTRODE ADVANCE. ALL TICKETS AND INSPECTION VERIFICATIONS WILL BE SUBMITTED TO THE OWNER'S REPRESENTATIVE WITHIN 24-HOURS AFTER -SITE AGO;
<br /> CONDUCTOR CONDED TO (2) 5/8" DIA. THE INSPECTION HAS TAKEN PLACE.
<br /> NEW SPRINT 100A RATED, NEMA-3R X 10'-0" LONG COPPER CLAD GROUND 9. ALL EQUIPMENT, WIRING, AND MATERIALS MUST HAVE A UL LABEL
<br /> 120/240V-10-3W PPC CABINET. RODS SPACED A MN. OF 6'-0"APART. smartlink
<br /> CONTRACTOR TO REMOVE THE NEUTRAL 100A� --•.) 100A 10. ALL WORK SHALL BE DONE BY LICENSED ELECTRICAL CONTRACTOR AND PERFORMED IN A WORKMANLIKE MANNER AND SHALL PROCEED IN
<br /> TO GROUND BOND INSIDE PPC. } CAM-LOK RECEPTACLE MOUNTED TO PPC AN ORDERLY MANNER SO AS NOT TO HOLD UP THE PROGRESS OF THE PROJECT.
<br /> WIREDIN DIRECTLYRE PANEL MANUFACTURER,
<br /> 11. THOROUGHLY TEST ALL UNES, FEEDERS, EQUIPMENT, AND DEVICES WITH MAXIMUM LOADS TO ASSURE PROPER OPERATION 11410 NE 122ND WAY STE.102
<br /> TO MAIN FUSE. KIRKLAND,WA 98034
<br /> 100A/2P
<br /> �y ~• • 12. CONDUCTOR LENGTHS SHALL BE CONTINUOUS FROM TERMINATION TO TERMINATION WITHOUT SPUCES
<br /> •—• • FACTORY INSTALLED CABLE.
<br /> • ~• ' 13. PROVIDE PULL BOXES WHERE SHOWN AND/OR WHERE REQUIRED BY CODES AND/OR UTIUTY COMPANIES. ENGINEERING LICENSE:
<br /> 20A/2P •^� • 14. ALL CONDUIT ROUGH IN SHALL BE COORDINATED WITH THE MECHANICAL EQUIPMENT TO AVOID LOCATION CONFUCTS, CONTRACTOR SHALL �7�, 1O(, '
<br /> 20A/1 P •,--..---* • VERIFY ALL LOCATIONS. �� �'
<br /> NOTE 15. ALL WIRES SHALL BE TAGGED AT ALL PULL BOXES, J-BOXES, EQUIPMENT BOXES, AND CABINETS WITH APPROVED PLASTIC TAGS. c<,- 0 •, /,,
<br /> USE EXISTING 100 AMP METER SERVICE IF POSSIBLE. . "" <, /,_w� G,,),
<br /> 16. ALL BREAKERS IN PANEL BOXES SHALL BE IDENTIFIED WITH TYPE WRITTEN LABELS NEATLY PLACED ALONG SIDE OF THE BREAKER.
<br /> (8) = FACTORY INSTALLED "' ' r ' u3., c?
<br /> ALL OTHER CIRCUIT BREAKERS TO BE PROVIDED BY CONTRACTOR. 17. ALL FIRE RATED WALL AND FLOOR PENETRATIONS ARE TO BE CAULKED AND SEALED WITH A FIRE RESISTANT CAULKING TO MAINTAIN THE \'
<br /> BASED ON PROVIDED INFORMATION. ELECTRICAL CONTRACTOR TO VERIFY. INTEGRITY OF THE FIRE SEPARATION. 0
<br /> 18. UTIUZE SONNEBORN TYPE NP-1 CAULKING FOR SEALING ALL EXTERIOR WALL PENETRATIONS ? , ,'3981 <:(")
<br /> ;LC
<br /> SCALE: SCALE; - C7„" : q/STOL-
<br /> SINGLE LINE DIAGRAM (TYP) NONE 3 GENERAL ELECTRICAL NOTES NONE 2 ,.,, �s . ',0.
<br /> —DRAWING NOTICE:
<br /> THESE DOCUMENTS ARE CONFIDENTIAL AND ARE
<br /> THE SOLE PROPERTY OF SPRINT AND MAY NOT BE
<br /> REPRODUCED,DISSEMINATED OR REDISTRIBUTED
<br /> WITHOUT THE EXPRESS WRITTEN CONSENT OF
<br /> NEW PANEL "PP1" 100A, 120/240-10-3W, 60Hz, 100A M.C.B. SPRINT.
<br /> BUS VA BUS BUS VA —REVISIONS:
<br /> A B LOAD WIRE GND COND. AMPS A B AMPS COND. GND WIRE LOAD A , DESCRIPTION DATE BY REV
<br /> 7000 1 - - - - SPACE
<br /> 7000 NEW ECAB CABINET #3 #8 0'-2" 100 4 SPACE
<br /> - SPACE - - - - ® - - - - SPACE - ,
<br /> - SPACE - - - - 8 - - - - SPACE -
<br /> 400 9 - - - SPACE
<br /> 400 NEW BCAB CABINET #10 #10 0'-1" 20 12 SPACE
<br /> 600 NEW WORK LIGHT #12 #12 0'-0 3/4" 20 ® - - - - SPACE -
<br /> - SPACE - - - - 16 - - - - SPACE - ISSUED FOR CONSTRUCTION 11/29/18 EPR 0
<br /> - SPACE - - - - 0 - - - - SPACE - ISSUED FOR REVIEW 10/01/18 EPR A
<br /> -
<br /> - SPACE - - - - 20 - - - - SPACE - SITE NAME:
<br /> SPACE - - - - ® - - - - SPACE - WESTERN MEDICAL
<br /> - SPACE - - - - 24 - - - - SPACE -
<br /> TOTAL VA: BUS A:8000 BUS B:17400 CONNECTED VA:15400 AMPERES: BUS A:70 BUS B:70 TOTAL:140 r SPRINT SITE#:
<br /> RATED VOLTAGE: 120/208 1 PHASE 3 WIRE BRANCH POLES:24 SE52XC206
<br /> RATED AMPS: 100 CABINET:ISURFACE
<br /> FULL NEUTRAL BUS GROUND BUS HINGED DOOR ECLOSURE TYPE:NEMA-3R
<br /> BRANCH DEVICES CIRCUIT BREAKER SITE ADDRESS:
<br /> MAIN 1 100A BREAKER I I 4310 COLBY AVE
<br /> ALL NEW BREAKERS MUST MATCH&HAVE A MINIMUM AIC RATING OF 42,000 AMPS SYMETRICAL EVERETT,WA 98203-2338
<br /> NOTE:
<br /> (8) = FACTORY INSTALLED SHEET DESCRIPTION:
<br /> ALL OTHER CIRCUIT BREAKERS TO BE PROVIDED BY CONTRACTOR.
<br /> BASED ON PROVIDED INFORMATION. ELECTRICAL CONTRACTOR TO VERIFY. ELECTRICAL PLAN
<br /> SHEET NUMBER: -""- `'
<br /> AC PANEL SCHEDULES 1 E-2(;\,____/:27`),,,
<br /> NONE .
<br />
|