Laserfiche WebLink
10/1/2019Page 2 <br /> 6:54:3'}AlYI City of Everett 2 Z <br /> INSPECTION ACTIVITY REPORT <br /> 9/20/2019 9/23/2019 ELEC 09-FINAL SKB CORRECTION eTRAKiT Inspection 9/19/2019 4:25 PM Nicholas Riddell <br /> Request The work has been completed by a licensed <br /> electrician,we have pulled the permit.How <br /> do we get the lights back on,can you <br /> please come out and inspect the completed <br /> work thus far?Thank you! Please call <br /> 425.314.6883 when arriving on site to gain <br /> access to wharehouse space. <br /> Contact Name:Nicholas Riddell <br /> Site Address:2201 EVERETT AVE <br /> Phone:4253146883 <br /> e-Mail:riddellrealestate@gmail.com <br /> (9/23/2019 2:18 PM SKB) <br /> Grounding electrode conductor's must land <br /> on the ground bus or there needs to be a <br /> jumper between the equipment Grounding <br /> bar and the grounded bus. <br /> (9/23/2019 2:21 PM SKB) <br /> Grounding electrode conductor must land <br /> on the grounded bus or a jumper must be <br /> installed between the grounded bus and the <br /> equipment ground bar. <br /> 9/23/2019 9/23/2019 ELEC 05-SERVICE SKB PARTIAL APR <br /> 9/30/2019 9/30/2019 ELEC 09-FINAL SKB APPRVD-PER} As noted (9/30/2019 3:05 PM SKB) <br /> Project taken over on 9/19/2019 by <br /> electrical contractor no EWP#E1909-103. <br /> All inspections after that date should have <br /> been called in and resulted on that permit <br /> and not on this one. <br /> 9/30/2019 9/30/2019 ADMIN USE KLC APPROVAL <br /> ONLY** <br /> INSP12 <br /> CAWS YS TEM <br />