1/24/2020 Page 1 <br /> City of Everett <br /> 9:50:25AM <br /> INSPECTION ACTIVITY REPORT <br /> Permit No. M1906-072 Site Address 2230 RUCKER AVE <br /> Applied 6/21/2019 Applicant Lot <br /> Approved 6/21/2019 Owner TONYS HOUSE LLC Block <br /> Issued 6/21/2019 Contractor INFRASOURCE SERVICES LLC Tract <br /> Parent Permit No. Description RELOCATION OF THE GAS METER <br /> Notes <br /> Scheduled Completed Tune Inspector Result Remarks Inspector's Comments <br /> 6/28/2019 6/28/2019 GAS 01-ROUGH IN DXW CORRECTION 253-370-7212 Logan <br /> (6/28/2019 1:46 PM DXW) <br /> Please label gas meters with unit#or <br /> address. <br /> test pressure on all gauges should be the <br /> same.some gauges were low. <br /> 7/5/2019 7/5/2019 GAS 01-ROUGH IN DXW PARTIAL APPR 253-320-9722 <br /> (7/5/2019 1:55 PM DXW) <br /> gas pipe R.I.ok for units <br /> #1-17 p.s.i. <br /> #2-17 p.s.i. <br /> #3-16 p.s.i. <br /> #4-17 p.s.i. <br /> #5-16 p.s.i. <br /> correction on unit#6 check for leaks and <br /> retest. <br /> 1/22/2020 1/22/2020 PERMIT TKJ APPROVAL <br /> EXTENSION <br /> 1/23/2020 1/23/2020 MECH 06-FINAL SDP APPRVD-PERI'v (1/22/2020 9:18 AM TAH) <br /> looking for final inspection-the gas meter <br /> is outside,the work was done by <br /> Infrasource on behalf of pse-permit was <br /> not obtained by the property owner. <br /> 1/23/2020 1/23/2020 ADMIN USE HPC APPROVAL <br /> ONLY** <br /> INSP12 CRIVIlfs YS TEM S <br />