Laserfiche WebLink
. , <br /> 05 --7-1--Alaxfp, 74ve, <br /> � vJlog - ore <br /> Crimson City Electric <br /> Tuesday,October 15, 2019 <br /> Greetings, <br /> We have assured the following are true regarding the issues of correction at the <br /> following address: <br /> 3105 Tulalip Avenue <br /> Everett, WA 98201 <br /> The following are the services that were provided: <br /> 1. Dedicated 20 amp Laundry Circuit per code has been installed and verified <br /> to be Dedicated. GFCI protected by the receptacle and with a AFCI/GFCI <br /> combo 20amp Circuit breaker at the panel. <br /> 2. Two small appliance, GFCI protected Circuit/Receptacles in the kitchen <br /> have been installed at proper height from countertop and distance between <br /> each other. 2 additional AFCI/GFCI receptacles were installed per <br /> inspector's corrections. <br /> 3. In the utility room all NM Cable Sheathing has been pulled all the way into <br /> the boxes; switch and receptacle installed. Dedicated laundry circuit <br /> receptacles protected by GFCI/AFCI Combo 20amp breaker. <br /> 4. All carbon/smoke detectors are wired to communicate with each other upon <br /> testing <br /> 5. Tested insulation for new circuits pulled in the basement; No further issues <br /> found <br /> 6. Upstairs attic/storage space inspected for any electricalairing and or <br /> devices present, non found. All has been corrected. <br /> //c)C <br />