Laserfiche WebLink
Section CONTROLS Page 513 <br /> Sp.-CIficot is NOVUS3000 Dated JUNE 2008 <br /> NOVUS 3000 CONTROL PANEL <br /> 1.01 GENERAL <br /> A. Contractor shall furnish all labor,materials,equipment,and incidentals required to provide duplex pump control panel as <br /> specified herein. <br /> B. The pump control panel shall be assembled and tested by a shop meeting UL standard 508A for industrial controls.Each <br /> control panel shall receive a factory test to ensure proper operation prior to shipment. <br /> 2.01 CONSTRUCTION <br /> A. The controls for the pump shall be contained in a(painted steel,fiberglass,stainless steel,aluminum) enclosure meeting <br /> NEMA(1,12,3R,4,4X)requirements with hinged door. <br /> B. The enclosure shall have provisions for padlocking. A nameplate shall be permanently affixed to the panel and include the <br /> voltage,phase,hertz,pump full load ampere rating,and pump horsepower rating.A warning label stating the power should <br /> be disconnected before servicing shall appear on the panel. <br /> C. An aluminum back panel shall be provided. Should the panel size be larger than 36"x 30",a 12 gauge steel back panel <br /> finished with nonconductive white polyester powder paint shall be provided. <br /> D. For each pump a run light and a hand-off-auto switch shall be provided.These switches shall be mounted on the inner <br /> door,shall be properly labeled as to function,and shall match the run lights in appearance. The run lights shall be green. <br /> E. The incoming power shall be(115,208,230,460,575)volts,(single,three)phase(50/60)hertz service.Terminal blocks <br /> with box type lugs shall be supplied to terminate all wiring for floats, heat sensors, and seal sensors for the pump, if <br /> required. The pump leads shall be terminated at box type terminal blocks. <br /> F. A circuit breaker shall be used to protect from line faults and to disconnect the pump from the incoming power.Circuit <br /> breakers shall be thermal magnetic and sized to meet NEC requirements for motor controls. <br /> G. The magnetic starter shall include a contactor with a minimum mechanical life of 3,000,000 operations and a minimum <br /> contact life of 1,000,000 operations. The magnetic starter shall include an overload relay that is IEC rated, ambient <br /> temperature compensated,and bimetallic.The overload relay shall be capable of being set in either a manual or automatic <br /> reset mode. In the manual mode,only the operator shall accomplish reset.Overload relays shall be Class 10 type,meaning <br /> at 6 times the full load amperes the overload relay shall trip within 10 seconds. <br /> H. Control voltage shall be 120VAC and may be accomplished by the means of a transformer should the input voltage be <br /> unable to produce a 120VAC signal. Control fuse(s) and an on-off switch/circuit breaker shall protect and isolate the <br /> control voltage from the line. <br /> I. Wire ties and/or wire track shall be used to maintain panel wiring in neat bundles for maintenance and to prevent <br /> interference with operating devices. All wiring shall be color-coded to facilitate maintenance and repair of the control <br /> panel. Where a color is repeated,number coding shall be added. A schematic shall be permanently attached to the inside <br /> surface of the front door. <br /> J. All ground connections shall be made with fork terminals and star washers to assure proper ground. <br /> K. A duplex pump controller shall be provided for control logic. It shall be a dedicated solid-state controller,which is easily <br /> replaceable with unpluggable terminal blocks on all wiring inputs and outputs. Controller shall be flush mounted on the <br /> dead front inner door,shall be UL listed,and shall operate on 120VAC±10%,50-70 Hz,with an operating temperature of <br /> —10°C to 60°C. <br /> 44 HYDROMATIC® <br /> wa <br />