ENWSTRUCTURAL <br /> ENGINEERS <br /> Engineers Northwest Inc.,RS. <br /> 14.The structural calculations include the isometric view of the FEM used to perform the design. The <br /> FEM does not include the dead live loads on the platform from the stairways. The FEM shall be <br /> revised and the structural design re-evaluated. The structural drawings shall be revised as needed. <br /> See IBC Sections 1604.4 and 1613.1, and ASCE 7-10 Section 12.7.3. <br /> Response: The live and dead load of the stair has been added at the supporting <br /> columns. Please see attached 3D view of the design model along with comment <br /> response #12-a. <br /> 15.The structural calculations state that the lateral force resisting system is a steel ordinary <br /> concentrically-braced frame. However, the drawings specify moment frame connections between <br /> the beams and columns at Grids B/4, C/1, and C/4 on Plans 1/S1.1 and 2/S1.1. The connections <br /> are not provided to exclusively facilitate cantilever support of the stairway framing, and lateral <br /> bracing is not provided at locations specifying moment connections. The FEM in the structural <br /> calculations indicates two-way bracing at each level for the full height of the structure on Grids B/2- <br /> 4, 2/B-C, and 4/B-C. The FEM does not include moment frame connections. Furthermore, the use <br /> of moment frames is not permitted in Seismic Design Category D per ASCE 7-10 Table 12.2-1 Item <br /> C.4, and it does not qualify for use per Section 12.2.5.6.1. The structural drawings shall be revised <br /> for consistency with the structural calculations. See IBC Sections 1603.1, 1604.4, and 1613.1. <br /> Response: All the lateral force resisting system is a steel ordinary concentrically-braced <br /> frames. Please see revised plan and details. <br /> 16.The columns included in the lateral frames shall satisfy the requirements of AISC 341-10 Section <br /> D1.4a in addition to other load requirements. Calculations substantiating the design of the columns <br /> shall be submitted for review. See IBC Section 2205.2.1.2. <br /> Response: All the columns are designed including the amplified seismic factor, please <br /> see attached response. <br /> 17. Structural calculations substantiating the design of the diaphragm bracing and connections are not <br /> included in the calculations package and shall be submitted for review. The angles are connected <br /> to the connection plates though one leg. The design shall consider eccentric loading in the braces <br /> and the connections. The brace-to-connection plate design shall include shear lag. The connection <br /> plate-to-structural framing forces shall be determined using a generally-accepted method (e.g., <br /> Uniform Force Method, etc.). See IBC Sections 1604.1 and 2205.1, and AISC 360-10 Sections D3, <br /> E5, F10, and H1, and Chapter J. <br /> Response: Please see attached diaphragm bracing connection as well as the angle with <br /> shear lag factors. <br /> 18. Structural calculations substantiating the design of the tension braces and their connections are not <br /> included in the calculations package and shall be submitted for review. The design load for the <br /> brace connections shall satisfy AISC 341-10 Section 6a. The connection plate-to-structural framing <br /> forces shall be determined using a generally-accepted method (e.g., Uniform Force Method, etc.). <br /> The base plates connect to the faces of the HSS columns and shall verify the strength of the <br /> column wall per AISC 360-10 Section K1 and Table K1.2. See IBC Sections 2205.1 and 2205.2.1.2, <br /> and AISC 360-10 Chapters D and J. <br /> Response: Please see attached calculation of all bracing connection. <br /> 9725 Third Avenue NE•Seattle,WA 98115 <br /> 206.525.7560.fax 206.522.6698 <br /> www. •ineersnw.com <br />