Laserfiche WebLink
LMR <br /> Consulting Mechanical Engineers Tel: 1-510-733-2330 <br /> 1165 A Street, Hayward,CA 94541 Fax: 1-510-733-0332 <br /> September 18, 2019 Ref. No. 1891-4. <br /> age- <br /> City of Everett <br /> Attn: MR. Drew Martin <br /> Project: Panda Express <br /> 3200 Cedar Street,2nd Floor <br /> Everett, WA 98201 <br /> Mr.Martin, <br /> The following are the City of Everett plan check comments for the review,with the associated responses. <br /> 1. The construction drawings do not provide a clear and consistent separation between the hood and the wall <br /> framing. Section 18/M-500 specifies a 3-inch "internal standoff'while Detail 14/M-500 indicates that the <br /> hood is directly connected to the wall; Detail 14 does not appear to indicate an internal construction that <br /> would provide an effective separation. Note that the construction drawings for the building under Permit No. <br /> B1805-014 indicate the wall framing is combustible construction consisting of wood studs. The hood shall <br /> be provided with a minimum 18-inch clearance to combustible materials unless reduced clearance <br /> construction is provided per IMC Table 308.4.2;the reduced clearance shall not be less than 6 inches for an <br /> unprotected clearance of 18 inches. The reduced clearance construction shall extend at least 18 inches in <br /> all directions from the hood surfaces. The design shall be revised. See IMC Section 507.2.6. <br /> Response: Added 3"min.internal stand off to detail 14/M-500. The building was built with <br /> non-combustible metal stud walls. Therefore no clearance required between the <br /> hood and the wall. Please refer to the revised details 14/M-500 and 18/M-500. <br /> 2. Up-blast fans serving Type I hoods shall be installed with a restraint to allow inspection and cleaning. <br /> Section 5/M-500 specifies a"removable bolted restraint cable"that appears to be a latch to secure the fan in <br /> its closed position. The detail shall specify a restraint cable to limit the swing of the fan when opened. The <br /> drawing shall be revised. See IMC 506.5.3. <br /> Response: The detail 5/M-500 has been revised. <br /> 3. Details 13/M-500 and 14/M-500 indicate that the hood will be supported by a combination of connections to <br /> the adjacent wall and roof framing, respectively. See IBC Sections 107.2.1, 1603.1, 1604.1,1604.4, and <br /> 1613.1. The following comments shall be addressed: <br /> a. Detail 14/M-500 shows a direct connection to the wall framing providing lateral and partial vertical <br /> support. However,the wall contains combustible construction, and therefore the connection may <br /> not be permitted. Revised connections may be required. Seismic bracing complying with ASCE 7- <br /> 10 Section 13.6 shall be provided as needed. <br /> Response: The detail 14/M-500 has been revised. <br /> b. The hood is partially suspended from the framing above using threaded rods to the roof trusses. <br /> The trusses are spaced at 32-inches on-center per the construction drawing under Permit No. <br /> B1805-010 and consequently may not align with the rod locations. Additional cross-framing, such <br /> as unistrut bars, appears to be required to transfer the rod loads to the trusses. Cross-framing shall <br /> be connected to the framing above on each side of a rod location (i.e., cross-framing shall not <br />