Laserfiche WebLink
PANEL SCHEDULE:08/24/2010 (E) PANEL 'PORT2' PROJECT:JAMES MONROE PORTABLES <br /> CLASSIFICATION:NORMAL VOLTAGE:208/120V 10,3-WIRE SECTION:1 OF 1 <br /> FED FROM:PANEL'PORT' MAINS:200A MAIN CIRCUIT BREAKER <br /> MOUNTING:FLUSH NEUTRAL:100%RATED <br /> CKT BREAKER LOAD LOAD BREAKER CKT <br /> NOTE ITEM DESCRIPTION NO. AMPS POLE (VA) 0 (VA) AMPS POLE NO. ITEM DESCRIPTION NOTE <br /> SPACE 1 - 1 A 1 2 SPACE <br /> SPACE 3 - 1 B - 1 4 SPACE <br /> SPACE 5 - 1 A 1 6 SPACE <br /> SPACE 7 - 1 B - 1 8 SPACE <br /> SPACE 9 - 1 A 1 10 SPACE <br /> SPACE 11 - 1 B 1 12 SPACE <br /> RECEPTACLES 13 20 1 720 A - 1 14 SPACE <br /> RECEPTACLES 15 20 1 720 B - 1 16 SPACE <br /> LIGHTING 17 20 1 _ 768 _A 5760 60 2 18 VENTILATOR <br /> LIGHTING 19 20 1 768 B 5760 - - 20 - <br /> LOAD CALCULATIONS <br /> LOAD DESCRIPTION CONN.(VA) DEMAND FACTOR CALC.(VA) <br /> MISCELLANEOUS CONTINUOUS: - 125% - LOAD SUMMARY <br /> EQUIPMENT&MISCELLANEOUS: - 100% - <br /> LIGHTING: 1536 125% 1920 TOTAL <br /> LARGEST MOTOR: - 125% - CONNECTED LOAD AMPS <br /> MOTORS: - 100% <br /> RECEPTACLE: 1440 100% 1440 PHASE A: 7,248 VA 60 A <br /> RECEPTACLES OVER 10kVA: - 50% - <br /> ELECTRIC HEATING: 11520 100% 11520 PHASE B: 7,248 VA 60 A <br /> TOTAL CALCULATED LOAD: 14,880 VA <br /> TOTAL CALCULATED AMPS: 72 A <br /> TOTALS: 14,496 14,880 <br /> NOTES: HARGIS ENGINEERS,INC. <br /> 1. 1201 THIRD AVENUE,SUITE 600 <br /> 2. SEATTLE,WA 98101 <br /> 3. <br /> 4. PH.(206)448-3376 <br /> 5. FAX.(206)448-4450 <br />