|
•
<br /> BRIGGS ENGINEERING Copyright- BEI 2018 PO BOX 140537, Garden City, ID 83714
<br /> MODULAR BUILDING PAD&PIER FOUNDATION DESIGN -FOUNDATION CALCULATIONS IBC-2015
<br /> CLIENT Pacific Mobile Dealers: Pacific Mobile Structures Criteria 25psf-RLL,40psf FLL,110mph, Exp
<br /> Structures C, Cat-D, Ss=1.5, Fp=1500 psf
<br /> Date: 1-Apr-18 PO# E18074 Location: KCDA Standards
<br /> 28x32 MODULAR FDN-Classroom West of
<br /> Project#: 201801 #01.3.01-1 State(s): ID-OR-WA
<br /> w/(2)Floor Joist Spans/Module
<br /> Cascades
<br /> I. DESIGN CRITERIA: 28x32 MODULAR FDN-Classroom w/(2) Floor Joist Spans/Module
<br /> Dead Load: Roof, RDL= 10 psf
<br /> 1st Floor Ceiling CDL= 1
<br /> E&M= 1
<br /> Floor, FDL= 10 psf
<br /> Wall,WDL= 9 psf
<br /> Roof Live Load: Snow Load, RLL= 25 psf
<br /> Load Duration Factor, Cd= 1.15 %
<br /> Floor Load: Uniform Floor Load, FLL= Classroom 40 psf IBC Table 1607.1
<br /> Concentrated Live Load, p= 1000 lbs. IBC Table 1607.1
<br /> Partion, PDL= 0 psf
<br /> Wind Load: Basic Wind Speed,V= 110 mph ASCE 7 Figure 26.5-1A
<br /> Building Risk Classification: Category II ASCE 7 Table 1.5-1
<br /> Wind Importance Factor, Iw= 1.00 ASCE 7 Table 1.5-1
<br /> Wind Directional Factor, Kd 0.85 ASCE 7 Table 26.6-1
<br /> "a"Edge Pressure Distance= 3.00 ft
<br /> 3 Roof Slope= 3 :12 = 14.04 Degrees
<br /> Edge Wind Pressure,Wep= 24.1 psf ASCE 7 Figure 28.6-1
<br /> Interior Wind Pressure,Wip= 16 psf ASCE 7 Figure 28.6-1
<br /> Average Wind Pressure,Wp= 17.74 psf ASCE 7 Figure 28.6-1
<br /> Exposure Category= C Exposure Factor,A= 1.21 ASCE 7 Figure 28.6-1
<br /> Wind Topographic Factor, Kz= 1.00 ASCE 7 Section 6.5
<br /> Design Wind Pressure, Pw=Wp*A*Iw*Kz= 18.2 psf IBC Section 1605.3.1
<br /> Average Uplift Wind Pressure, Wup = -19.6 psf
<br /> Seismic: Upper Modue Weight= 0.00 psf
<br /> Base Module Weight= 27.79 psf
<br /> Total Weight,Wtot= 27.79 psf
<br /> Snow Load % Used in Seismic Design = 0%
<br /> Soil Site Class D
<br /> Seismic Category= D Nest of Cascade:IBC Table 1613.3(1)
<br /> Mapped Spectral Accelerations,short periods, Ss= 1.5000 IBC Figure 1615
<br /> Site Coefficient, Fa = 1.00 IBC Table 1615.1.2(1)
<br /> Max. Spectral Response, SMS= Fa*Ss= 1.50 IBC Equation 16-16
<br /> Design Spectral Response, SDS=2/3*SMs= 1.00 IBC Equation 16-18
<br /> Response Modification Coefficient, R= 4.00 IBC Table 1617.6
<br /> Lateral Load Factor, F=(1, Single Story; 1.1,2-story; 1.2,3-story) 1 ASCE 7-05, 12.14.8.1
<br /> Total Shear,pst=F*SDS*Wtot/R= 6.95 psf ASCE 7-05 Equation 12.14.11
<br /> Dimensions: Nominal Module Length, ML= 32 ft.
<br /> Nominal Module Width, MW= 14.00 ft.
<br /> Width,W = #Units= 2 28.00 ft.
<br /> Length, L= #Units= 1 32.00 ft.
<br /> 1st Floor Wall Ht. = 9.00 ft.
<br /> 2nd Flr.Wall Height,Wht= 0.00 ft.
<br /> Roof Height, Rht= 3 :12 Slope 3.50 ft.
<br /> Floor Height above NG, Fht= 30 inches 2.50 ft
<br /> Building Ht Coeff, Htc=Rht+Wht+Fht-10 1.00
<br /> No.of floor spans per module, nfs= 2
<br /> Clear Distance between supports, L2a= 84.00 inches
<br /> 3 �
<br /> 201801.01.3-1,FDN-Calcs 01-28x32-KCDA-W 2/4
<br />
|