9/27/2019 Page 1 <br /> City of Everett <br /> 11:31:47AM <br /> INSPECTION ACTIVITY REPORT <br /> Permit No. EW 1809-004 Site Address 1217 LOMBARD AVE#B <br /> Applied 9/21/2018 Applicant MARTINEZ JOSE Lot <br /> Approved 9/21/2018 Owner MARTINEZ JOSE OLVIDIO TURCIOS Block <br /> Issued 9/21/2018 Contractor OWNER Tract <br /> Parent Permit No. C1802-009 Description CHANGE SERVICE PANEL TO 200AMP AND WIRE <br /> Notes <br /> Scheduled Completed Type Inspector Result Remarks Inspector's Comments <br /> 9/24/2018 9/24/2018 ELEC 03-ROUGH SKB CORRECTION Provide a 2nd strap on mast. <br /> IN Make up all grounds prior to inspection. <br /> Provide a wall switch and light in storage <br /> room. <br /> Provide a receptacle in the dining area. <br /> 9/25/2018 9/25/2018 ELEC 05-SERVICE SKB APPROVAL <br /> 9/25/2018 9/25/2018 ELEC 03-ROUGH SKB APPROVAL <br /> IN <br /> 10/10/2018 10/10/2018 ELEC 08-OTHER SKB CORRECTION No access 1:54pm <br /> 12/28/2018 12/28/2018 ELEC 09-FINAL SKB CORRECTION (12/28/2018 10:01 AM SKB) <br /> Provide wet rated and receptacles outside. <br /> provide tamper resistant type receptacles for <br /> all receptacles.Provide GFCI protection for <br /> all outside,garage and kitchen countertop <br /> receptacles. <br /> 1/24/2019 1/25/2019 ELEC 09-FINAL MCB CORRECTION (1/25/2019 9:30 AM MCB) <br /> Gfci kitchen and garage <br /> 1/31/2019 1/31/2019 ELEC 09-FINAL SKB APPROVAL AM please <br /> 1/31/2019 1/31/2019 ADMIN USE AKH APPROVAL <br /> ONLY** <br /> INSP12 <br />