5010 VIEW DR 2020-07-15
>
Address Records
>
VIEW DR
>
5010
>
5010 VIEW DR 2020-07-15
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
7/15/2020 1:35:31 PM
Creation date
7/15/2020 1:34:54 PM
Metadata
Fields
Template:
Address Document
Street Name
VIEW DR
Street Number
5010
Imported From Microfiche
No
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
42
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
10/16/2019 Page <br /> City of Everett <br /> 12:04:53PM <br /> INSPECTION ACTIVITY REPORT <br /> Permit No. El 806-161 Site Address 5010 VIEW DR <br /> Applied 6/25/2018 Applicant Lot <br /> Approved 7/25/2018 Owner EVERETT SCHOOL DIST 2 Block <br /> Issued 7/26/2018 Contractor STEELE ELECTRIC INC Tract <br /> Parent Permit No. Description ELECT FOR NEW PORTABLE CLASSROOM-LOWELL ELEM <br /> Notes PUT IN POWER MAST FOR EXTG PANEL,PUD TO CONNECT.PER SB THIS ISA STAND ALONE <br /> 120/240V 200AMP OR LESS SERVICE SO IT DOES NOT REQUIRE PLAN REVIEW. <br /> Scheduled Completed Tyne Inspector Result Remarks Inspector's Comments <br /> 7/27/2018 7/27/2018 ELEC 05-SERVICE SKB CORRECTION Label AIC at service <br /> Bond meyers hubs at service <br /> Provide physical protection of service,i.e <br /> bollards <br /> 8/7/2018 8/7/2018 MARK FINAL** SKB APPROVAL <br /> 8/7/2018 8/7/2018 ELEC 09-FINAL SKB APPROVAL <br /> 8/7/2018 8/7/2018 ELEC 05-SERVICE SKB APPROVAL <br /> INSP12 CRWSYSTEMS <br />
The URL can be used to link to this page
Your browser does not support the video tag.