Laserfiche WebLink
R-102 Restaurant Fire Suppression Manual SECTION 4–SYSTEM DESIGN ' <br /> UL EX3470 ULC EX3470 <br /> 2014-SEP-01 REV. 11 PAGE 4-71 <br /> • DETECTION SYSTEM REQUIREMENTS - • - <br /> Once the fire suppression system design has been determined, <br /> a detection system design must be completed. This section ► <br /> contains guidelines and limitations for detection system instal- I Ir <br /> lation. 1 "a—.--4r--m,. ,——' <br /> Detector Identification <br /> The two types of detectors are distinguished from each other by <br /> 1111 their location in the detection system. 20 Fr�s.o m) <br /> MAXIMUM <br /> ► 1.The Terminal Detector is the last in a series of detectors, <br /> or the only detector used in a single-detector system.This <br /> detector is thus named because it is at the point at which the <br /> wire rope ends, or"terminates." ► <br /> 2.A Series Detector is any detector located in-line between the I #. .- . <br /> regulated release mechanism and the terminal detector. . <br /> Detector/Pulley Elbow/Conduit Offset Design Limitations <br /> • FIGURE 4-139 <br /> 1.Conduit runs, pulley elbows, and number of detectors per 000271 <br /> system must be within the approved system guidelines.The <br /> following requirements must not be exceeded: NOTICE <br /> Maximum Maximum Maximum When gas appliances are used and the flue <br /> Number of Number of Length of gases from the burner are exhausted into the <br /> Detectors Elbows 1/2 in. Conduit duct, the detector must be kept out of the air <br /> • per System per System per System stream of these exhaust gases.These gases <br /> fir, Scissors Style 15 20 150 ft(45.7 m) can be very hot and could actuate the system <br /> Detector unnecessarily. <br /> (Without Duct openings that are long and narrow or <br /> Offset Conduit large enough to require multiple duct nozzles <br /> Scissors Style 15 16 150 ft(45.7 m) may require additional detectors. <br /> Detector(With <br /> Offset Conduit ELECTROSTATIC PRECIPITATOR <br /> 2.If the hazard requires more than 15 detectors, up to five If an electrostatic precipitator is located at or near the base of <br /> 101 Remote Releases (Part No. 433485) can be used for the exhaust duct, it is necessary to locate a detector below the <br /> system actuation. Each 101 remote release allows the use precipitator, at the base of the duct, and also locate one in the <br /> of a maximum of 15"scissor"style detectors(14 series and duct,just above the precipitator.See Figure 4-140. <br /> 1 terminal)for a total of 75 detectors if needed. <br /> When installing the detector bracket and system conduit, make <br /> Detector Placement Requirements certain they do not interfere with the operation of the precipitator. <br /> EXHAUST DUCTS Note: On secondary filtration units utilizing multiple filter stages/ <br /> Each exhaust duct must have at least one detector installed ,media, contact Technical Services for instructions. <br /> in the duct entrance, located in the airstream of the cooking <br /> vapors,or at a maximum of 20 ft(6.0 m) into the duct opening. <br /> See Figure 4-139 <br /> MI <br /> c.,,,.) . —r-------------------Hemiiii.... /'''----- <br /> /O.: <br /> FIGURE 4-140 <br /> 000268 <br />