Laserfiche WebLink
Mr. Audie Wallace <br /> McKinstry Co., LLC <br /> Plan Check Number: X1907-001, Second Building Review <br /> August 29, 2019 <br /> Architectural <br /> 1. This comment has not been completely addressed. The original comment stated that Sheet <br /> M4.24 shows a ceiling diffuser penetrating the corridor ceiling at Grid 19/2.5, and that a smoke <br /> damper shall be provided. Sheet M4.24 was revised to provide a damper at Grid K/3.8. <br /> However, the damper only prevents smoke from infiltrating the rooms served by this branch of <br /> the duct and is not sufficient to prevent smoke from traveling through the remainder of the <br /> system. The design shall be revised to relocate the damper or provide additional dampers to <br /> prevent smoke from entering the system. The required rating for the dampers shall be <br /> specified per IBC Section 717.3.2.2. See IBC Sections 710.8 and 717.3.2.2. <br /> 2. This comment has not been completely addressed. The original comment stated that Sheet <br /> M4.24 shows a ceiling diffuser penetrating the corridor ceiling at Grid J.8/3.2, and that a smoke <br /> damper shall be provided. Sheet M4.24 was revised to provide a damper at Grid K/3.8. <br /> However, the damper only prevents smoke from infiltrating the rooms served by this branch of <br /> the duct and is not sufficient to prevent smoke from traveling through the remainder of the <br /> system. The design shall be revised to relocate the damper or provide additional dampers to <br /> prevent smoke from entering the system. The required rating for the dampers shall be <br /> specified per IBC Section 717.3.2.2. See IBC Sections 710.8 and 717.3.2.2. <br /> 3. This comment has not been completely addressed. The original comment stated that the 8" <br /> duct at Grid J.3/3.5 on Sheet M4.24 penetrates a 1-hour fire barrier shall include a fire damper. <br /> A fire damper has been specified in response. The required rating for the damper shall be <br /> specified per IBC Table 717.3.2.1. See IBC Section 717.5.2. <br /> 4. No additional comment. <br /> Additional Comments: <br /> 5. The drawing set appears to be revised per the Drawing Index on Sheet M0.01. In addition, the <br /> drawings listed in the Index do not match the sheets included in the set. The Index shall be <br /> revised. Note that Sheet M0.01 was only included in one of the two replacement sets <br /> resubmitted. Two complete sets shall be provided. See IBC Section 107.2.1. <br /> 6. The project includes numerous piping that penetrate the walls and wall membranes, and the <br /> horizontal assemblies. The architectural drawings under Permit No. B1904-036 do not include <br /> details for sealing the penetrations in the fire and smoke barriers. Details shall be included in <br /> the mechanical drawing set to seal the penetrations. The details shall include rated assemblies <br /> and shall provide the test listing. See IBC Section 714. <br /> O3200 Cedar Street © 425.257.8810 © everetteps@everettwa.gov <br /> Everett,WA 98201 425.257.8857 fax everettwa.gov/permits <br /> Page 2 of 3 <br />