<br /> ME�HANICAL EQI�IF'ME�lT F�EDER ��HEDUL� � � � ��
<br /> EQUIPMENT VOLT. PHASE AMP HP KNJ DISC. SW. FUSE FEEDER REMARKS � �� � �
<br /> - --- - -- - � �
<br /> �4C-1 208 1 1 N/A N/A 'ST' THERMAL OVERLOAQ SWITCH 2O8V, 2�' THERMAL �(2} #12 & (1) #12 GND IN 3/4"C. A, E °� � o "'
<br /> � �- .= �
<br /> CU-1 208 1 11 N/A N/A 30A, 2P 240V, NEMA 3R NON-FUSED (2) #10 & (1) #10 GND IN 3/4"C. A, E � � � �
<br /> EF-1 208 1 3.7 3/4 N/A 30A, 2P, 240V, NEMA 3R NUN-FUSED (2) #10 & (1) #10 GND IN 3i4"C. B, D, E Q w w �
<br /> E�'-2 208 1 3.7 3/4 N/A 30A, 2P, 240V, NEMA 3R NON-FUSED (2) #10 & (1) #10 GND fN 3/4"C. �, D, E �
<br /> EF-3 120 1 5.8 1/4 N/A 'ST' THERMAL OVERL4AD SWITCH 120V, 1 P, NEMA 3R THEFZMAL (2) #12 & (1) �12 GND IN 314"C. B, D, E � �
<br /> EF-4 120 1 4.4 1/6 N/A 'S�' THERMAL OVEF�LOAD SWITCH 120V, 1 P, NEMA 3R THERMAL (2) #12 & (1} #12 GND IN �/4"C. B, D, E �
<br /> . _ .
<br /> E�-5 120 1 3.4 1/10 N/A 'ST' TH�RMAL OVERLOAD SWI�CH 120V, 1 P, NEMA 3R TH�I�MAL {2) #12 & (1) #12 GND (N 3/4"C. B, D, E U
<br /> �F-6 120 1 5.8 1/4 N/A 'ST' THERMAL OVERLOAD SVi/ITCH 120V, 1 P, NEMA 3R THERMAL (2) #12 & (1) #12 GND IN 3/4"C. B, D, E
<br /> F-1 480 3 3.4 2 NlA 30A, 3P, 600V, NEMA 1 4.5A DUAL ELEMENT TIME DELAY (3) #10 & (1) #10 GND I�1 3/4"C. B E ������,���������,�,��������������
<br /> F-2 480 3 3.4 2 N/A 30A, 3P, 600V, NEMA 1 4.5A DUAL ELEMENT TIME DELAY 3 #10 & 11 #10 GND IN 3/$"C. g E 355 Research Parkway
<br /> � � � J Meriden,CT 06450
<br /> FtTU-'I 480 3 57 7.5 N/A 1QOA, 3P, 600V, NEMA 3R NON-FUSED (3) #4 & (1) #8 GND IN 1-1/2"C. A, E �203] 63o-�ao�
<br /> -- _ -- ----_--_------ — (203) 630-`L615 Fax
<br /> RTU-2 4$0 3 57 7.5 N/A 100A, 3P, 600V, NEMA 3R NON-FUSED (3) #4 & (1) #8 GND IN 1-1/2"C. A, E
<br /> -- - - _��».�.._ ,�; .,� �._ .:�,�.. ._.,,��.M.�
<br /> F�TU-3 480 3 57 7.5 N/A 100A, 3P, 600V, NEMA 3R NON-FUSED (3) #4 & (1) #� GND IN 1-1/2"C. A, E
<br /> RTU-A� 480 3 57 7.5 N/A 1p0A, 3P, 600V, NEMA 3R N�N-FUSED (3) #4 & (1) #8 GND IN 1-1/2"C. A, E �SztN � •
<br /> P F�TU-5 480 3 57 7.5 N/A 100A, 3P, 6QOV, NEMA 3R NON-FUSED (3) #4 & (1) #8 GND IN 1-1/2"C. A, E ��o�wns�,l`��f.
<br /> RTU-6 480 3 57 7.5 N/A 100A, 3P, 60QV, NEMA 3R NON-FUSED (3) #4 & (1) #8 GND IN 1-1/2"C. A, E ��� "' co
<br /> — - -- - --- - -- �. x
<br /> RTU-7 480 3 57 7.5 N/A 100A, 3P, 600V, NEMA 3R NON-FUSED (3) #4 & (1) #8 GND IN 1-1/2"C. A, E f
<br /> � -
<br /> FZTU-8 480 3 19.9 1.14 N/A 30A, 3P, 600V, NEMA 3R NON-FUSED (3) #10 & (1) #10 GND IN 3/4"C. A, E �o � s��i ,.-, ,�.
<br /> �__
<br /> - -- -- '{'�:>�c�s-�c�v �c+
<br /> �ZTU-9 480 3 44 5.0 N/A 60A, 3P, 60QV, NEMA 3R NON-FUSED (3) #6 & (1) #10 GND IN 1"C. A, E �S;oN L glyG1�`
<br /> — — — — �/T/ � .
<br /> RTU-10 480 3 9 0.61 N/A 30A, 3P, 600V, NEMA 3R RION-FUS�D (3) #12 c� (1 } #102 GND IN 3/4"C. A, E �,
<br /> WH� 208 3 22 N/A 8 30A, 3P, 240V, NEMA 1 NON-FUSED (3) #10 & (1) #10 GND IN 3i4"C. C, � �
<br /> WH1 208 3 22 N/A 8 30A, 3P, 240V, NEMA 1 NC)N-FUSED (3) #�0 & (1) #10 GND IN �/�l"C. C, E
<br /> V1/H1 208 3 22 NIA 8 30A, 3F', 240V, NEMA 1 NON-FUSED (3) #10 & (1) #10 GND IN 3/4"C. C, E •
<br /> Whl2 480 3 87 NfA 96 2QOA, 3P, 600V, NEMA 1 NON-FUSED (3) #1/0 & (1) #6 GND IN 2"C. C, E y���=nu� �,�,HI szib� ������
<br /> � .
<br /> NOTES:
<br /> 1. ALL EQUIPMENT FEEDERS SHALL BE FURNISHED AND WSTALLED FROM CIRCUIT BREAKER TO FINAL TERMINATION ON EQUIPMENT FOR A COMPLETE INSTALLATION AS INDICATED BY DIVISION 26.
<br /> 2. ALL CIRCUIT BREAKERS SERVING MECHANICAL EQUIPMENT SHALL BE HACR RATED OF SIZE AS WDICATED BY DNISION 26.
<br /> 3. A�L EQUIPMENT FEEDER TERMINATIONS TO DISCONNECT SWITCHES AND MOTORS SHALL BE RUN IN MAXIMUM 4'LIQUID-TIGNT FLEXIBLE STEEL CONDUITS.
<br /> 4. ALL STARTERS SHALL BE FURNISHED AND INSTALLED ADJACENT TO ELECTRICAL PANEL SERVING MECHANICAL EQUIPMENT BY DIVISION 26,UNLESS NOTED OTHERWISE. CONTROL WIRING FOR STARTERS SHALL BE BY DIVISION 23.
<br /> 5. ALL MECHANICA�EQUIPMENT SHALL HAVE A NEW PERMANENT LABEL,INDICATING ELECTRICAL PANEL&G/B NUMBERS FEEDING IT,SECURED TO UNIT MOUNTED DISCONNECT SWfTCH BY DIVISION 26.
<br /> 6. VERIFY EXACT LOCATIONS OF MECHANICAL EQUIPMENT IN FIELD WITH MECHAINCAL CONTRACTOR.
<br /> 7. THE SHOWN EQUIPMENT CONDUCTORS ARE SIZED TAKEN IN CONSIDERATION THE VOLTAGE DROP.THE ELECTRICAI.CONTRACTOR SHALL VERIFY THE WIRE SIZE ACCORDING WITH FIELD CONDITIONS.
<br /> 8. REFER TO FLOOR PLAN FOR HOMERUN POWER INFORMATION.
<br /> 9. RTU'S FED FROM THE BUSWAY HAVE TWO DISCONNECTS OF THE SIZE SHOWN ON SCHEDULE.THE DISCONNECT/BUS PLUG ON TNE BUSWAY SHALL BE PROVIDED WITH A FUSE OF THE SIZE SHOWN.
<br /> 10. PWU=PURCHASED WITH UNIT.
<br /> 11. TPS=THERMALLY-PROTECTED SWITCH. � ,
<br /> 12. REFER TO FLOOR PLAN FOR NOMERUN POWER INFORMATION. �
<br /> 13. PROVIDE THE CORRECT OVERGURRENT PROTECTION PER TNE NAMEPLATE INFORMATION FOR EACN PIECE OF EQUIPMENT.
<br /> . 14. PROVIDE 20A,120V GFI DUPLEX REGEPTACLE AT EACH ROOFTOP PIECE OF EQUIPMENT.PROVIDE HOMERUN FROM NEAREST 208Y/120V PANEL � •
<br /> REMARKS: � ~ ,—
<br /> A. DISCONNECT SWITCH,STARTERS,REIAYS,CONTROL WIRING PROVIDEU BY MECH.CONTRACTOR.WIRING TO DISCONNECT SWITCN&EQUIPMENT TERMINALS PROVIDED BY ELECTRICAL CONTRACTOR. ~ � 0
<br /> B. STARTERS,RELAYS,CONTROL WIRING PROVIDED BY MECH.CONTRACTOR.DISCONNECT SWITCH&WIRING TO DISCONNECT SWITCH&EQUIPMENT TERMINALS PROVIDED BY ELECTRICAL CONTRACTOR. � f� N
<br /> C. STARTERS,RELAYS,CONTROL WIRING PROVIDED BY PLUMB.CONTRACTOR.DISCONNECT SWITCH&WIRING TO DISCONNECT SWITCH&EQUIPMENT TFRMINALS PROVIDED BY ELECTRICAL CONTRACTOR. [�
<br /> OC�
<br /> D. CONTROLLED BY EXHAUST FAN TIMER.GOORDINATE TIME SCHEDULE WITH OWNER'S REP. W � Q�
<br /> E. INDOOR UNITAQUIRES ITS POWER FROM THEASSOCIATED OUTDOOR CONDENSING UNIT. Q
<br /> F. CONTROLLED BY TIMECLOCK PROVIDED&WIRED BY MECH.CONTRACTOR.DISCONNECT SWITCH(LINE SIDE OF TIMEGLOCK)&WIRING TO DISCONNECT SWITCH,TIMECLOCK&EQUIP.TERMINALS PROVIDED BY ELECT.CONTRACTOR. � O Q
<br /> G. LOWERS SHALL BE INTERLOCKED WITH EXHAUST FANS BY MECH.CONTRACTORS.DISCONNECTS SWITCH&WIRWG TO DISCONNECT SWITCH&EQUIPMENT TERMINALS BY ELECTRICAL CONTRACTOR. (� � ��„
<br /> H. MULTIPLE LOUVERS ARE TO BE GANGED TOGETHER ON(1)H4MERUN.SEE PLAN DRAWINGS FOR FURTHER INFORMATION. �
<br /> W f'
<br /> � � � .
<br /> � � W
<br /> . � � .
<br /> W
<br /> � �I
<br /> � �
<br /> �
<br /> O
<br /> (TYPICAL RTU-1 THRU RTU-9) �
<br /> RTU-1 RTU-2 RTU-3 RTU-9 �
<br /> ROOF
<br /> o S S �� S S S J S ,
<br /> �INITIATION CIRCUIT
<br /> jRTS ;RTS ;RTS �RTS ',RTS �RTS RTS; RTS
<br /> RTU-1 RTU-2 RTU-3 RTU-4 RTU-5 RTU-6 RTU-7 RTU-8 RTU-9 RTU-10 F-1 F-2 .���� �'"�� ���'��� ���"����
<br /> CM CM CM CM CM CM GM CM CM CM CM cM --€� INITIATION CIRCUIT
<br /> � EXISTING SPRINKLER RISER FLOW AND TAMPER ,
<br /> � SWITCHES. COORDINATE QUANTITIES & L4CATIONS o
<br /> � WITH FIRE PROTECTfON DRAWINGS. �
<br /> . � � �
<br /> U
<br /> � cM cM cM cM �— �� �--,'� �—i� fNITIATION CIRCUIT z �
<br /> �
<br /> �i FS FS TS TS O
<br /> �
<br /> -� u,
<br /> � �
<br /> N -
<br /> U �£ � 3� �f
<br /> W F F F F F F F � � NOTIFICATION CIRCUIT
<br /> � W
<br /> d- o .
<br /> rn
<br /> �
<br /> 0
<br /> o .
<br /> v � �
<br /> % 1 ALA � IA A z
<br /> �
<br /> �
<br /> � a�������,.��,..,ri�,�..v�w..�����m_w���� .
<br /> � 1. REFER TO FLOOR PLANS FOR LOCATIONS AND C�UANTITIES OF ALL DEVICES. �esic�ned nnB
<br /> � Drawn: HF
<br /> �
<br /> v 2. PROVIDE A N1INIMUM OF 2 N�TIFICATION CIRCUITS CIRCUIT EVERY OTHER DEVICE TO SEPARATE GIRCUIT. Re�iewed: �K���
<br /> � 3/4°C. WITH PULL STRfNG ' Scale: 12"= t'-o"
<br /> 0
<br /> / TO �'EL/COM BACKBOARD. Pro�ect No. t9oo�t94
<br /> � FURNISH & INSTALL CABLE FACP ANN 3. LOCATE DUCT SMOKE DETECTOR REMOTE TEST SWITCHES IN CLEARLY ACGESSI�LE LOCATION (FLUSH ON WALL BELOW Date: 04l19/2019
<br /> � CEILING OR RECESSED IN CEILING IN �INISHED SPACES).
<br /> � AS REQUiRED.
<br /> � .
<br /> ,V 4. INT�RCONNECT WIRING �'ROM SMOKE DETECT'OR AND ASSOCIATED SMOKE DAMPER BY ELECTRICAL CONTRACTOR.
<br /> � � � .���� «�� ..u��w.�,�,��
<br /> � � 120VAC POWER, 3/4"C, 2 #12, 1 #12G. CONNECT 5. CONTRACTOR SHALL PROVIDE AL�L REQUIRED PROGRAMING AND SHALL TEST FIRE ALARM SYSTEM AFTER COMPLETION OF T't'e: �
<br /> �°� TO DEQICATED 20A 1 P CIRCUIT BREAKER AS THE ENTIRE PROJECT TO ENSURE IT C�MPLIES WITH ALL STATE AND LOCAL CODES AND 1TS IN PROPER WORKING CONDITION.
<br /> #6GND. IN 3l4"C. INDICATED ON POWER PLAN PROVIDE CIRCUI7 PARTIAL ONE-LINE
<br /> U _ �C�NNECTTO D4M. ' FIRE ALARM RISER
<br /> WATER SERV. BY SREAKER TAB LOCK. IDENTIFY CIRCUIT BREAKER DIAGRAM
<br /> Q MAIN ELECTRICAL ROOM MECH. MEANS. WITH RED MARKING AS 'FfRE ALARM CIRCUIT'. NEW TENANT SPAGE
<br /> Sheet No.
<br /> �
<br /> d'
<br /> � PA TLA� ON�-LI NE FI RE P�L�RM RI� � DIA�RAM � �
<br /> . � � NOT TO SCALE � �� �
<br /> o, �--
<br /> �
<br /> �-
<br /> �O 2017 BL COMPANIES,INC. THESE DRAWINGS SHALL NOT BE UTILIZED BY ANY PERSON, FIRM OR CORPORATION WITHOUT THE SPECIFIC WRITTEN PERMISSION OF Bl COMPANIES.