0'NNER
<br /> KITCHEN EQUIPMENT CONNECTION SCHEDULE - ,
<br /> TAG EQUIPMENT VOLTS/ AMPS HP FEEDER SIZE MTG. CONNECTION REMARKS NOTES
<br /> PHASE HEIGHT -_- - --__ -
<br /> E-109 WOODSTONE FIRE DECK OVEN 120/1 2 3/4"C., 2#12, 1#12G, DIRECT EARLY INSTALLATION REQUIRED 3
<br /> E-120 DOUGH PRESS 208/3 15 - 3/4"C., 3#12, 1#12G. +12" NEMA L15-20P _
<br /> E-140 REF COUNTER 27" 120/1 fi.3 - 3/4"C., Z#12, 1#12G. NEMA 5-15P 2635158th CT NE
<br /> E-142 REF COUNTER 60" 120/1 6.6 - 3/4"C., 2#12, 1#12G. NEMA 5-15P SUItB 2��
<br /> E-146 GRAB N GO COOLER 12Q/208/1 13 3/4 3/4"C., 3#12, 1#12G. NEMA 14-20P SELF-CONTAINED 2 Bellevue,WA 9$008
<br /> F E-161 SHAKE MACHINE-RIGHT 208/1 - 1 3/4"C., 2#12, 1#12G. NEMA L6-20P 2 ARC}ITECTOFRECORD �
<br /> E-182 UC REFRIGERATOR 120/1 2 - 3/4"C., 2#12, 1#12G. NEMA 5-15P 2 -�
<br /> E-183 UC REFRIGERATOR 12d/1 2 - 3/4"C., 2#12, 1#12G. NEMA 5-15P 2 �
<br /> E-210 KEGERATOR 120/1 1.4 - 3/4"C., 2#12, 1#12G. +18" NEMA 5-15P
<br /> E-221 COLD WELL 120/1 3 - 3/4"C., 2#12, 1#12G. NEMA 5-15P -
<br /> E-302 WALK IN COOLER CONDENSER 208/1 7.7 - 3/4"C., 2#12, 1#12G. NEMA 3R DC CPB1QODC-A+ 2
<br /> E-303 WALK IN FREEZER CONDENSER 208/1 5.8 - 3/4"C., 2#12, 1#12G. NEMA 3R DC CPF075DC-B+ 2
<br /> E-320 DISHWASHER 208J3 46.8 - 1"C., 3#6, 1#1QG. DIRECT - �
<br /> E�21 TEA BREWER 120/1 14.4 - 3/4"C., 2#12, 1#12G. +52" NEMA 5-15P
<br /> E-425 16" IMMERSION BLENDER 120/1 6.25 - 3/4"C., 2#12, 1#12G. +52" NEMA 5-15P
<br /> E-426 DOUGH PRESS BACKUP 208/1 14.1 - 3l4"C., 2#12, 1#12G. +52" NEMA 6-2QP FUTURE EQUIPMENT 2 � � A � H I T E
<br /> E-500 SODA MACHINE 120/1 10 - 3/4"C., 2#12, 1#12G. +18" NEMA 5-15P `
<br /> E-501 ICE MACHINE 208/1 11.8 - 3/4"C., 2#12, 1#12G. +18" NEMA 6-15R 2 Graphite Design Group, LLC
<br /> E-502 JUICE DISPENSER 120/1 5.5 - 3/4"C., 2#12, 1#12G. +18" NEMA 5-15P 1809 Seventh Ave,#7�� _
<br /> Seattle,WA 98101
<br /> M-1Q9 POS 120/1 3 - 3/4"C., 2#12, 1#12G, NEMA 5-15P DOUBLE-DUPLEX+DATA � 2�6.224.3335
<br /> M-303 GLYCOL PUMP 120/1 - 1/3 3/4"C., 2#12, 1#12G. +108" NEMA 5-15P
<br /> M-308 AMPJPREAMP 120/1 4 - 3/4"C., 2#12, 1#12G. +78" NEMA 5-15P coNsu�rauT
<br /> E , .
<br /> GENERALNOTES
<br /> A. REVIEW ALL FOOD SERVICE PLAN SHEETS FOR ADDITIONAL ELECTRICAL REQUIREMENTS NOT LISTEQ IN THIS SCHEDULE. PROVIDE CIRCUIT CONNECTIONS AS REQUIRED.
<br /> B. PROVIDE LIQUID TIGHT FLEXIBLE METAL CONDUIT AND WATER PROOF CONNECTIONS FOR ALL FLEXIBLE DIRECT CONNEGTIONS.
<br /> C. PROVIQE GFCI TYPE RECEPTACLES FOR ALL 125V 1 PH 15A AND 20A RECEPTACLES. �,hn�acicel
<br /> D. MAKE ALL FINAL CONNECTIONS TO ALL KITCHEN AND COOLER EQUIPMENT. PROVIDE ALL APPURTENANCES AS REQUIRED. _
<br /> �191�1�R�
<br /> SPECIFIC NOTES �'"�`����`������
<br /> 800-581-0963 www.�d�d�.aom
<br /> SEJOBR: '19U3�8 �
<br /> 1 PROVIDE DATA CONNECTION FOR POS TERMINAL. COORDINATE LOCATION WITH OWNER.
<br /> 2 COORDINATE RECEPTACLE TYPE WITH MANUFACTURER PRIOR TO ROUGH IN. PROVIDE AS REQUIRED. , :
<br /> 3 SUPPLY MANUFACTURER RELAY AND FAN SPEED CONTROL OPTION FOR SIMULTANEOUS OVEN AND FAN CONTROL.
<br /> FAULT CURRENT CALCULATIONS 5�` �
<br /> �yR�Ysc�'
<br /> , O oF W�sy, �y ,
<br /> FAULT CURRENT AT SECONDARY SIDE OF UTILITY TRANSFORMERS WITH INFINITE PRIMARY FAULT CURRENT �� P �,, n
<br /> POINT NAME PRIMARY ISC PHASE kVA RATING SECONDARY VOLTAGE (L—L) SECONDARY FLA IMPEDANCE (�Z) ISC AVAILABLE � � � `� �
<br /> UTILITY XFMR INFINITE 3 PHASE 208 VOLTS 28670 AMPS ,�
<br /> 31548
<br /> 'O �F�I STERF'� �
<br /> FAULT CURRENT AT END OF CONDUCTOR RUN ��FS NA �
<br /> PREVIOUS POINT CIRCUIT CHARACTERISTICS RESULTS
<br /> POINT NAME ISC AVAILABLE POINT NAME LENGTH VOLTAGE �L—L� PHASE SETS(S� CONDUCTOR SIZE CONDUCTOR TYPE GONDUIT TYPE f M ISC AVAILABLE �oA �aso9 oate: 07/»/�s
<br /> UTILITY XFMR 28670 AMPS SERVICE DIS. 25 FEET 208 VOLTS 3 2 #500 kcmil COPPER NONMETALLIC 0.1117 0.8995 26351 AMPS
<br /> SERVICE DIS. 26351 AMPS PNL L1 5 FEET 208 VOLTS 3 2 #3/0 COPPER METALLIC 0.0427 0.9590 25272 AMPS .
<br /> PNL L1 25272 AMPS PNL L2 1 FEET 208 VOLTS 3 2 #3/0 COPPER METALLIC 0.0082 0.9919 25067 AMPS
<br /> ,
<br /> FAULT CURRENT CALCULATIONS GENERAL NOTES
<br /> 1. THE TOTAL MOTOR CONTRIBUTION OF THE ENTIRE SYSTEM (562 AMPS) IS ADDED TO THE FIRST POINT IN THE SYSTEM AND IS, THEREFORE>CARRIED THROUGH ALL �
<br /> DOWNSTREAM POINTS MEANING THAT NONE OF THE SUBSEQUENT POINTS ARE CALCULATED WITHOUT MOTOR CONTRIBUTION.
<br /> � � �
<br /> c
<br /> REFER TO ARCHITECTURAL SHEET A-602 FOR LIGHTING SCHEDULE.
<br /> Q �
<br /> Z � N
<br /> z �
<br /> �
<br /> WWQ �
<br /> W � �
<br /> �C � �
<br /> WW
<br /> � �
<br /> C� � w
<br /> o �
<br /> � �' W
<br /> �
<br /> W �
<br /> B � ,
<br /> W
<br /> ISSUED 1 REUISED DATE
<br /> PERMIT SET 07.12.19 ,
<br /> A
<br /> PERMIT SET 01,12.19
<br /> SCHEDULES
<br /> E-601
<br /> M0�5uper-Fast Piva,LLC refains ownership of CA�documenis � CopyrigM d 2019 Graphite Design Group,LLC
<br /> .