<br /> SPECIFlCATIONS C. NEUTR,4L GROUNDING: THE NEUTRAL POINT �F ALL TRANSFORMERS SHALL BE SOLIDLY GROUNDED B. PRODUCTS: D. MOTOR CONTROLS AND EQUIPMENT CONNECTIONS: -��� = = '
<br /> =� r= -�� �M1.�
<br /> TO THE GROUNDING SYSTEM AND TRANSFORMER ENCLOSURE WITH CODE SIZE GROUND CONDUCTORS. _- == =_ ___ -=- '
<br /> 280500 -COMMON WORK RESULTS FOR ELECTRICAL THE NEUTRAL BUS IN EACH PANELBOARD SHALL BE ISOLATED FROM THE GROUND. THE NEUTRAL 1. RELAY PANELS: 1. GENERAL: PROVIDE ALL LINE VOLTAGE WIRING AND CONNECTIONS TO EQUIPMENT AND MOTORS AS - - _ _- = - --
<br /> SHALL BE GROUNDED ONLY AT A SINGLE POINT AT THE MAIN SWITCHBOARD OR AT SEPARATELY DERIVED SHOWN ON THE PLANS, DIAGRAMS OR SPECIFIED HEREIN. OBTAIN ALL NECESSARY ELECTRICAL AND = _ �
<br /> A. SCOPE OF WORK SYSTEM TRANSFORMERS. a. DESCRIPTION: LIGHTING CONTROL PANELS SHALL BE UL LISTED AND CON5IST OF THE FOLLOWING: PHYSICAL INFORMATION FROM THE TRAQE PROVIDING THE EQUIPMENT, PRIOR TO ROUGH = - -- •
<br /> ADJUST INSTALLATION ftEQUIREMENTS AS NECESSARY FOR A COMPLEfE AND OPERABLE SYSTEM. _ _ _= - `
<br /> 1. COMPLY WITH THE GENERAL CONDITIONS OF THIS CONTRACT. THE REQUIREMENTS OF THIS D. RECEPTACLE GROUNDING: CONNECT THE GROUND TERMINAL OF ALL RECEPTACLES BY UTIUZING A 1) ENCLOSURE/TUB: NEMA 1. 2. MOTOR CONTROLS, SEPARATELY MOUNTED; PROVIDE SEPARATELY MOUNTED MOTOR STAR �1 t�1�� �. �
<br /> SPECIFICATION ARE IN ADDITION TO THE REQUIREMENTS OF THE GENERAL CONDITIONS. SEPARATE GROUNDING CONDUCTOR BEfWEEN THE RECEPTACLE GROUNDING SCREW AND THE GROUND EQUIPMENT AS SHOWN OR NOTED. COORDINAT CATI N =--=-- - - = "
<br /> CONDUCTOR PROVIDED IN THE BRANCH CIRCUIT. INTEGRAL MOUNTING STRAPS WITHIN THE RECEPTACLE 2) COVER: FLUSH, HINGED, LOCKABLE AND SHALL RESTRiCT ACCESS TO LINE VOLTAGE SECTION. E LO 0 AND INTERLOCKWG WITH TE�P�ATURE
<br /> 2. UNLESS OTHERWISE NOTED, PROVIDE DEMOLITION OF EXISTING POWER RECEPTACLES, LIGHT CONNECTED TO THE DEVICE MOUNTING STRAPS ARE NOT APPROVED AS A GROUNDING METHOD. CONTROLS CONTRACTOR. VERIFY MOTOR HORSEPOWER SIZE OR FULL-LOAD AMPERAGE PRIOR TO - �
<br /> FIXTURES, RACEWAYS, WIRING, VOICE/DATA OUTLETS AND VOICE/DATA CABLING. DEMOLISH FIRE ALARM 3) INTERIOR: BARRIER FOR SEPARATION OF HIGH-VOLTAGE (CLASS 1) AND LOW-VOLTAGE (CLASS 2) ORDERING OVERLOAD HEATERS AND SIZE UNITS IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE. 2Q35�58�1 CT NE
<br /> DEVICES AND WIRING WHERE IN CONFLICT WITH NEW WORK. E. FLEXIBLE CONDUIT GROUNDING: PROVIDE A SEPARATE GROUNDING CONDUCTOR IN ALL FLEXIBLE WIRING. IT SHALL INCLUDE INTELLIGENCE BOARDS, POWER SUPPLY AND CONTROL RELAYS. CLOCK '
<br /> GONDUIT RUNS INCLUDING WATERTIGHT FLEXIBLE CONDUIT WITH INTEGRAL GRQUNDING STRAPS. INSTALL 265100 -INTERIOR UGFfTING ,
<br /> 3. PROVIDE ALL LABOR AND MATERIAL NECESSARY TO ACCOMPLISH THE WORK SPECIFIED HEREIN AND GftOUND CONDUCTOR INSIDE CONDUIT WITH UNGROUNDED CONDUCTORS. DISPLAY AND KEYPAD SHALL BE MOUNTED ON INTERIOR CABINET DOOR FOR EASY USER ACCESS AND Slll�B ZOO
<br /> , F AS SHOWN ON THE DRAWWGS.
<br /> PROGRAMMING. A. GENERAL: REFER TO THE FIXTURE SCHEDULE ON THE CONTRACT DRAWINGS. B@II2Vll8,WA98008
<br /> F. GROUND CONNECTIONS: GROUND CONNECTIONS TO BUILDING STEEL, GROUND RODS AND CABLE b. FEATURES; � � '
<br /> 4. COORDINATE WORK WITH ALL OTHER TRADES. TOPS SHALL UTILIZE AN EXOTHERMIC WELDING PROCESS. CADWELD, ERICO PRODUCTS, INC., OR B. LABELS: PR�VIDE UL LABELS ON ALL NEW FIXTURES. LIGHTING FIXTURES INSTALLED IN DAMP a�cHiTecraF�coao �
<br /> APPROVED EQUAL. OR WEf LOCATIONS SHALL HAVE LABEL'SUITABLE FOR DAMP LOCATIONS' OR'SUITABLE FOR WET �
<br /> 5. VISIT THE SITE AND VERIFY EXISTING CONDITIONS PRIOR TO SUBMITTING BID. 1} PANEL SHALL ACCEPT UP TO SIXTEEN SINGLE POLE RELAYS. RELAYS SHALL BE INDIVIDUAL LOCATIONS'. �
<br /> 260533 -RACEWAY ANO BOXE:S FOR ELECTRICAL SYSTEMS LATCHING RELAYS WITH 20 AMP LOAD CONTACTS FOR BALLAST (INCLUDING HID, MAGNEfIC OR
<br /> 6. REMOVE ALL WASTE AND RUBBISH FROM THE SITE ON A DAILY BASIS. ELECTRONIC TYPE BALLASTS), TUNGSTEN AND GENERAL PURPOSE LOADS. PROVIDE ISOLATED C. LAMPS: .
<br /> A. RACEWAYS AUXILIARY CONTACTS FOR PILOT LIGHT SWITCHING. REIAYS SHALI. USE QUICK CONNECTORS AND BE = '
<br /> B. WARRANTY: WORKMANSHIP AND MATERIALS SHALL BE GUARANTEED FOR A PERIOD OF ONE YEAR INDIVIDUALLY REPLACEABLE TO FACILITATE EASE OF USE. 1. APPROVED MANUFACTURERS: OSRAM/SYLVANIA, GE, OR PHILIPS. SEE FIXTURE SCHEDULE FOR -P �
<br /> FROM THE DATE OF FINAL ACCEPTANCE BY THE OWNER. PROVIDE ADDITIONAL WARRANTY FOR 1. ELECTRICAL METALLIC TUBING (EMT): STEEL-SCREW TYPE. FITTINGS TWO INCHES AND LARGER ADDITIONAL INFORMATION. ___-_--
<br /> VOICE/DATA SYSTEM AS NOTED ELSEWHERE. SHALL CONTAIN DUAL SET-SCREWS ON EACH SIDE OF THE COUPLING. 2) WHERE INDICATED, PANELS SHALL PROVIDE SPACE WITHIN THE HIGH VOLTAGE SECTION OF THE �=�_�___ j .
<br /> ENCLOSURE TO ACCOMMODATE UP TO 12 MULTI-POLE CONTACTORS. TWO SECTIONS OF DIN RAIL 2. PROVIDE FOR EACH FIXTURE, NUMBER, SIZE AND TYPE AS REQUIRED BY FIXTURE OR AS --T� �
<br /> C. REGULATIONS 2. FLEXIBLE METALLIC CONDUIT: GALVANIZED STEEL, SECURELY INTERLOCKED. MOUNTING SHALL BE PROVIDED AS STANDARD. NO FIELD DRILLING OR FABRICATION SHALL BE INDICATED ON THE DRAWINGS. �-_ _
<br /> REQUIRED FOR MOUNTING CONTACTORS OR OTHER ACCESSORIES WITHIN THE ENCLOSURE. _ ��� -
<br /> ����_�__ �
<br /> 1. ELECTRICAL WORK SHALL COMPLY WITH THE FOLLOWING CODES AS PRESENTLY APPLICABLE: 3. MC CABLE - CONGEALED IN WALLS ONLY. 3. FLUORESCENT: PROVIDE EACH FIXTURE WITH THE NUMBER, SIZE AND TfPE AS REQUIRED BY ���
<br /> 2. APPROVED MANUFACTURERS: FIXTURE OR INDICATED ON DRAWINGS. LAMP COLOR SHALL BE 3500K WITH A COLOR RENDERING INDEX
<br /> , a. NATIONAL ELECTRICAL CODE {NEC) B. FITfINGS (CRI) OF 80 OR BEiTER. EA�,M� SHALL HAVE LESS THAN 10 MG OF MERCURY. ALL LAMPS j� � A � H I T E .
<br /> a. RELAY PANEL: HUBBELL CX162S162NM OR APPROVED EQUAL. OF A SPECIFIC TYPE ARE TO BE OF THE SAME MANUFACTURER. TNERE SHALL BE NO PERCEPTIBLE � �
<br /> b. E N E R G Y C O D E 1. E L E C T R I C A L M E T A L L I C T U B I N G (E M T): S T E E L-S C R E W T Y P E. F I T I I N G S T W Q I N C H E S A N D L A R G E R C O L O R D I F F E R E N C E S B E f W E E N L A M P S. �`
<br /> b. PHOTOCELL: HUBBELL LUXSTAT-LS
<br /> SHALL CONTAIN DUAL SEf-SCREWS ON EACH SIDE OF THE COUPLING. Gf8(Jhlt2 D251�f1 GfOU(}, LLC �
<br /> c. LOCAL AND STATE CODES AND REGULATIONS c. OVERRIDE SWITCH: HUBBELL LVSM2PL-COLOR 4. LED: PROVIDE EACH FIXTURE WITH THE NUMBER, SIZE AND TYPE AS REQUIRED BY THE FIXTURE 1809 Seventh Ave
<br /> 2. FLEXIBLE MEfALLIC CONDUIT: STEEL, ONE- OR TWO-SCREW GLAMP TYPE. OR INDICATED ON THE DRAWINGS. ,#7OO
<br /> 2. PERMITS: OBTAIN AND PAY FOR ALL REQUIRED PERMITS. d. OCCUPANCY SENSOR SWITCH: SENSOR SWITCH WSD PDT-WH Seattie,WA 98101 � .
<br /> 3. CONDUIT STRAPS: HEAVY DUTY, TWO-HOLE PRESSEQ STEEL D. BALLASTS: ZO6,224.3335 �
<br /> D. SUBMITTAL AND SHOP DRAWINGS: PRIOR TO INSTALLATION, SUBMIT CATALOG DATA FOR ALL
<br /> EQUIPMENT AND MATERIALS FOR REVIEW. SUBMIT SHOP DRAWINGS SHOWING COMPLETE 4. OUTLEf AND DEVICE BOXES 26272$ -WIRlNG DEVICES 1. APPROVED MANUFACTURERS: ADVANCE, MAGNETEK OR LUTRON.
<br /> E TERMINAL-TO-TERMINAL WIRING FOR EACH SIGNAL AND COMMUNICATION SYSTEM. THREE COPIES cotrsu�rarrr '+ .
<br /> REQUIRED, a. WTERIOR SURFACE-MOUNTED IN UNFINISHED AREAS: ONE-PIECE PRESSED STEEL, A. WIRING DEVICES 2. ELECTRONIC FLOURESGENT BALLASTS: BALLASTS SHALL BE TYPE REQUIRED FOR THE NUMBER �
<br /> ELECTRO-GALVANIZED, SIZE AND DEPTH REQUIRED BY CODE, EXCEPT 4-INCH SQUARE OR 4-INCH AND TYPE OF LAMPS IN EACH CASE. EACH FIXTURE SHALL HAVE ITS OWN BALLAST. REMOTE, TANDEM
<br /> E. OPERATIONS AND MAINTENANCE MANUALS: PROVIDE MAINTENANCE AND OPERATIONS DATA FOR ALL OCTAGONAL MINIMUM. 1. APPROVED MANUFACTURERS: HUBBELL, P & S OR LEVITON. ALL PART NUMBERS REFER TO OR MASTER/SLAVE-WIRED BALLASTS SHALL NOT BE UTILIZED. AL� BALLASTS SHALL BE HPF - •
<br /> ELECTRICAL EQUIPMENT AND SIGNAL AND COMMUNICATIONS SYSTEMS. THREE COPIES ARE REQUIRED. HUBBELL AND UL APPROVED. ALL FLUORESCENT BALLASTS SHALL OPERATE AT 20 KHZ OR GREATER AND CLASS
<br /> b. INTERIOR FLUSH-MOUNTED: SAME AS ABOVE EXCEPT PROVED PLASTER RING EXTENSION TO P THERMALLY PROTECTED RESET TYPE TO MEET SECTION 410-73 (E) OF THE NATIONAL ELECTRICAL
<br /> F. RECORD DRAWINGS: CORRECTIONS AND CHANGES MADE DURING THE PROGRESS OF THE WORK FINISHED SURFACE. 2. COLOR OF SWITCH HAND�ES: BLACK IN COLOR, WHITE IN COLOR IF ON WHITE SURFACE (PAINT CODE AND BE CSA CERTIFIED. BALLAST FACTOR FOR ALL LAMP/BALLAST GOMBINATIONS SHAL��EXCEED
<br /> � SHALL BE NEATLY RECORDED AS ACTUALLY INSTALLED FOR AS-BUILT RECORDS. SUBMIT TO THE OR TILE). .90 FOR ALL CASES. BALLAST SHALL COMPLY WITH FCC REQUIREMENTS UNDER PART 18, CLASS A. ` '
<br /> ARCHITECT UPON PROJECT COMPLETION. 5. JUNCTION AND PULL BOXES FOR INTERIOR AREAS: STEEL, SCREW COVER, CODE GAUGE AND SIZE. ALL BALLASTS SHALL BE GUARANTEED BY THE MANUFACTURER FOR A PERIOD OF TYYO YEARS AFTER
<br /> LARGE JUNCTION AND PULL BOXES SHALL BE FABRICATED SHEET STEEL WITH BAKED ENAMEL FINISH 3. RECEPTACLE FACES: BLACK IN GO�OR, WHITE IN COLOR IF ON WHITE SURFACE (PAINT OR TILE) INSTALLATION. RAPID-START BALLASTS SHA�L BE CERTIFIED TO HAV�'AAf$OUND RATING. THE '
<br /> G. CERTIFICATES OF INSPECTION: SUBMIT SIGNED-OFF PERMITS FROM THE CODE ENFORCWG AND RETURN FLANGE WITH SCREW RETAINED COVER. FOR NORMAL POWER. VOLTAGE RATING OF THE BALLAST SHALL BE AS REQUIRED BY THE SERVICE VOLTAGE. �
<br /> AGENCIES TO THE OWNER UPON PROJECT COMPLETION. �hnackel
<br /> C. EXECUTION B. RECEPTACLES - @(1Qjt1t�'S �
<br /> H. PRODUCT LISTING OR LABELING: ALL ELECTRICAL EQUIPMENT SHALL BE LISTED AND LABELED BY 271500 -COMMUNICATIONS HORIZONTAL CABLING N°'"Y°�`°o�"otoa�°s�°°H°"°p"p,s �
<br /> UNDERWaITERS LABORATORIES, INC. 1. GENERAL: 1. DUPLEX RECEPTACLES: SPECIFICATION-GRADE, 20 AMPERE, 125-VOLT, GROUNDED TYPE, HBL5362 800-581-0963 wryrwsdwdoNmm
<br /> SERIES. A. SCOPE: CONTRACTOR SHALL FURNISH AND INSTALL ALL MATERIALS FOR A COMPLETE, FUNCTIONAL gE�o�: ,go�,6
<br /> I. MATERIAL AND EQUIPMENT: ALL MATERIALS AND EQUIPMENT SHALL BE NEW UNLESS NOTED a. COORDINATION: THE CONTRACTOR SHALL REVIEW ALL DRAWINGS, DEL4ILS, AND ELEVATIONS PRIOR DATA AND VOICE COMMUNICATIONS SYSTEM INFRASTRUCTURE IN ACCORDANCE WITH THIS SPECIFICATIONS '
<br /> OTHERWISE. PROTECT ALL MATERIALS AND EQUIPMENT FROM DAMAGE OR CORROSION. TO ROUGH-IN. WHERE EQUIPMENT IS FURNISHED BY OTHERS, THE CONTRACTOR SHALL REVIEW ALL 2. DOUBLE DUPLEX RECEPTACLES: SPECIFICATION-GRADE, 20-AMPERE, 125-VOLT, GROUNDED TYPE, AND THE CONTRACT DRAWINGS. �
<br /> DRAWINGS, DETAILS AND ELEVATIONS PRIOR TO ROUGH-IN. WHERE EQUIPMENT IS FURNISHED BY HBL5362 SERIES.
<br /> J. CUTTING AND PATCHING: PROVIDE ALL REQUIRED CUTTING AND PATCHING FOR THE ELECTRICAL OTHERS, THE CONTRACTOR SHALL ASCERTAIN THE PROPER VOLTAGE, LOAD AND CONNECTION B. INSTALLATION SHALL INCLUDE CABLE (TWISTED-PAIR COPPER), INTERCONNECT PATCH EQUIPMENT, �
<br /> WORK. REQUIREMENTS PRIOR TO ROUGH-IN. 3. GROUND FAULT INTERRUPTION RECEPTACLE: SPECIFICATION-GRAQE, 2Q-AMPERE, 120-VOLT, CONNECTORS, JUMPERS, WIRING BLOCKS AND TELECOMMUNICATIONS OUTLETS.
<br /> CLASS A, 5-MILLfAMPERE SEN5ITIVITY, GF5362 SERIES.
<br /> K. EXISTING CONDITIONS b. MATERIALS; ALL MATERIALS OF A SPECIFIC TYPE SHALL BE PROVIDED BY THE SAME
<br /> " MANUFACTURER THROUGHOUT THE PROJECT. e. SWITCHES C. UPON COMPLETION OF INSTALLATION THE CONTRACTOR SHALL TEST ALL COPPER PATHWAYS AND s�'� ' '
<br /> 1. GENERAL: SPECIFIC SCOPE OF DEMOLITION WORK AND OPERATING CONDITIONS TO BE '
<br /> a RECORD THE TEST RESULTS.
<br /> ENCOUNTERED SHALL BE VERIFIED BY ON-SITE REVIEW PRIOR TO SUBMI?TWG BID. DEMOLITION WORK 2. RACEWAYS: INSTALL RACEWAY NPES AND SIZES AS L.ISTED BELOW; 1. SINGLE-POLE SWITCHES: SPECIFICATION-GRADE, 20AMPERE, 1221 SERIES. ROY S �
<br /> IN GENERAL IS NOTED OR SHOWN ON THE DOCUMENTS BASED UPON AVAILAffi1f�WINGS OF RECORD' D. PROVIDE THREE JACKS PER OUTLET LOCATIONS AS SHOWN ON PLANS. USE SINGLE GANG, FLUSH Q�y oF w,as,�, Cy�
<br /> AND MAY NOT SHOW THE ACTUAL CONDITIONS AS THEY PRESENTLY EXIST. a. ELECTRICAL METALLIC TUBING (EMT): ALL INTERIOR AREAS. MAY BE USED FOR FEEDERS WITH 2. THREE-WAY SWITCHES: SPECIFICATION-GRADE, 20-AMPERE, 1223 SERIES. MOUNT FACEPLATES. PROVIDE ONE CATEGORY 5E CABLE PER JACK UNLESS OTHERWISE INDICATED. � �`� ��� 9�
<br /> INTEGRAL GREEN GROUND CONDUCTOR. TERMINATE WITH CATEGORY 5E INSERT JACKS UNLESS OTHERWISE INDICATED. PROVIDE UNIPRISE � ;� � T '
<br /> 2. OWNER-RETAINED EQUIPMENT: THE OWNER MAY WISH TO RETAIN CERTAIN SPECIFIC ITEMS 3. OCCUPANCY WALL SWITCHES: SPECIFICATION-GRADE, 20-AMPERE WITH INTEGRAL PRECISION �„� _ � � '
<br /> S C H E D U L E D F O R D E M O L I T I O N. T H E C ONTR A C TOR SH ALL C AREFUL�Y REMO VE THESE ITEMS, PROVIDE b. FLEXIBLE METALLIC CONDUIT: RECESSED FIXTURE CONNECTIONS, INTERIOR CONCEALED EQUIPMENT I N F R A R E D O C C U P A N C Y S E N S O R. #CCQ0205XX (XX=COL�R) MODULAR JACKS FACEPLATES SHALL BE WHITE, CQMMSCOPE #1 08 1 68543. ' r- .
<br /> PROTECTION AND PACKAGING AS MAY BE REQUIRED TO PROTECT THE EQUIPMENT AND TURN OVER SOLD CONNECTIONS, EXPANSION JOINTS AND SOUND CONTROL. NOT TO BE USED FOR EXP05ED E. P R O V I D E S U P E R I O R E S S E X D A T A G A I N #6 6-2 4 0-2 B D A T A S T A T I O N CA B L E, 4-PA I R, 2 4A W G, U T P, �r
<br /> EQUIPMENT TO THE OWNER AT A PLACE DESIGNATED ON THE JOBSITE. ANY EQUIPMENT THAT THE INSTALLATIONS WITHIN THE FlNISHED AREAS OF THE BUILDING. 4. LOW VOLTAGE WALL SWITCHES: HUBBELL LOW VOLTA�E SWITCH LVSM SERIES OR APPROVED A '�'F�/S T EREO � '9 .
<br /> OWNER DOES NOT DESIRE TO RETAIN SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND BE E Q U A L. U O/N E C C M P O R E Q U I V A L E N T. �� :
<br /> REMOVED FROM THE SITE. c. MINIMUM RACEWAY SIZE SHALL BE 3/4INCH, EXCEPT FOR RACEWAYS WITH NO MORE THAN THREE F. ALL CABLES RQUTED ON BACKBOARDS SHALL BE SUPPORTED USING NYLON ZIP TIE MOUNTS THAT FS NA
<br /> #12 AWG CONDUCTORS WHICH MAY BE 1/2 INCH. 5. LINE VOLTAGE DIMMING SWITCHES: SPECIFICATION GRADE, 800W SLIDE DIMMING SWITCH. LEVITON ARE SECURLY MOUNTED TO THE BACK BOARD BY SCREWS IN ADDITION TO THE ADHESIVE BACK. '
<br /> 3. UNUSED CONDUIT AND WIRING: ALL UNUSED CONDUCTORS RESULTING FROM THIS PROJECT SHALL RENOIR SERIES OR APPROVED EQUAL. co,a l�•2sos oot�: o�/»/�s
<br /> BE REMOVED. ALL UNUSED CONDUIT SHALL BE REMOVED EXCEPT WHERE L�CATED IN OR ABOVE D. INSTALLATION:
<br /> EXISTING CONSTRUCTION WHICH IS NOT BEING ALTERED AND WOULD REQUIRE REMOVAL AND 6. TIMER SWITCH: EI600 SERIES DIGITAL IN-WALL TIMERS G. DATA/VOICE TERMINAL BACKBOARD SHALL BE �" THICK PLYWOOD, APA EXTERIOR GRADE DOUGLAS
<br /> ' REPLACEMENT OF THE EXISTING CONSTRUCTION. 1_ CONCEALMENT: ALL RACEWAYS SHALL BE CONCEALED IN FINISHED AREAS. WHERE EXISTING WALL FIR A-C, AND FIRE RETARDANT WITH FLAME SPREAD RATING NOT MORE THAN 25 WHEN TESTED • . .
<br /> SURFACES ARE INACCESSIBLE, SURFACE METAL RACEWAYS FOR THESE EXCEPTIONS MAY BE PROVIDED D. DEVICE PIATES: BLACK IN COLOR, WHITE IN COLOR IF ON WHITE SURFACE (PAINT OR TILE), ACCORDING Td ASTM E-84. •
<br /> 4. EXISTING TEL/DATA CABLES AND OUTLETS: PROVIDE DEMOLITION OF EXISTING VOICE DATA WHEN APPROVED. SMOOTH, HIGH-IMPACT TNERMOPIASTIC, P&S/SIERRA OR APPROVED EQUAL H. PROVIDE SUPERIOR ESSEX CAT 3 4 PAIR STATION CABLE FOR ALL JACKS LASELED FOR
<br /> OUTLEfS EXCEPT WHERE OTHERWISE SHOWN. VERIFY EXTENT OF WORK PRIOR TO SUBMITTING BID.
<br /> PROPERLY SUPPORT AND MAINTAIN IN SERVICE ANY REMAINING VOICE/DATA SYSTEM WIRING INSTALLED 2. EXPOSED RACEWAYS. INSTALL EXPOSED RACEWAYS AS HIGH AS POSSIBLE> ABOVE DUCTWORK, E. EXECUTION TE�EPHONE PROVIDE # 18-241-43 WHITE, PLENUM RATED OR EQUIVALENT.
<br /> EXPOSED ABOVE SUSPENDED CEILINGS WITHIN THE PROJECT AREA. SECURE CABLES TO STRUCTURE PARALLEL OR AT RIGHT ANGLES TO BUILDING LINES. �
<br /> ABOVE USING TIE WRAPS SECURED TO INDEPENDENT TIE WIRES SUSPENDED FROM STRUCTURE ABOVE. 1. GENERAL• INSTALL DEVICES LEVEL, PLUMB AND SQUARE WITH BUILDING LINES. I. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING EMT SLEEVES AT ANY LOCATION WHERE "
<br /> 3. EXPANSION AND EARTHQUAKE JOINTS. RACEWAYS SHALL NOT BE INSTALLED IN CONCRETE SLAB A WALL, PARTITION, FLOOR OR CEILWG 15 PENETRATED. WHERE A FIRE-RATED WALL, FLOOR OR
<br /> 5. EXISTWG RACEWAYS: PROPERLY SUPPORT ALL EXISTWG RACEWAYS ABOVE SUSPENDED CEIUNGS OR WALL CONSTRUCTION WHEN PASSING THROUGH ON EXPANSION OR EARTHQUAKE JOINT. 2. SWITCH LOCATIONS: LOCATE SWITCHES 6 INCHES FROM DOOR CASING. CEILING IS PENEfRATED, SEA� AROUND ALL CABLES WITH UL CLASSIFIED FIRE SEAL SUFFICIENT TO �
<br /> WHERE WORK IS TAKING PLACE. VERIFY EXTENT OF WORK PRIOR TO SUBMITTING BID. RETURN THE STRUCTURE TO ITS ORIGINAL RATING. '�
<br /> 4. ROUTING: ALL RACEWAYS SHALL BE INSTALLED PARA�LEL OR AT RIGHT ANGLES TO THE BUILDING 3. RECEPTACLE MOUNTING HEIGHT: + 18"TO THE CENTERLINE OF THE BOX UNLESS OTHERWISE �
<br /> � L. CONTINUITY OF SERVICE: PERMANENTLY REROUTE OR RELOCATE EXISTING WIRING AND/OR CONSTRUCTION UNLESS PROHIBITED BY A PHYSICAL OBSTRUCTION. NOTED. J. PROVIDE PLASTIC BUSHING ON ALL CONDUITS AND SLEEVES PRIOR TO INSTALLING CABLE. CABLE �
<br /> EQUIPMENT WHICH IS IN CONFLICT WITH EXISTING BUILDING ALTERATIONS AND WHICH IS REQUIRED TO 5. RACEWAY SUPPORTS: RACEWAYS SHALL BE SUPPORTED WITH HEAVY-DUlY, ONE-HOLE, PRESSED INSTALLED IN CONDUITS OR SLEEVES WITHOUT BUSHINGS SHALL BE REMOVED AND REPLACED. ,
<br /> BE MAINTAINED IN USE. STEEL 5TRAPS ON INTERIOR SURFACES. SUPPORT PENDANT-MOUNTED RACEWAYS ON 3/8 INCH ROD 4. SWITCHES: + 48-TO THE CENTERLINE OF THE BOX.
<br /> WITH PEAR-SHAPED HANGER OR TRAPEZE-TYPE HANGER WITH 3/8 INCH ROD (MINIMUM) AND K. PROVIDE METALLIC RACEWAYS, ABOVE INACCESSIBLE CEtLINGS, INSTALLED EXPOSED OR WHERE
<br /> 262416 -PANELBOARDS SUBJECT TO PHYSICAL DAMAGE. RACEWAY FILL SHALL NOT EXCEED 40 PERCENT. MINIMUM RACEWAY
<br /> , M. REMOVAL AND REPLACEMENT OF EXISTING ACCESSIBLE CEILING PANELS, LIGHTING FIXTURES AND 1-5/8 INCH SQUARE PREFORMED CHANNEL AND PIPE CLAMPS. PARALLEL, SURFACE-MOUNTED SIZE SHALL BE 3/4 INCH. ,� �
<br /> SPEAKERS: REMOVE AND REINSTALL ALL NECESSARY GEILING PANELS, LIGHTING �IXTURES, SPEAKERS RACEWAYS SHALL BE SUPPORTED FR�M 1-5/8 INCH SQUARE PREFORMED CHANNEL AND PIPE CLAMPS. A. 480Y
<br /> ��
<br /> AND OTHER EXISTING EQUIPMENT IN EXISTING ACCESSIBLE CEILINGS AS REQUIRED TO INSTALL THE ALL FITTINGS AND SUPPORTS HALL BE HOT-DIP GALVANIZED IN EXTERIOR AREAS. /277V OR 208Y/120V, COPPER BUS BOLT-ON MOLDED CASE THERMAL MAGNEfIC TYPE � Q
<br /> ELECTRICAL WORK. CIRCUIT BREAKERS HAVING A MINIMUM WTERRUPTING R,4TING OF 14,Od0 AMPERE FOR 480Y/277V � N '
<br /> 6. INDEPENDENT SUPPORT: CONDUITS SHALL NOT BE SUPPORTED FROM THE CEILING SUSPENSION PANELS AND 10,OaQ AMPERE FOR 208Y/120V PANELS. Z �
<br /> N. ANCHOR,4GE AND BRACING: PROVIDE COMPLEfE SEISMIC ANCHORAGE AND BRACING fOR THE SYSTEM, DUCTS, PIPES OR OTHER SYSTEMS FOREIGN TO THE ELECTRICRL INSTALLATION. THE ENTIRE W W
<br /> LATERAL AND VERTICAL SUPPORT OF CONDUIT AND ELECTRICAL EQUIPMENT AS REQUIRED BY THE ELECTRICAL INSTALLATION SHALL BE KEPT INDEPENDENT FROM ANY OTHER TRADE. B. MOUNTING: WHERE PANELBOARDS ARE TQ BE INSTALLED AGAINST PLASTERBOARD WALLS, PROV►DE W `� .
<br /> INTERNATIONAL BUILDING CODE. END OF ELECTRICAL SPECIFlCATIONS
<br /> SEPARATE SUPPORT CHANNELS SECURED TO BLOCKING BETWEEN STEEL STUQS. COORDINATE BLOCKWG � � � . .
<br /> 0. FIRESTOPPING: PROVIDE FIRESTOPPWG FOR ALL PENETRATION IN RATED WALLS, CEILINGS AND �• PUL�BOXES WITH COVERS: SHAL� BE PROVIDED AS SHOWN ON THE DRAWINGS OR AS REQUIRED WORK WITH THE GYPSUM WALLBOARD CONTRACTOR. PANELS SHALL NOT BE SECURED DIRECTLY TO
<br /> FLOORS. BY CODE. ALL PULLBOXES SHAL� BE LOCATED SO AS TO BE ACCESSIBLE. GYPSUM WALLBOARD MATERIAL. � �
<br /> •;
<br /> 8. FLEXIBLE CONDUIT: SHALL BE USED ONLY FOR LIGHTING FIXTURE PIGTAILS IN ACCESSBLE C. PROVIDE SHORT CIRCUIT STUDY OBTAINING AVAILABLE FAULT FROM SERVING UTILITY. PROVIDE = W �
<br /> P. PAINTING: PAINT ALL EXPOSED RACEWAYS, EXCEPT SMR, IN FINISHED AREAS TO MATCH ADJACENT CEILINGS, FLUSH-MOUNTED SPEAKER PIGTAILS IN ACCESSIBLE CEILINGS, SOUND CONTROL, MOTOR DOCUMENTATION TO DEMONSTRATE THAT ALL SUBMITTED EQUIPMENT AND PROTECTIVE DEVICES MEET OR W L�
<br /> SURFACES. CONNECTIONS AND AT BUILDING EXPANSION JQINTS AS SPECIFIED. ANY OTHER PROPOSED USE OF EXCEED AVAILABLE FAULT AT POINT OF APPLICATION. PROVIDE E4UIPMENT W COMPUANCE WITH � � j �
<br /> FLEXIBLE CONDUIT MUST BE APPROVED PRIOR TO INSTALLATION. AVAIIABLE FAULT.
<br /> Q. INSTRUCTION: CONTRACTOR SHALL INSTRUCT THE OWNER W THE USE AND OPERATION OF ALL � W
<br /> SYSTEMS INSTALLED UNDER THE SCOPE OF THIS CONTRACT. 9. EMPTY RACEWAYS: PROVIDE A NYLON PULL STRWG IN ALL EMPTY RACEWAYS. D. PERFORM AN ARC-FLASH STUdY IN ACCORDANCE WITH THE NEC AND AHJ TO DETERMINE INCIDENT � �
<br /> ENERGY EXPOSURE, FLASH PROTECTIQN BOUNDARY, SHOCK HAZARD APPROACH LIMITS AND REQUIRED ' �
<br /> R. OWNER FURNISHED EQUIPMENT: PROVIDE COMPLETE ELECTRICAL SERVICE AND CONNECTION TO 10. BOXES AND FIl-fINGS: PPE LEVELS. PROVIDE REQUIRED DATA FOR APPROVED ARC-FLASH WARNING LABELS ON ALL �
<br /> ALL OWNER-FURNISHED EQUIPMENT. PANELBOARDS ANQ DISCONNECT SWITCHES. PROVIDE WARNING LABELS ON ALL PANELBOARDS. '
<br /> B a. GENERAL: BOXES SHALL BE SUPPORTED SECURELY AND INDEPENDENTLY. MOUNT BOXES ON
<br /> 260519 - CONDUCTORS AND GABLES BUILDING SURFACES OR SUPPORT WITH TRAPEZE HANGER AS DESCRIBED IN RACEWAY INSTALLATION. E. PROVIDE NAMEPLATE FOR EACH PANELBOARD PER 260553 ELECTRICAL IDENTIFICATION. �
<br /> JUNCTION BOXES SHALL NOT BE USED UNLESS THE NUMBER OF BENDS, PULLING LENGTH, OR CIRCUIT F. APPROVED MANUFACTURER'S: SQUARE D, GENERAL ELECTRIC OR SIEMENS.
<br /> A. WIRE AND CABLE: REQUIREMENTS NECESSITATES THEIR INSTALLATION. JUNCTION OR PULLBOX OPENINGS MUST BE � .
<br /> ACCESSIBLE.
<br /> 1. BRANCH CIRCUITS: TYPE THHN OR THWN, 6Q0-VOLT INSULATION, STRANDED COPPER CONDUCTOR. 262816 -ENCLOSED SWITCHES AND CIRCUR BREAKERS .,
<br /> MINIMUM CONDUCTOR SIZE: b. SOUND CONTROL: WHERE BOXES ARE MOUNTED IN A COMMON WALL, THEY SHALL WHEREVER
<br /> POSSBLE, BE OFFSET HORIZONTALLY SO THAT THEY ARE NOT MOUNTED BACK-TO-BACK. CONNECT A. APPROVED MANUFACTURER'S: SQUARE D, GENERAL ELECTRIC OR SIEMENS. �
<br /> a. NEUTRAL: #12 RWG OFFSEf BOXES WITH FLEXIBLE CONDUIT N4T TO EXCEED 18 INCHES IN LENGTH.
<br /> B. SINGLE-PHASE MOTOR: MOTORS 1/3 HP OR LESS PROVIDE WITH TOGG�E-TYPE, 20-AMP, �
<br /> b. GROUND: #12 AWG 260553 -IDENTIFICATION FOR ELECTRICAL SYSTEMS 120-VOL7 RATING, SPECIFICATION-GRADE DISCONNECT SWITCHES.
<br /> , c. PHASE CONDUCTORS (MORE THAN SIX IN A RACEWAY): #10 AWG A. GENERAL: LABEL ALL JUNCTION BOXES, TERMINAL CABINETS, ETC., WITH 7HE CIRCUIT NUMBER OR C. THREE-PHASE MOTOR: MOTORS � HP AND LARGER PROVIDE WITH AMP AND VOLTAGE RATING AS
<br /> LOW-VOLTAGE SYSTEM CONTAINED WITHIN. REQUIRED, SPECIFICATION-GRADE DISCONNECT SWITCHES. NEMA RATED PER ENVIRONMENT. • �
<br /> d. PHASE CONDUCTORS (SIX OR LESS IN A R,4CEWAY): #12 AWG D. EQUIPMENT DISCONNECTS: SHALL BE FUSED OR NONFUSED AS REQUIRED BY THE EQUIPMENT
<br /> B. EQUIPMENT NAMEPLATES: SHALL BE ENGRAVED IN 1/16 INCH THICK PHENQLIC �ErrERs a ISSUEDIREVISED DATE �
<br /> 2. FEEDERS: FEEDERS SHALL BE SIZED AS SHOWN ON THE DRAWINGS AND COLOR-CODED IN MINIMUM OF 3/16 INCH HIGH. GOLORING SHALL BE WNITE LETfERS ON BLACK BACKGROUND. MANUFACTURER, RATED AT 125 PERCENT OF FULL LOAD NAMEPIATE AMPERAGE OR RATED HORSEPOWER, PERMITSET 07,��.19
<br /> ACCORDANCE WITH LIST BELOW. MAKE NO SPLICES UNLESS SHOWN ON THE PLANS. - HEAVY-DUTY TYPE.
<br /> 260923 -LIGHTING COMROL DEVICES E. DISCONNECTS: PROVIDE DISCONNECTS AT ALL MOTORS AND OTHER EQUIPMENT ITEMS UNLESS � •
<br /> 3. COLOR CODE WIRE IN ACCORDANCE WITH THE CODING SHOWN BELOW. POWER SYSTEMS THE EQUIPMENT HAS A SELF-CONTAINED, CODE APPROVED DISCONNECTING MErHOD. EQUIPMENT �
<br /> CONDUCTORS ARE IDENTIFIED AS FOLLOWS: A. OCCUPANCY SENSOR: DUAL TECHNOLOGY TYPE, CEILING OR WALL SWITCH MOUNTED. USE A DISCONNECTS SHALL BE FUSED OR NON-FUSED AS REQUIRED BY THE EQUIPMENT MANUFACTURER.
<br /> 208Y 120V 480Y 277V COMBINATION OF PASSIVE INFRARED AND ULTRASONIC DETECTION MEfHODS. MANUFACTURE�2: HUBBELL .;
<br /> PHASE A: BLACK BROWN OR APPROVED EQUAL 262813 -FUSES
<br /> PHASE B: RED ORANGE �
<br /> PHASE C: BLUE YELLOW 260926 -UGHTING CONTROL PANELBOARDS A. MANUFACTURERS: BUSSMAN, FERREZ SHAWMUT.
<br /> A NEUTRAL: WHITE GRAY
<br /> GROUND: GREEN GREEN A. GENERAL: B. FUSES: PROVIDE 200,0-QO AIC, CURRENT LIMITING, UL TIME DELAY FUSES AS FOLLOWS:
<br /> , TRAVELERS; YELLOW (FOR 3- AND 4-WAY SWITCHING) 1. THE WORK COVERED IN THIS SECTION IS SUBJECT TO ALL OF THE REQUIREMENTS IN THE 1. FEEDERS 600 AMPS AND LESS: CLASS RK-1, LPN-RK FOR 250-VOLT, DUAL ELEMENT, CLASS
<br /> CONTROLS: BLACK WITH WIRE NUMBERS ON EACH CONDUCTOR GENERAL CONDITIONS OF THE SPECIFICATIONS. CONTRACTOR SHALI. COORDINATE ALL OF THE WORK IN RK-1, LPS-RK FOR 600 VOLT, DUAL ELEMENT. � �
<br /> THE SECTION WITH ALL OF THE TRADES COVERED IN OTHER SECTIONS OF THE SPECIFICATION TO
<br /> 4. SPLICES AND TERMINATIONS: LIGHTING AND RECEPTACLE BRANCH CIRCUIT CONDUCTORS UP TO PROVIDE A COMPLETE AND OPERABLE SYSTEM. 2. MOTOR CIRCUIT 600 VOLTS AND BELOW: CLASS RK-1 OR CLASS J SIZED AT 125 PERCENT FLC PERMITSET O7,�Z,19
<br /> N0. 10 AWG SHALL BE SPLICED WITH WING NUT TYPE CONNECTORS. OF MOTQR.
<br /> 2. SYSTEM DESCRIPTION: WSTALL A LIGHTING CONTROL SYSTEM CONSISTING OF RELAY/CONTACTOR
<br /> 260526 -GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS PANEL(S), CONTROL SWITCHES, OCCUPANCY SENSORS, PHOTOCELLS AND OTHER CONTROLLING DEVICES. C. MOTOR �oNTRa�s ELECTRICAL � �
<br /> THE DEVICES ARE CONNECTED BY LOW-VOLTAGE AND LINE-VOLTAGE WIRING. THE GENERAL OPERATION �
<br /> A. GENERAL: PROVIDE THROUGH THE ENTIRE ELECTRICAL SYSTEM. A SEPARATE GREEN EQUIPMENT OF LIGHTING AND CONTROLLED LOADS SHALL INCLUDE: 1. APPROVED MANUFACTURERS: SQUARE D, GENERAL ELECTRIC OR SIEMENS. SPECIFICATIONS ;;
<br /> GROUNDING CONDUCTOR SHALL BE PROVIDED IN ALL LIGHTING AND POWER f2ACEWAYS.
<br /> a. INTERIOR LIGHTING, MANUAL SWITCH, PHOTOCELL AND OCCUPANCY SENSOR CONTROL ON/OFF WITH 2. MANUAL STARTERS: TOGGLE TYPE, LOCKABLE �N THE OFF POSITION, OVERLOAD PROTECTION, PILOT :
<br /> B. BONDING: IN�ULATED GROUNDING BUSHINGS SHALL BE INSTALLED TO BOND ALL FEEDER AUTOMATIC TIME SCHEDULED SHUT OFF. LIGHT AND NEMA 1 ENCLOSURE.
<br /> CONDUITS TO THE SWITCHBOARD GROUND BUS OR PANEL GROUND BUS AT BOTH ENDS OF FEEDER
<br /> RACEWAYS. INSULATED GROUNDWG BUSHINGS SHALL BE INSTALLED TO BOND A�L FEEDER CONDUITS b. SCHEDULED ON-OFF LOADS: TIME ON, TIME -0FF BY AUTOMATIC TIME SCHEDULE WITH AFTER �
<br /> TO THE GROUND BUS OR PANEL ENCLOSURES AT BOTH ENDS OF THE RUNS. HOUR OVERRIDE CAPABILITY AND SHUTOFF.