H E D L E ����f`
<br /> U � �����
<br /> American Property Development,Inc.
<br /> 110 110th Avenue NE suite 550
<br /> FAN SCHEDULE SYSTEM HEAT PUMP SCHEDULE - INDOOR UNIT Bellevue,WA98004
<br /> EQUIP MOUNTING/ AIRFLOW, ESP. IN ELECTRICAL WEIGHT, POWER LEVEL, COOLING CAPACITY,
<br /> SERVICE OPERATION BASIS OF DESIGN (1) FAN TOTAL ELECTRICAL
<br /> N0. DISCHARGE CFM WG VOLTAGE HP LBS dBA MOUNTING/ BTUH HEATING WEIGHT BASIS OF DESIGN CONNECTED
<br /> EQUIP N0. SERVICE �BS OUTDOOR
<br /> GEF-1 GARAGE EXHAUST INLINE 39,000 1.5 208V/3P 20 (5) 1,315 94 GREENHECK TBI-FS-5L48-200 (4) DISCHARGE AIRFLOW, CFM CAPACITY, � ) ��� UNIT
<br /> GEF-2 GARAGE EXHAUST INLINE 2,600 1.5 208V 3P 2 5 150 78 GREENHECK TBI-FS-5H24-20 4 TOTAL SENSIBLE BTUH VOLTAGE RLA
<br /> HIGH/MED/LOW
<br /> TF-1 GARAGE TRANSFER FAN CEILING 1550 0.5 208 3P 0.5 - CONTINUOUS 254 77 HOWDEN ITF-50 4 16 LOBBY COFFEE CEILING �
<br /> TF-2 GARAGE TRANSFER FAN CEILING 1550 0.5 208 3P 0.5 - CONTINUOUS 254 77 HOWDEN ITF-50 4 16 FCU-1 AREA DUCTED 1800/155Q/1450 54,000 40,500 61,400 208V/1P 3.5 115 LG ARNU543BRA4 HP-1 �O���O�
<br /> TF-3 GARAGE TRANSFER FAN CEILING 1550 0.5 208 3P 0.5 - CONTINUOUS 254 77 HOWDEN ITF-50 4 16 CEILING
<br /> �
<br /> FCU-2 LOBBY GAME ROOM DUCTED 1800/1550/1450 54,000 40,500 61,400 208V/1P 3.5 115 LG ARNU543BRA4 HP-2 ENGINEERING, ING
<br /> VTSF-2 TRANSFORMER SUPPLY INLINE 1,200 0.25 120V 1P 1 2 11 124 59 GREENHECK BSQ-120-5 4 15 LOBBY LIVING ROOM CEILING 1940140THAVEW.,SUITE302
<br /> VTEF-1 TRANSFORMER EXHAUST INLINE 1,800 0.25 120V 1P 3 4 11 139 65 GREENHECK BSQ-130-7 4 15 FCU-3 aND OFFICES DUCTED 1800/1550/1450 54,000 40,500 61,400 208V/1P 3.5 115 LG ARNU5436RA4 HP-3 LY206-3064334398036
<br /> � VTEF-2 TRANSFORMER EXHAUST INLINE 1,800 0.25 120V 1P 3 4 11 139 65 GREENHECK BSQ-130-7 4 15 LOBBY RECEPTION CEILING CONTACT:JONROBISON
<br /> FCU-4 AND MAIL ROOM DUCTED 1800/1550/1450 54,000 40,500 61,400 208V/1P 3.5 115 LG ARNU543BRA4 HP-4
<br /> EF-1 RESIDENTIAL UNIT CEILING MOUNTED 55 80 0.25 120V/1P FHP 9) 10) 25 0.3 PANASONIC FV-08VKM3 (3 CEILING
<br /> EF-2 PHONE CABLE ROOM INLINE 400 0.25 120V/1P FHP (12) 55 39 GREENHECK CSP-A510 (2) FCU-5 GYM DUCTED �150/1000/900 36,200 27,500 40,600 208V/1P 2.65 115 LG ARNU363BRA4 HP-5 ��pOo�oDpO�
<br /> EF-3 ELEC/METER ROOM INLINE 400 0.25 120V/1 P FHP (12) 36 39 GREENHECK CSP-A510 (2) NOTES: 1 REFRIGERANT SHALL BE R-410A. � �� �R�e/�p
<br /> �'��oF W'�tii �.S �
<br /> EF-4 GARAGE TRASH AREA INLINE 280 0.25 120V/1 P FHP CONTINUOUS 23 38 GREENHECK CSP-A290 (2) o Q-:�� �..pZo
<br /> EF-5 L3 TRASH AREA INLINE 100 0.25 120V/1P FHP CONTINUOUS 11 39 GREENHECK CSP-B110 (2) o'�: _ � °
<br /> EF-6 L3 CORRIDOR SOUTH CEILING MOUNTED 200 0.25 120V/1 P FHP CONTINUOUS 24 40 GREENHECK SP-A200 (2) o ��.. � � :� a �
<br /> EF-7 L3 CORRIDOR NORTH CEILING MOUNTED 200 0.25 120V/1 P FHP CONTINUOUS 24 40 GREENHECK SP-A200 (2) S YS TE M H E A T P U M P S C H E D U L E - 0 U TD 0 0 R U N I T o � F��� p ..� o
<br /> EF-8 L4 TRASH AREA INLINE 100 0.25 120V/1P FHP CONTINUOUS 11 39 GREENHECK CSP-B110 (2) EQUIP CAPACITY, TOTAL COOLING TOTAL HEATING ELECTRICAL DIMENSIONS, WEIGHT, BASIS OF DESIGN ��O ��ONAL E�\p�0
<br /> EF-9 L4 CORRIDOR SOUTH CEILING MOUNTED 200 0.25 120V/1P FHP CONTINUOUS 24 40 GREENHECK SP-A200 (2) SERVICE IN HE CONNECTED FAN COIL UNIT �Opoopp0�
<br /> N0. TONS CAPACITY, BTUH CAPACITY, BTUH LBS
<br /> EF-10 L4 CORRIDOR NORTH CEILING MOUNTED 200 0.25 120V/1 P FHP CONTINUOUS 24 40 GREENHECK SP-A200 (2) VOLTAGE MCA MOCP L W H (1)(2)(3)(4) >0/>3/> 7
<br /> EF-11 L5 TRASH AREA INLINE 100 0.25 120V/1P FHP CONTINUOUS 11 39 GREENHECK CSP-6110 (2) LOBBY COFFEE
<br /> EF-12 L5 CORRIDOR SOUTH CEILING MOUNTED 200 0.25 120V/1P FHP CONTINUOUS 24 40 GREENHECK SP-A200 (2) HP-1 AREA 5 60,000 64,000 208V/1P 25.4 40 38 13 55 275 LG ARUN060GSS4 FCU-1
<br /> COPYRIGHT CO 2005, ALL RIGHTS RESERVED
<br /> EF-13 L5 CORRIDOR NORTH CEILING MOUNTED 200 0.25 120V/1P FHP CONTINUOUS 24 40 GREENHECK SP-A200 (2) HP-2 LOBBY GAME ROOM 5 60,000 64,000 208V/1P 25.4 40 38 13 55 275 LG ARUN060GSS4 FCU-2 SUBMITTAL/REVISIONS
<br /> EF-14 L6 TRASH AREA INLINE 100 0.25 120V/1 P FHP CONTINUOUS 11 39 GREENHECK CSP-B110 (2)
<br /> EF-15 L6 CORRIDOR SOUTH CEILING MOUNTED 200 0.25 120V/1P FHP CONTINUOUS 24 40 GREENHECK SP-A200 (2) HP-3 LOBBY LIVING ROOM 5 60,000 64,OOQ 208V/1P 25.4 40 38 13 55 275 LG ARUN060GSS4 FCU-3 # oATE DESCRIPTION
<br /> AND OFFICES
<br /> EF-16 L6 CORRIDOR NORTH CEILING MOUNTED 200 0.25 120V/1P FHP CONTINUOUS 24 40 GREENHECK SP-A200 (2) ,2/20/,� eio sET
<br /> EF-17 L7 TRASH AREA INLINE 100 0.25 120V/1P FHP CONTINUOUS 11 39 GREENHECK CSP-B110 (2) HP_4 LOBBY RECEPTION 5 60,000 64,000 208V/1P 25.4 40 38 13 55 275 LG ARUN060GSS4 FCU-4 1 03/28/18 PERMIT REVISIONS
<br /> EF-18 L7 CORRIDOR SOUTH CEILING MOUNTED 200 0.25 120Vf1P FHP CONTINUOUS 24 40 GREENHECK SP-A200 (2) AND MAIL ROOM
<br /> EF-19 L7 CORRIDOR NORTH CEILING MOUNTED 200 0.25 120V/1 P FHP CONTINUOUS 24 40 GREENHECK SP-A200 (2) HP-5 GYM 3 38,000 42,000 208V/1 P 25 40 38 13 55 225 LG ARUN036GSS4 FCU-5
<br /> EF-20 RESIDENTIAL UNIT CEILING MOUNTED 60 0.25 120V�1P FHP (6� 25 0.3 PANASONIC FV-08VQC5 (3) NOTES: 1 ARI LISTED WITH ALL STANDARD FEATURES, INSTALLATION ACCESSORIES AND COMPRESSOR SHORT CYCLING PROTECTION. FILTER DRIVER, REFRIGERANT LINE FILTER, LIQUID
<br /> EF-21 L2 SE METER ROOM INLINE 200 0.25 120V/1P FHP (17) 11 39 GREENHECK CSP-6200 (2) 50LENOID VALVE, AND SAFETY PRESSURE SWITCHES. INSTALL REFRIGERANT TUBING AND LENGTH IN STRICT ACCORDANCE WITH MANUFACTURER'S RECOMMENpATION.
<br /> EF-22 L2 NW METER ROOM (NLINE 200 0.25 120V�1P FHP (17� 11 39 GREENHECK CSP-6200 2 (2) PROVIDE ALL REQUIRED ACCESSORIES FOR LOW-AMBIENT AND LONG-LlNE APPLICATIONS.
<br /> � � (3) ROUTING OF REFRIGERANT LINES FROM INDOOR TO OUTDOOR UNITS NOT SHOWN ON PLANS. CONTRACTOR TO FIELD COORDINATE ROUTING.
<br /> EF-23 L1 N ELEVATOR LOBBY INLINE 50 0.25 120V/1P FHP CONTINUOUS 11 39 GREENHECK CSP-6110 (2) (4) REFRIGERANT SHALL BE R-410A.
<br /> EF-25 L2 SW METER ROOM INLINE 200 0.25 120V/1P FHP (17) 11 39 GREENHECK CSP-B200 (2)
<br /> EF-27 LEVEL NE JAN TOR C OSET CEILING LMOUNTED 50 0.25 120V/1 P FHP CONTINUOUS 12 30 GREENHECK SPP A90oo (2> S P L I T A I R C 0 N D I TI 0 N E R S C H E D U L E - 0 U TD 0 0 R U N I T
<br /> � A NOMINCAL TOTAL COOLING SEER ELECTRICAL CONNECTED
<br /> SPF-1 PRESSURIZATION FAN VANE AXIAL 6,000 1.0 208V/3P 2 (14) 325 70 GREENHECK SWB-120-20 (7)(13) EQUIP N0. SERVICE CAPACITY, CAPACITY, BTUH (EER) BASIS OF DESIGN (1)(2)(3) INDOOR UNIT
<br /> STAIR 2 TONS VOLTAGE MCA MOCP
<br /> SPF-2 PRESSURIZATION FAN VANE AXIAL 6,000 1.0 208V/3P 2 (14) 325 70 GREENHECK SWB-120-20 (7)(13) OAC-1 ELEVATOR EQUIP ROOM 1.5 17,000 17.00 208V/1P 12.2 20 LG LSU180HEV (4) IAC-1
<br /> OAC-2 ELEVATOR EQUIP ROOM 1.5 17,000 17.00 208V/1P 12.2 20 LG LSU180HEV (4) IAC-2
<br /> BEF-1 LEVEL 2 BATHROOM CEILING MOUNTED 75 0.25 120V 1P FHP CONTINUOUS 12 30 GREENHECK SP-A90 OAC-3 LEVEL 3 DATA ROOM 0.75 8,500 16.30 208V/1P 9.0 15 LG LSU090HEV IAC-3
<br /> B F-2 L V L 1 B TH 0 M CE LING MOUNT D 5 0.25 12 V 1 P FH C NTINU U 12 30 RE N ECK S -A90 OAC-4 LEVEL 4 DATA ROOM 0.75 8,500 16.30 208V/1 P 9.0 15 LG LSU090HEV IAC-4
<br /> B F- L VE 1 H 0 EI IN U T 7 0 5 2 V P HP CO TI U S 1 3 G E H C S - 0
<br /> OAC-5 LEVEL 5 DATA ROOM 0.75 8,500 16.30 208V/1P 9.0 15 LG LSU090HEV IAC-5 .
<br /> NOTES: 1 PROVIDE BACKDRAFT DAMPERS ON EXHAUST FANS. OAC-6 LEVEL 6 DATA ROOM 0.75 8,500 16.30 208V/1P 9.0 15 LG LSU090HEV IAC-6
<br /> (2) SUPP�Y MANUAL SPEED CONTROLLER. COORDINATE INSTALLATION WITH ELECTRICAL. �
<br /> (3) FAN SHALL HAVE A SONE RATING OF 1.0 OR LESS MEASURED AT 0.10 INCHES WATER COLUMN. NOISE RATING SHALL BE DETERMINED AS PER HVI 915 OAC-7 LEVEL 7 DATA ROOM 0.75 8,500 16.30 208V/1P 9.0 15 LG LSU090HEV IAC-7 �
<br /> (4) PROVIDE VARIABLE FREQUENCY DRIVE (VFD) WITH INTEGRAL DISCONNECT SWITCH. VFD TO BE COMPATIBLE WITH MOTOR. ELECTRICAL TO MOUNT & WIRE VFD. NOTES: 1 ARI LISTED WITH ALL STANDARD FEATURES, INSTALLATION ACCESSORIES AND COMPRESSOR SHORT CYCLING PROTECTION. FILTER DRIER, REFRIGERANT LINE FILTER, LIQUID
<br /> SOLENOID VALVE, AND SAFETY PRESSURE SWITCHES. INSTALL REFRIGERANT TUBING IN STRICT ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS. �
<br /> (5) REFER TO PARKING GARAGE VENTILATION NOTES ON DRAWING M0.01. (2) WITH FACTORY OPTION ELEC7RICAL DISCONNECT. �
<br /> (6� INTERLOCK WITH HUMIDITY CONTROL. (3) ROUTING OF REFRIGERANT LINES FROM INDOOR TO OUTDOOR UNITS NOT SHOWN ON PLANS. CONTRACTOR TO FIELD COORDINATE ROUTING. n 1
<br /> (7) TO BE POWERED BY EMERGENCY ELECTRICAL SYSTEM (TAP AHEAD OF THE MAIN).. (4) PRIOR TO ORDERING, CONTRACTOR TO COORDINATE WITH ELEVATOR MFR TO ENSURE UNIT CAN ADEQUATELY COOL THE ROOM. � �
<br /> (8) INTERLOCK WITH LIGHT SWITCH OR LIGHTING OCCUPANCY SENSOR. COORDINATE WITH ELECTRICAL. (Y�
<br /> (9) INCLUDE SMART ACTION MOTION SENSOR MODULE (FV-MSVK1) AND MULTI-SPEED WITH TIME DELAY (FV-VS15VK1). REFER TO OUTSIDE AIR AND WHOLE HOUSE
<br /> VENTILATION NOTES ON SHEET M001. �
<br /> (10) FAN SHALL BE 2-SPEED, WITH 55 CFM CONTINUOUS LOW SETTING AND 80 CFM HIGH SPEED ACTIVATED BY MOTION SENSOR.
<br /> (11) CONNECT TO THERMOSTATS IN TRANSFORMER VAULT. COORDINATE CONTROL SEQUENCE OF OPERATION REQUIREMENTS WITH SNOHOMISH COUNTY PUD. .
<br /> (13) FAN TS�ALLABE RI ATED &LIUL LIOSTED FOR SMO ET CONTROL SM�TEMS (�MOKE DUTY EQUfREMEN WS)�NG BY E�ECTRICAL. S P L I T A I R C 0 N D I TI 0 N E R S C H E D U L E - I N D 0 0 R U N I T W
<br /> (14) REFER TO SMOKE CONTROL SEQUENCE OF OPERATIONS. FAN ELECTRICAL >
<br /> (15) OPERATE IN TEMPERATURE RANGE FROM 70'F TO 140'F. COATED WITH PERMATECTOR. MOUNTING/ CONNECTED �, (n Z
<br /> (16) PRIOR TO ORDERING, CONTRACTOR TO COORDINATE WITH FAN MFR TO ENSURE THAT THE FAN CAN PROPERLY TRANSFER AIR THROUGH THE GARAGE. EQUIP N0. SERVICE DISCHARGE AIRFLOW, CFM MOTOR VOLTAGE MCA MOCP BASIS OF DESIGN (1)(3) OUTDOOR UNIT .}� Q
<br /> (17) INTERLOCK THERMOSTAT. SET THERMOSTAT TO 70'F. DRIVE � � �
<br /> IAC-1 ELEVATOR CTRL ROOM HIGH WALL 500 DIRECT 208V/1P 0.5 15 LG LSN180HEV (2) OAC-1 � � z
<br /> IAC-2 ELEVATOR CTRL ROOM HIGH WALL 500 DIRECT 208V/1P 0.5 15 LG LSN180HEV (2) OAC-2
<br /> _ IAC-3 LEVEL 3 DATA ROOM HIGH WALL 300 DIRECT 208V/1 P 0.5 15 LG LSN090HEV OAC-3 `�j � _
<br /> C 0 R R I D 0 R M A K E U P A I R U N I T IAC-4 LEVEL 4 DATA ROOM HIGH WALL 300 DIRECT 208V/1 P 0.5 15 �G LSN090HEV OAC-4 � � Q
<br /> IAC-5 LEVEL 5 DATA ROOM HIGH WALL 300 DIRECT 208V/1P 0.5 15 LG LSN090NEV OAC-5 >
<br /> SUPPLY FAN COOLING HEATING ELECTRICAL IAC-6 LEVEL 6 DATA ROOM HIGH WALL 300 DIRECT 208V/1P 0.5 15 LG LSN090HEV OAC-6 � C� �
<br /> EQUIP DISCHARGE ESP, IN MOTOR COOLING ENT AIR LVG AIR GAS AIR TEMP EER WEIGHT, gASIS OF DESIGN IAC-7 LEVEL 7 DATA ROOM HIGH WALL 300 DIRECT 208V/1P 0.5 15 LG LSN090HEV OAC-7 O � F-
<br /> N0. AIRFLOW, TOTAL INPUT OUTPUT VOLTAGE MCA MOCP �gs NOTES: 1 PROVIDE ELECTRICAL DISCONNECT SWITCH AND INDiVIDUAL THERMOSTAT FOR EACH UNIT. � M � W
<br /> CFM WG (1� HP�BHP DW WB DB WB ENT LVG (2) PRIOR TO ORDERING, CONTRACTOR TO COORDINATE WITH ELEVATOR MFR TO ENSURE UNIT CAN ADEQUATELY COOL THE ROOM. W
<br /> (MBH� (MBH) (MBH) (3) PROVIDE OPTIONAL CONDENSATE PUMP KIT. ~ �
<br /> AHU-1 HORIZONTAL 2,500 0.75 2/1.01 103 85 67 54 54 210 168 23 86.2 12.8 208V/3P 43 60 1225 AAON RN-008 (2)(3) � ;
<br /> NOTES: 1 ESP IS EXTERNAL TO UNIT CASING; DOES NOT INCLUDE CASING, CLEAN FILTER, WET COIL, OR AUX HEAT LOSSES. w
<br /> (2)PROVIDE HORIZONTAL DISCHARGE CURB WITH VIBRATION ISOLATION RAILS. o W
<br /> (3)PROVIDE COMPATIBLE THERMOSTAT AND ASSOCIATED CONTROL WIRING. �
<br /> �
<br /> ELECTRIC WALL HEATERS DIFFUSER SCHEDULE
<br /> HEATING ELECTRICAL CALLOUT DESCRIPTION AIRFLOW FACE SIZE,BASIS OF DESIGN
<br /> EQUIP N0. SERVICE MOUNTING/ DISCHARGE WEIGHT, LBS BASIS OF DESIGN (1)(2) RANGE, CFM IN
<br /> BTU/HR. VOLTAGE RG-1 CEILING RETURN GRILLE 0-1500 24x24 TITUS 350ZRL
<br /> EH-1 APT STUDIO WALL MOUNTED 6,000 208V/1P 1.75 10 KING PAW2022 RG-2 CEILING RETURN GRILLE 0-750 12x12 TITUS 350ZRL
<br /> EH-2 APT LIVING WALL MOUNTED 5,100 208V/1P 1.50 10 KING PAW2022
<br /> EH-3 APT BEDROOM WALL MOUNTED 3,400 208V/1 P 1.00 10 KING PAW2022 SG-1 SIDEWALL SUPPLY GRILLE 0-1500 12x12 TITUS 300RL
<br /> CD-1 CEILING SUPPLY GRILLE 0-1000 24x24 TITUS MCD
<br /> EWH-1 LEVEL 1 ENTRY VESTIBULE WALL MOUNTED 6,800 208V/1 P 2 10 KING KCF CD-2 CEILING SUPPLY GRILLE 0-500 12x12 TITUS MCD
<br /> EWH-2 FIRE ROOM WALL MOUNTED 6,800 208V/1P 2 10 KING KCF (3) �
<br /> NOTES: 1 INSTALL UNITS AS SHOWN AND AS RECOMMENDED BY THE MANUFACTURER IN COMPLIANCE WITH LOCAL CODES. �/�
<br /> (2) HEATER SHALL HAVE INTEGRA� T-STAT, UON. G� uJ
<br /> (3) SET T-STAT TO MAINTAIN 55'F.
<br /> U �
<br /> ENERGY RECOVERY VENTILATOR z �
<br /> Q p
<br /> FAN ELECTRICAL DIMENSIONS, INCHES = w
<br /> MOUNTING/ WEIGHT BASIS OF DESIGN
<br /> EQUIP N0. pISCHARGE AIRFLOW, ESP. IN MOTOR VOLTAGE AMP L W H ��BS� ��� � _
<br /> CFM WG HP
<br /> � U
<br /> ERV-1 HORIZONTAL 470 0.5 FHP 208V/1PH 2.8 42 45 15 148 LG ARVU053ZEAS2 SPLIT SYSTEM HEAT PUMP OUTDOOR UNIT (HP-X), SPLIT W = C �^
<br /> SYSTEM HEAT PUMP INDOOR UNIT (FCU-X), AND ENERGY �, �, c �,
<br /> ERV-2 HORIZONTAL 470 0.5 FHP 208V/1PH 2.$ 42 45 15 148 LG ARVU053ZEAS2 RECOVERY VENTILATOR (ERV-X) SCHEDULES UPDATED.
<br /> ERV-3 HORIZONTAL 470 0.5 FHP 208V/1PH 2.8 42 45 15 148 LG ARVU053ZEAS2 � DRAWN BY -_ ._..
<br /> ENERGY RECOVERY SYSTEM SHALL HAVE THE CAPABILITY TO PROVIDE A CHANGE IN THE ENTHALPY OF THE THE
<br /> NOTES: (1) OUTDOOR AIR SUPPLY OF NOT LESS THAN 50 PERCENT OF THE DIFFERENCE BETWEEN THE OUTDOOR AIR AND SHEET NUMBER
<br /> RETURN AIR ENTHALPIES, AT DESIGN CONDITIONS.