Laserfiche WebLink
November 12,2002 <br /> Edwin Pilapil <br /> Sparling <br /> 720 Olive Way <br /> Suite 1100 <br /> Seattle, WA 98101-1853 <br /> Re: Colby Campus 3rd Floor Backfill Permit# E0208-035, -036 <br /> Dear Edwin, <br /> In order to proceed with plan review of this project please address the following: <br /> • Please provide a fixture schedule. <br /> • Attachment CCC,used to calculate the load of Bus#5, is from an incorrect <br /> calculation. Please use figures from the Radiology 1 &2 project,dated June <br /> 2001. <br /> • As noted in the plan review process of the Radiology project the generators <br /> serving this area are at or near maximum capacity. This item must be <br /> substantively addressed before occupancy of the third floor will be permitted. • <br /> If you have any questions, please call me at 425-257-8810. Thanks. <br /> Sincerely, <br /> Tim Alaniz <br /> Electrical Inspector <br /> Fcc:left-Olsen.Rodgcrs Electric <br />