Laserfiche WebLink
F. Subsection 903.2.4 of the IFC, entitled "Group F-1," is hereby deleted and the following inserted in <br /> its place: <br /> 903.2.4 Group F-1 & Group F-2. An automatic Sprinkler system shall be provided throughout all <br /> buildings containing a Group F-1 or Group F-2 occupancies where one of the following conditions <br /> exists: <br /> 1. A Group F-1 or a Group F-2 fire area exceeds 6,000 square feet. <br /> 2. A Group F-1 fire area is located more than three stories above grade plane. <br /> 3. The combined area of all Group F-1 fire areas on all floors, including any mezzanines, <br /> exceeds 24,000 square feet. <br /> 4. A Group F-1 occupancy used for the manufacture of upholstered furniture or <br /> mattresses exceeds 2,500 square feet. <br /> G. Subsection 903.2.7 Item 1 of the IFC, entitled "Group M," is hereby amended: <br /> 903.2.7 Item 1. Replace the following language "12,000" with "6,000". <br /> H. Subsection 903.2.9 Item 1 of the IFC, entitled "Group S-1," is hereby amended: <br /> 903.2.9 Item 1. Replace the following language "12,000" with "6,000". <br /> I. Subsection 903.2.10 of the IFC, entitled "Group S-2 enclosed parking garages," is hereby deleted and <br /> the following inserted in its place: <br /> 903.2.10 Group S-2. An automatic sprinkler system shall be provided throughout all buildings <br /> containing a Group S-2 occupancy where one of the following conditions exist: <br /> 1. A Group S-2 fire area exceeds 6,000 square feet. <br /> 2. Where an enclosed parking garage is located beneath other groups. <br /> Exception: Enclosed parking garages located beneath Group R-3 occupancies. <br /> J. Subsection 903.2.13 of the IFC, entitled "Group B," is hereby added: <br /> 903.2.13 Group B. An automatic sprinkler system shall be provided throughout all buildings <br /> containing a Group B occupancy where a fire area that exceeds 6,000 square feet. <br /> K. Subsection 903.2.14 of the IFC, entitled "Group U," is hereby added: <br /> 903.2.14 Group U. An automatic sprinkler system shall be provided throughout all buildings <br /> containing a Group U occupancy where a fire area that exceeds 6,000 square feet. <br /> L. Subsection 903.3.1.2.1 of the IFC, entitled "Balconies and decks," is hereby deleted and the <br /> following inserted in its place: <br /> 903.3.1.2.1 Balconies and decks. Sprinkler protection shall be provided for exterior balconies, decks <br /> and ground floor patios of dwellings units and sleeping units. Sidewall sprinklers that are used to <br /> FIRE CODE ORDINANCE Page 18 of 39 <br />