0 • <br /> Drew Martin <br /> From: Drew Martin <br /> Sent: Monday, October 28, 2019 2:40 PM <br /> To: 'Dustin Long' <br /> Cc: 'peter@us-mechanical.com'; 'jason@therobsonco.com'; 'Frank Birchler' <br /> Subject: RE: Fire stopping at N2o closet for Dr.Jade Gan Permit#B1910-026 <br /> Dustin, <br /> The email follows our discussion regarding a proposed change to the gas cabinet to extend the walls to the roof <br /> sheathing and eliminate the protections for the exhaust and supply ducts. This is acceptable provided that the walls do <br /> not have structural framing crossing through them. The room essentially becomes a shaft extending up to the roof <br /> sheathing. If this change is made,you will need to redline the building drawings. Also,we will still need a detail for the <br /> pipe penetrations of the gas lines through the walls. If the design remains as is, let me know so I can verify some of the <br /> items we discussed regarding the ducts and whether the wrap and dampers are sufficient to meet the shaft <br /> requirements. The gas line penetrations details will still be required for this approach. <br /> Drew Martin, P.E.,S.E. <br /> LiAssociate Engineer—Commercial Plans Examiner I Permit Services <br /> 425.257.8813 13200 Cedar Street, 2nd Floor, Everett,WA 98201 <br /> EVERETT Hours: Monday—Friday 7:30am-12:OOpm and 1:OOpm-4:OOpm <br /> everettwa.gov I Facebook I Twitter <br /> Note:Emails and attachments sent to and from the City of Everett are public records and may be subject to disclosure pursuant to the Public <br /> Records Act. <br /> From: Drew Martin <br /> Sent: Monday, October 28, 2019 12:24 PM <br /> To: 'Dustin Long' <dlong@bigskynorthwest.com> <br /> Cc: peter@us-mechanical.com;jason@therobsonco.com; Frank Birchler<FBirchler@bigskynorthwest.com> <br /> Subject: RE: Fire stopping at N2o closet for Dr.Jade Gan Permit#B1910-026 <br /> The drawings need to include a typical detail(s)for the required construction of pipes penetrating the rated <br /> assemblies. The details should reference listings for the tested firestopping. <br /> Drew Martin,P.E.,S.E. <br /> LIAssociate Engineer—Commercial Plans Examiner I Permit Services <br /> 425.257.8813 13200 Cedar Street, 2nd Floor, Everett,WA 98201 <br /> EVERETT Hours: Monday—Friday 7:30am-12:OOpm and 1:OOpm-4:OOpm <br /> everettwa.gov I Facebook I Twitter <br /> Note:Emails and attachments sent to and from the City of Everett are public records and may be subject to disclosure pursuant to the Public <br /> Records Act. <br /> From: Dustin Long<dlong@bigskynorthwest.com> <br /> Sent: Friday, October 25,2019 1:34 PM <br /> To: Drew Martin<dmartin@everettwa.gov> <br /> Cc: peter@us-mechanical.com; iason@therobsonco.com; Frank Birchler<FBirchler@bigskynorthwest.com> <br /> Subject: Fire stopping at N2o closet for Dr.Jade Gan Permit#B1910-026 <br /> (72- <br />